Have a look at the manual American Water Heater 98 Gallon 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
21 PERIODIC MAINTENANCE VENTING SYSTEM INSPECTION At least once a year a visual inspection should be made of the venting system. You should look for: 1. Obstructions which could cause improper venting. The combustion and ventilation air flow must not be obstructed. 2. Damage or deterioration which could cause improper venting or leakage of combustion products. 3. Rusted flakes around top of water heater. Be sure the vent piping is properly connected to prevent escape of dangerous flue gases which could cause deadly asphyxiation. Obstructions and deteriorated vent systems may present serious health risk or asphyxiation. Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioner refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach and process chemicals are typical compounds which are potentially corrosive. If after inspection of vent system you found sooting or deterioration, something is wrong. Call the local gas utility to correct problem and clean or replace the flue and venting before resuming operation of water heater. BURNER INSPECTION Flood damage to a water heater may not be readily visible or immediately detectable. However, over a period of time a flooded water heater will create dangerous conditions which can cause DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. Contact a qualified installer or service technician to replace a flooded water heater. Do not attempt to repair the unit! It must be replaced! At least once a year a visual inspection should be made of the main burner and pilot burner, see Figure 19. Inspect burner fl ames through viewport. Flames should be very small with a blue haze and small amounts of yellow or orange at the edges. After several minutes of operation the burner screen may glow red. You should check for sooting. Soot is not normal and will impair proper combustion. Soot build-up indicates a problem that requires correction before further use. Turn “OFF” gas to water heater and leave off until repairs are made, because failure to correct the cause of the sooting can result in a fire causing death, serious injury, or property damage. Flame Characteristics Correct FlameRed/Orange FIGURE 19. Natural Gas (Low Nox)Burner Door Assembly Use brush on this surface BurnerPilot Assembly FIGURE 20. BURNER CLEANING If inspection of the burner shows that cleaning is required, turn the gas control knob clockwise ( ) to the “OFF” position, depressing slightly. NOTE: The knob cannot be turned from “PILOT” to “OFF” unless knob is depressed slightly. DO NOT FORCE. Check the burner to see if it’s dirty or clogged. The burner may be cleaned with a soft paint brush, see Figure 20. Do not use a wire brush or any tool that may damage the burner screen. Important: Do not use the burner if the burner screen is damaged. NOTE: Damage may be rips or holes in the burner screen. Discoloration is normal. HOUSEKEEPING Fire and Explosion Hazard Do not obstruct combustion air openings at the bottom of the water heater . Do not use or store flammable vapor products such as gasoline, solvents or adhesives in the same room or area near water heater or other appliance. C an cause serious injury or death. Vacuum around base of water heater for dust, dirt, and lint on a regular basis.
22 When checking the Temperature-Pressure Relief Valve operation, make sure that (1) no one is in front of or around the outlet of the Temperature-Pressure Relief Valve discharge line, and (2) that the water discharge will not cause any property damage, as the water may be extremely hot. Use care when operating valve as the valve may be hot. To check the relief valve, lift the lever at the end of valve several times, see Figure 21. The valve should seat properly and operate freely. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater and drain the water heater, see Draining And Flushing on page 24. Replace the Temperature-Pressure Relief Valve with a properly rated/sized new one, see Temperature-Pressure Relief Valve on page 11 for instructions on replacement. DISCHARGE PIPE TEMPERA TURE-PRESSURERELIEF VA LVE FIGURE 21. If the Temperature-Pressure Relief Valve on the water heater weeps or discharges periodically, this may be due to thermal expansion. NOTE: Excessive water pressure is the most common cause of Temperature-Pressure Relief Valve leakage. Excessive water system pressure is most often caused by “thermal expansion” in a “closed system.” See Closed Water Systems and Thermal Expansion on page 11. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion. Temperature-Pressure Relief Valve leakage due to pressure build up in a closed system that does not have a thermal expansion tank installed is not covered under the limited warranty. Thermal expansion tanks must be installed on all closed water systems. DO NOT PLUG THE TEMPERATURE-PRESSURE RELIEF VALVE OPENING. THIS CAN CAUSE PROPERTY DAMAGE, SERIOUS INJURY OR DEATH. Explosion Hazard Te mperature-Pressure Relief Valve must comply with ANSI Z21.22- CSA 4.4 and ASME code. Properly sized temperature- pressure relief valve must be installed in opening provided . Can result in overheating and excessive tank pressure . Can cause serious injury or death. RECOMMENDED PROCEDURE FOR PERIODIC REMOVAL OF LIME DEPOSITS FROM TANK TYPE COMMERCIAL WATER HEATERS The amount of calcium carbonate (lime) released from water is in direct proportion to water temperature and usage, see chart. The higher the water temperature or water usage, the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, heaters and on cooking utensils. INSTALLED IN SUITABLE AREA: To insure sufficient ventilation and combustion air supply, proper clearances from the water heater must be maintained. See Facts to Consider About The Location section. Combustible materials such as clothing, cleaning materials, or flammable liquids, etc. must not be placed against or adjacent to the water heater which can cause a fire. ANODE ROD INSPECTION Property Damage Hazard Av oid water heater damage. Inspection and replacement of anode rod required . CAUTION The anode rod is used to protect the tank from corrosion. Most hot water tanks are equipped with an anode rod. The submerged rod sacrifices itself to protect the tank. Instead of corroding the tank, water ions attack and eat away the anode rod. This does not affect water’s taste or color. The rod must be maintained to keep the tank in operating condition. Anode deterioration depends on water conductivity, not necessarily water condition. A corroded or pitted anode rod indicates high water conductivity and should be checked and/or replaced more often than an anode rod that appears to be intact. Replacement of a depleted anode rod can extend the life of your water heater. Inspection should be conducted by a qualified service technician, and at a minimum should be checked annually after the warranty period. Artificially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions. The use of a water softener may decrease the life of the water heater tank. The anode rod should be inspected after a maximum of three years and annually thereafter until the condition of the anode rod dictates its replacement. NOTE: Artificially softened water requires the anode rod to be inspected annually. The following are typical (but not all) signs of a depleted anode rod: • The majority of the rods diameter is less than 3/8”. • Significant sections of the support wire (approx. 1/3 or more of the anode rod’s length) are visible. TEMPERATURE-PRESSURE RELIEF VALVE TEST Burn hazard. Hot water discharge. Keep clear of Temperature- Pressure Relief V alve discharge outlet. It is recommended that the Temperature-Pressure Relief Valve should be checked to ensure that it is in operating condition every 6 months.
23 Lime accumulation not only reduces the life of the equipment but also reduces efficiency of the heater and increases fuel consumption. The usage of water softening equipment greatly reduces the hardness of the water. However, this equipment does not always remove all of the hardness (lime). For this reason it is recommended that a regular schedule for deliming be maintained. The time between cleaning will vary from weeks to months depending upon water conditions and usage. The depth of lime buildup should be measured periodically. Heaters equipped with cleanouts will have about 2” of lime buildup when the level of lime has reached the bottom of the cleanout opening. A schedule for deliming should then be set up,based on the amount of time it would take for a 1” buildup of lime. It is recommended that the water heater initially be inspected after 6 months. Example 1: Initial inspection after 6 months shows 1/2” of lime accumulation. Therefore, the heater should be delimed once a year. Example 2: Initial inspection after 6 months shows 2” of lime accumulation. Therefore, the heater should be delimed every 3 months. FIGURE 22. DELIMING SOLVENTS UN•LIME is recommended for deliming. UN•LIME is a patented food grade acid which is safe to handle and does not create the harmful fumes which are associated with other products. UN•LIME may be obtained from your dealer, distributor or water heater manufacturer. Order Part Number 9005416105, 1 gallon, packed 4 gallons per case or Part Number 9005417105, 5 gallon container. NOTE: Un•Lime is not available for use in Canada. Hydrochloric base acids are not recommended for use on glass lined tanks. Observe handling instructions on label of product being used. TANK CLEANOUT PROCEDURE The following practices will ensure longer life and enable the unit to operate at its designed efficiency: 1. Once a month the heater should be flushed. Open the drain valve and allow two gallons of water to drain from the heater. Inlet water valve should remain open to maintain pressure in tank. 2. A cleanout opening is provided for periodic cleaning of the tank. Gas must be shut off and heater drained before opening cleanout. To clean heater through cleanout opening, proceed as follows: 1. Drain heater. 2. Remove outer cover plate from lower side of heater jacket. 3. Remove six (6) hex head screws securing tank cleanout plate and remove plate. 4. Remove lime, scale, or sediment using care not to damage the glass lining. 5. Inspect cleanout plate gasket, if new gasket is required, see replacement parts list for item number. 6. Install cleanout plate. Be sure to draw plate up tight by tightening screws securely. 7. Replace outer jacket cover plate. FIGURE 23.9. In some water areas the sediment might not be removed by this method and may result in the water heater making rumbling or boiling noises. To dissolve and remove these more stubborn mineral deposits, UN•LIME Professional Delimer should be used. DELIMING USING FLO-JUG METHOD UN•LIME in the 5 gallon size is recommended for deliming of all models. Contact your local dealer, distributor or, water heater manufacturer. PREPARE THE WATER HEATERTo delime the water heater using the Flo-Jug method, first prepare the heater for deliming. Explosion Hazard Flammable hydrogen gases may be present . Keep all ignition sources away from faucet when turning on hot water. Do not smoke or have open flame or sparks in vicinity of heater. Do not mix UN•LIME with other chemicals. Do not allow contact with magnesium, aluminum or galvanized metals. Chemical Hazard • Product contains phosphoric acid. • Keep out of reach of children. • Use rubber or neoprene gloves. UN•LIME contains phosphoric acid. In case of external contact, flush with cool water. If irritation persists, get medical attention. If swallowed, give 1 or 2 glasses of water or milk and call physician. Get immediate medical attention for eyes. Keep out of reach of children. NOTE: THE USE OF RUBBER OR NEOPRENE GLOVES IS RECOMMENDED, ESPECIALLY IF YOU HAVE ANY OPEN SORES OR CUTS TO AVOID UNNECESSARY IRRITATION OR DISCOMFORT. 1. Turn off fuel and/or power supply to heater. Also, turn off power to any electrical device or equipment, which is attached, or part of the system. 2. Open hot water side of faucet closest to heater and allow water to run until it is cool enough to handle safely.
24 3. Close cold water inlet valve to heater. 4. Connect hose to drain valve at bottom of heater and start draining heater into suitable floor drain area. 5. Remove relief valve while heater is draining. NOTE: Do not replace relief valve until deliming is completed. Relief valve opening will also act as a vent in case of possible contact between the delimer and the anode rod(s), which may produce flammable hydrogen-air mixtures. 6. If relief valve appears to be limed-up, place it in a clean glass or plastic container adequate in size so that you can pour enough UN•LIME® into the container to cover the valve and allow space for foaming. When foaming stops, run fresh cool water into the container and rinse the relief valve for a few minutes. 7. If heater does not drain completely after a reasonable length of time, turn off the main water supply valve to stop water from entering the tank due to a by-pass problem or defective cold water inlet valve. Also, check for clogged drain valve opening. Heater must be completely drained before introducing UN•LIME. 8. Remove the cleanout cover and place a clean plastic bucket next to the cleanout opening. Partially open the cold water inlet valve to allow time to accomplish the following and then close the valve. While the water is being run through the tank, insert a stiff wire, copper tube flattened at one end or an opened wire coat hanger through the cleanout opening and scrape out any loose deposits of scale or sediment. This is an economical way to avoid unnecessary usage of the deliming solution. Repeat the opening and closing of the cold water inlet valve as necessary but be sure the heater is completely drained when ready to introduce the UN•LIME. Upon completion, reinstall the cleanout cover and use a new cleanout cover gasket (part number 9004099215). Remove the drain valve. 9. Install the long plastic male adapter insert fitting into the drain valve opening of heater after applying Teflon tape or paste to threads. Tighten firmly by hand and use wrench or adjustable pliers to check for secure connection. Do not over tighten to avoid damage to threads and fittings. PREPARE THE UP-N-DOWN TRANSFER KITThe next step is the preparation on the Up-N-Down Transfer Kit, if you have not already done so: 1. With the 5 gallon Up-N-Down container in the vertical position, unscrew the plastic vent cap in the handle and pierce the plastic membrane over the vent boss under the cap to allow the container to vent. Note: If your container does not have the vent cap and vent boss, drill a 3/16” (4.76mm) hole in the handle. When you have finished deliming you will be able to plug this drilled vent with the stainless steel screw that is supplied with the kit. 2. Remove the container’s cap and cut plastic membrane located in the 3/4” IPT opening in cap. Take care to not damage the threads. 3. Find the 3/4” male adapter, apply teflon tape to the threaded end and screw it into the 3/4” IPT opening in the cap. 4. Put cap with male adapter back on the container and slide 3/4” hose over end of male adapter and fasten in place using hose clamp provided. DELIME USING FLO-JUG METHOD5. Slide the hose clamp over end of hose and slide hose over the male adapter in the water heater drain opening and secure in place using hose clamp. 6. Lift container to the “Pour” Position being careful to keep the vent in the handle above the liquid level and pour the UN•LIME into the heater. 7. Lower container, you may have to place the container on its empty carton to prevent the UN•LIME from flowing back into the container. 8. Let UN•LIME remain in the heater for 5 minutes and then lower the container to the “Drain” Position. 9. Deliming activity is indicated by foaming on the surface of the UN•LIME. If there is deliming activity, repeat steps 6 thru 8. Normally, lime removal will be completed within one hour. Severe build-up of lime may take longer than an hour to complete descaling. Note: To check UN•LIME for continued use, place some scale or white chalk in a glass with a small amount of UN•LIME. If the material is vigorously dissolved by the UN•LIME, it can be reused; if not, the UN•LIME should be replaced. If the temperature-pressure relief valve on the appliance weeps or discharges periodically, this may be due to thermal expansion. You may have a check valve installed in the water line or a water meter with a check valve. Consult your local water supplier or service technician for further information. Do not plug the temperature-pressure relief valve. DRAINING AND FLUSHING It is recommended that the water heater storage tank be drained and flushed every 6 months to reduce sediment buildup. The water heater should be drained if being shut down during freezing temperatures. See Installation Considerations in this manual for the location of the water heater components described below. Burn harzard. Hot water discharge. Keep hands clear of drain valve discharge. TO DRAIN THE WATER HEATER STORAGE TANK:1. Turn off the gas supply at the Main Gas Shutoff Valve if the water heater is going to be shut down for an extended period. 2. Ensure the cold water inlet valve is open. 3. Open a nearby hot water faucet and let the water run until the water is no longer hot. 4. Close the cold water inlet valve to the water heater. 5. Connect a hose to the water heater drain valve and terminate it to an adequate drain. 6. Open the water heater drain valve and allow all the water to drain from the storage tank. 7. Close the water heater drain valve when all water in the storage tank has drained. 8. Close the hot water faucet opened in Step 4. 9. If the water heater is going to be shut down for an extended period, the drain valve should be left open. TO FLUSH THE WATER HEATER STORAGE TANK:1. Ensure the cold water inlet valve is open. 2. Open a nearby hot water faucet and let the water run until the water is no longer hot. Then close the hot water faucet. 3. Connect a hose to the drain valve and terminate it to an adequate drain. 4. Ensure the drain hose is secured before and during the entire flushing procedure. Flushing is performed with system water pressure applied to the water heater. 5. Open the water heater drain valve to flush the storage tank. 6. Flush the water heater storage tank to remove sediment and allow the water to flow until it runs clean. 7. Close the water heater drain valve when flushing is completed. 8. Remove the drain hose. 9. Fill the water heater - see Filling The Water Heater in this manual. 10. Turn on the gas supply to the water heater at the Main Gas Shutoff Valve. 11. Allow the water heater to complete several heating cycles to ensure it is operating properly. SERVICE Before calling for repair service, read the “Start Up Conditions” and “Operational Conditions” found in the “For Your Information” section of this manual. If a condition persists or you are uncertain about the operation of the water heater contact a service technician. If you are not thoroughly familiar with gas codes, your water heater, and safety practices, contact your gas supplier or qualified installer to check the water heater. Use the ”Leakage Checkpoints” guide to check a “Leaking” water heater. Many suspected “Leakers” are not leaking tanks. Often the source of the water can be found and corrected. Read this manual first. Then before checking the water heater make sure the gas supply has been turned “OFF”, and never turn the gas “ON” before the tank is completely full of water. Never use this water heater unless it is completely filled with water. To prevent damage to the tank, the tank must be filled with water. Water must flow from the hot water faucet before turning “ON” gas to the water heater.
25 LEAKAGE CHECKPOINTS A. Water at the draft hood is water vapor which has condensed out of the combustion products. This is caused by a problem in the vent. Contact the gas utility. B. *Condensation may be seen on pipes in humid weather or pipe connections may be leaking. C. *The anode rod fitting may be leaking. D. Small amounts of water from temperature-pressure relief valve may be due to thermal expansion or high water pressure in your area. E. *The temperature-pressure relief valve may be leaking at the tank fitting. F. Water from a drain valve may be due to the valve being slightly opened. G. *The drain valve may be leaking at the tank fitting. H. Combustion products contain water vapor which can condense on the cooler surfaces of the tank. Droplets form and drip onto the burner or run on the floor. This is common at the time of start-up after installation and when incoming water is cold. I. Water in the water heater bottom or on the floor may be from condensation, loose connections, or the relief valve. DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken. Leakage from other appliances, water lines, or ground seepage should also be checked. * To check where threaded portion enters tank, insert cotton swab between jacket opening and fitting. If cotton is wet, follow “Draining and Flushing” instructions in the “Periodic Maintenance” section and then remove fitting. Put pipe dope or teflon tape on the threads and replace. Then follow “Filling the Water Heater” instructions in the Installation Requirements section.
26 TROUBLESHOOTING GUIDELINES These guidelines should be utilized by a qualified service agent. Problem Cause Solution WATER LEAKSImproperly sealed, hot or cold supply connection, relief valve, drain valve, or thermostat threads. Tighten threaded connections. Leakage from other appliances or water lines. Inspect other appliances near water heater. Condensation of flue products. Refer to CONDENSATION. LEAKING T&P VALVE Thermal expansion in closed water system. Install thermal expansion tank (DO NOT plug T&P valve). Improperly seated valve. Check relief valve for proper operation (DO NOT plug T&P valve). SMELLY WATER High sulfate or mineral content in water supply. Drain and flush heater thoroughly, then refill. Bacteria in water supply. Chlorinate or aerate water supply. PILOT WILL NOT LIGHT Gas control knob not positioned correctly. Refer to LIGHTING INSTRUCTIONS. Main gas supply off. Turn on main gas shutoff valve. Thermocouple malfunction. Replace pilot assembly and/or thermocouple. BURNER WILL NOT STAY LIT Thermocouple malfunction. Replace pilot assembly and/or thermocouple. Defective Gas Control. Replace Gas Control. PILOT OUTAGE Dirty pilot burner. Clean pilot assembly. Thermocouple malfunction. Replace pilot assembly and/or thermocouple. Defective Gas Control. Replace Gas Control. Thermocouple tip is not in contact with pilot flame. Insert thermocouple correctly. NOT ENOUGH HOT WATER Heater not lit or thermostat not on. Refer to LIGHTING INSTRUCTIONS. Thermostat set too low. Refer to TEMPERATURE REGULATION. Heater undersized. Reduce hot water use. Low gas pressure. Contact your gas supplier. Incoming water is unusually cold. Allow more time for heater to re-heat. Leaking hot water pipes or fixtures. Have plumber check and repair leaks. High temperature limit switch activated. Contact a service technician to determine cause. WATER TOO HOT Thermostat set too high. Refer to TEMPERATURE REGULATION. WATER HEATER SOUNDSCondensation dripping on burner. Refer to CONDENSATION. SIZZLING OR RUMBLING Sediment or calcium in bottom of heater tank. Clean sediment from tank. Refer to DRAINING instructions in Maintenance section of manual. SOOTING Improper combustion. No adjustment available. Contact a service technician to determine cause. VENT GAS ODORS Lack of supply air. Contact a service technician to determine cause. Improperly installed vent piping. Downdraft. Poor combustion.
27 WATER PIPING DIAGRAMS October 2009 | Printed in U.S.A. | © A. O. Smith For Technical Information and Automated Fax Service, call 800-527-1953 or visit www.hotwater.com. AOSCG61130 | PAGE 1 of 1 A. O. Smith Corporation reserves the right to make product changes or im\ provements without prior notice.NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed press\ ure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage.4. The Tank Temperature Control should be wired to and control the pump between the w\ ater heater(s) and the storage tank(s). 5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.SINGLE FLUE - (1 UNIT) LEGEND TEMPERAT URE & PRESSURE RELIEF VA LV EPRESSURE RELIEF VA LV ECIRCULATING PUMPTANK TEMPERAT URE CONTROLDRAIN FULL PORT BALL VA LV E TEMPERATURE GAGEWATER FLOW SWITCH CHECK VA LV E WARNING: THIS DRAW ING SHOWS SUGGESTEDPIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. FINISHED FLOOR HOTC OLD COLD EXPANSION TANK COLD WATER SUPPLY PIPE T&P TO OPEN DRAIN
28October 2009 | Printed in U.S.A. | © A. O. Smith For Technical Information and Automated Fax Service, call 800-527-1953 or visit www.hotwater.com. AOSCG61140 | PAGE 1 of 1 A. O. Smith Corporation reserves the right to make product changes or im\ provements without prior notice.NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed press\ ure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the w\ ater heater(s) and the storage tank(s). 5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.SINGLE FLUE - (1 UNIT) WITH VERTICAL STORAGE TANK LEGEND TEMPERAT URE & PRESSURE RELIEF VA LV EPRESSURE RELIEF VA LV ECIRCULATING PUMPTANK TEMPERAT URE CONTROLDRAIN FULL PORT BALL VA LV E TEMPERATURE GAGEWATER FLOW SWITCH CHECK VA LV E WARNING: THIS DRAW ING SHOWS SUGGESTEDPIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. FINISHED FLOOR HOTC OLD EXPANSION TANK COLD WATER SUPPLY HOT WATER RETURN FROM FIXTURES HOT WATER TO FIXTURES ALT. COLD WATER CONNECTION PIPE T&P TO OPEN DRAIN
29October 2009 | Printed in U.S.A. | © A. O. Smith For Technical Information and Automated Fax Service, call 800-527-1953 or visit www.hotwater.com. AOSCG61150 | PAGE 1 of 1 A. O. Smith Corporation reserves the right to make product changes or im\ provements without prior notice.NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed press\ ure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the w\ ater heater(s) and the storage tank(s). 5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.SINGLE FLUE - (1 UNIT) WITH HORIZONTAL STORAGE TANK LEGEND TEMPERAT URE & PRESSURE RELIEF VA LV EPRESSURE RELIEF VA LV ECIRCULATING PUMPTANK TEMPERAT URE CONTROLDRAIN FULL PORT BALL VA LV E TEMPERATURE GAGEWATER FLOW SWITCH CHECK VA LV E WARNING: THIS DRAW ING SHOWS SUGGESTEDPIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. FINISHED FLOOR HOTC OLD EXPANSION TANKCOLD WATER SUPPLYHOT WATER RETURN FROM FIXTURES HOT WATER TO FIXTURES ALTERNATE LOCATION PIPE T&P TO OPEN DRAIN
30October 2009 | Printed in U.S.A. | © A. O. Smith For Technical Information and Automated Fax Service, call 800-527-1953 or visi t www.hotwater.com. AOSCG61160 | PAGE 1 of 1 A. O. Smith Corporation reserves the right to make product changes or im\ provements without prior notice.NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed press\ ure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the w\ ater heater(s) and the storage tank(s).5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.SINGLE FLUE - (1 UNIT) WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE & PRESSURE RELIEF VALVEPRESSURE RELIEF VALVECIRCULATING PUMPTANK TEMPERATURE CONTROLDRAIN FULL PORT BALL VALVETEMPERATURE GAGEWATER FLOW SWITCH CHECK VALVE WARNING: THIS DRAWING SHOWS SUGGESTEDPIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. HOT WATER RETURN MINIMUM 10´´ to 12´´ HOT WATER OUTLET TEMPERED WATER RETURN TEMPERED WATER OUTLET COLD WATER SUPPLY LINE TEMPERATURE CONTROL COLD HOT EXPANSION TANK PIPE T&P TO OPEN DRAIN 219332_AOSCG61160.indd 1 12/9/09 11:24:14 AM