Home > AirComm Corporation > Air Conditioner > AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a

AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a

    Download as PDF Print this page Share this page

    Have a look at the manual AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 24   
     
     CONDITION  
    SERVICE PRESSURE 
    GAUGE READING  
     PROBABLE CAUSE  
    CORRECTIVE ACTION 
    FAULTY 
    COMPRESSOR 
     
    Insufficient cooling. SUCTION  
    PRESSURE:  much 
    above normal 
     
     
    DISCHARGE 
    PRESSURE: much  
    below normal Internal problem in 
    compressor, or damaged 
    gasket and valve. 1. Discharge system. 
    2. Remove and 
    check 
    compressor. 
    3. Repair or 
    replace 
    compressor. 
    4. Check oil level. 
    5. Replace receiver drier. 
    6. Evacuate and 
    charge 
    system. 
     
    TOO MUCH OIL IN 
    SYSTEM (Excessive) 
     
    Insufficient cooling. 
     
     
     SUCTION  
    PRESSURE:  above 
    normal 
     
     
    DISCHARGE 
    PRESSURE:  above 
    normal 
     Too much oil circulates with 
    refrigerant, causing the 
    cooling capacity of the 
    system to be reduced. Refer to Oil Level Check 
    for correcting oil level. 
     
     
     
      
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 25   
    5.4 Compressor Troubleshooting 
     
    A. General 
     
    The following procedures are used for troubleshooting the compressor. 
     
    B. Tools and Equipment 
     
     
    Designation  
    Ref. No.  
    Qty  
    Remarks 
     
     
    Service Pressure Gauge  
    Comm. Avail.  
    1  
    None 
     
    DC Power Supply  
      
    A/R  
    None 
     
    C. Compressor Troubleshooting Procedures 
     
    With the air conditioning system operating, do any of the following conditions 
    occur: 
     
    NOTE:  Always attach a service gauge set to the system prior to trouble 
    shooting, to insure proper refrigerant charge is present. 
     
    Trouble
     Probable Cause Correction 
    1. Unusually high suction 
    pressure with low 
    discharge pressure. (a) Internal problem with 
    compressor body. 
    (b) Faulty Expansion 
    valve 
     (a) Replace compressor. 
     
    (b) Replace expansion 
    valve 
    2. Unusually low suction 
    and discharge pressure. System or compressor 
    leak. 
     Repair leak or replace 
    compressor 
    3. High compressor 
    discharge pressure. (a) Air exhaust duct 
    collapsed or restricted. 
    (b) Refrigerant 
    overcharge. (a) Inspect/replace 
    exhaust duct. 
    (b) Discharge refrigerant 
    until only occasional 
    bubble are present in 
    sight glass (if so 
    equipped) or until 
    pressures are with range 
    (ref Table A.1). 
      
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 26  4. Rough running.  Internal compressor 
    problem. 
     Replace compressor. 
     
    6.0 CHECKS 
     
    6.1 General 
     
    The following procedures are used to perform typical maintenance checks for air 
    conditioning system refrigerant leaks, refrigerant charge and compressor oil 
    level. 
     
    CAUTION:  Do not operate air conditioning system with condenser air outlet 
    blocked. 
     
    A. Tools and Equipment 
     
     
    Designation  
    Ref. No.  
    Qty  
    Remarks 
     
     
    Service Pressure Gage  
    Comm. Avail.  
    1  
    None 
     
    Oil Dipstick  
    Make from metal 
    wire.  
    1  
    See Fig. 3. 
     
    Electronic Leak Detector  
    Comm. Avail.  
    A/R  
    Type H-10G 
     
    Polyolester Oil  
    Comm. Avail.  
    A/R  
    Viscosity ISO 68 
     
    6.2  Refrigerant Level Check 
     
    A.  Connect service cart with gages to the system 
    B.  Select air conditioning system to ON. 
    C.  Set the temperature selector (if so equipped) to the full cold position. 
    D.  Set the blower speed to the maximum position. 
    E.  Run system for five (5) minutes minimum. 
    F. Check that pressures are within range per Table A.1.  Add or recover 
    refrigerant as required until pressures are within range. If so equipped, a less 
    accurate method is to check the sight glass for presence of bubbles. Add 
    refrigerant until bubbles disappear.   
    NOTE: Accurate readings are difficult to obtain when ambient temperatures are 
    below 65F.  Always re-check refrigerant level when ambient temperature is 
    above 65F for proper level.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 27   
    6.3  Refrigerant System Leakage Check 
     
    A.  The system leakage check is to be performed in an area with an ambient 
    temperature of 65F or above. 
    B.  Install service pressure gage to low and high pressure R-134a service 
    valves. 
    C.  Check for system pressure of approximately 64 psig or above.  The low 
    pressure gage may be used to check system pressure.  If system 
    pressure is below 64 psig, a small amount of refrigerant R-134a may be 
    added to obtain the required pressure. 
    D.  On systems that have not been operated for 2 weeks or longer, operate 
    the system for a minimum of 15 minutes.  This will lubricate the 
    compressor shaft seal and ensure a more accurate leakage check of the 
    shaft seal. 
    E.  With the system off, and using a type H-10G electronic leak detector or 
    equivalent, check all connections, compressor shaft seal, and fabricated 
    components for leakage.  No leakage is acceptable 
     
    6.4  Compressor Oil Level Check 
     
    NOTE: It is not necessary to check the compressor oil level during routine 
    maintenance.  It only needs to be checked when a system component 
    is replaced or when incorrect oil level is suspected.  Only polyolester oil 
    viscosity grade ISO 68 should be used. 
     
    A.  Operate air conditioning system for 10 minutes.  This will collect as much 
    oil as possible in the compressor. 
    B. Perform flushing procedure. 
      
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page A-1   
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
    APPENDIX A 
      
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page A-2   
    A-1.0 CHARGE PRESSURES 
     
    A-1.1 Normal Range 
     
    OAT
    65 25 35 135 155
    70 35 40 145 160
    75 35 45 150 170
    80 40 50 175 210
    85 45 55 225 250
    90 45 55 250 270
    95 50 55 275 300
    100 50 55 315 325
    105 50 55 330 335
    110 50 55 340 345Normal range for pressuresSuction (psig) Discharge (psig)
     
    Table A.1 
     
    A-1.2 Interpreting Readings 
     
    Suction Discharge
    Low Low
    Low Hi gh
    Hi gh Low
    Hi gh Hi ghNeeds service.  Possible 
    faulty compre ssor.
    Overcharged.  Recover 
    refrigerant until pressures are 
    in range. Interpreting Pressure Re adingsAction Required
    Add re fri ge rant until 
    pressures are in range.
    Need service. Possible 
    expansion valve blockage
     
    Table A.2  
    						
    All AirComm Corporation manuals Comments (0)

    Related Manuals for AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a