Home
>
AirComm Corporation
>
Air Conditioner
>
AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a
AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a
Have a look at the manual AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
TR-134 Revision J September 13, 2013 Page 14 4.3 Plumbing System Maintenance Procedures A. General The following procedures are used to perform typical maintenance on the air conditioning system plumbing. Procedures are provided for hose or fitting replacement. New ACC air conditioning systems use swaged hose fittings. Some systems that have been converted from R12 to R134a refrigerant use Barb Lok hose fittings. Fittings are either o-ring type or use flared connections. B. Tools and Equipment Designation Ref. No. Qty Remarks R134a Compatible Hose Swaging Kit Available from ACC 1 None Sharp Knife Comm. Avail. 1 None Impact Wrench Comm. Avail. 1 None Light Machine Oil Comm. Avail. A/R None Polyolester Oil Comm. Avail. A/R Viscosity ISO 68 Sealant ES49000-1 A/R None C. Hose or Fitting Replacement (Swaged Hose Fittings) NOTE: If it is found that a hose or fitting has a leak, it will be necessary to replace the entire hose assembly. Follow the Hose Swaging Instruction below: 1. Hose should only be cut with a sharp knife. (Note: Use of serrated blades or saws to cut hose will leave particles that can contaminate system.) 2. Insert the proper size die in the swaging tool. 3. Insert fitting in swaging tool so that it is centered in the die and hand tighten. 4. Insert hose in fitting until it bottoms (Note: Indicating hole is in base of fitting). 5. Using impact wrench, tighten nut until die housings contact. (Note: It is important to keep hose pushed into fitting while swaging). 6. Reverse impact and back off nut until housing contacts rubber stops.
TR-134 Revision J September 13, 2013 Page 15 D. Hose or Fitting Replacement (Barb-Lok Hose Fittings) NOTE: If it is found that a hose or fitting has a leak, it will be necessary to replace the entire hose assembly. Follow the Hose Barb-Lok Instruction below: 1. Hose should only be cut with a sharp knife. (Note: Use of serrated blades or saws to cut hose will leave particles that can contaminate system.) 2. Slide the Barb-Lok socket onto the hose fitting with the round end towards the stop. Apply a few drops of machine oil to nut to ease installation. (Note: Do not lubricate fitting barbs.) 3. Push hose on barbed end of fitting until all barbs are covered. Hose end shall be about 1/8 inch past last barb. 4. Hold hose in place. Pull socket towards hose and thread onto hose counter-clockwise. Use wrench to turn socket onto hose. The round end of the socket should be 0.82 inch (or one socket length) from the push-on hose stop. 5. About 1/8 inch of hose should protrude past the socket. This may be trimmed to improve the appearance of the hose assembly. E. Connection to Components - O-Ring Replacement 1. Place the appropriate o-ring over the tube O end of the fitting. 2. Lubricate o-ring with polyolester oil or sealant prior to assembly. 3. Apply sealant to all fitting mating surfaces prior to assembly. F. Recommended standard dry torque specifications. Thread Size O-Ring Flare FT-Lb N-M FT-Lb N-M 5/8” 11-13 15-18 20-25 27-34 3/4 15-20 20-27 35-40 47-54 7/8” 21-27 29-37 50-60 68-81 1 1/16” 28-33 38-45 70-80 95-108 G. Connection to Components - Flared Fittings 1. Apply sealant to all fitting mating surfaces prior to assembly. H. Receiver/Drier Replacement 1. Replace receiver/drier whenever the compressor is replaced or when the air conditioning system plumbing is left open to the atmosphere for a period of time greater than 10 minutes.
TR-134 Revision J September 13, 2013 Page 16 4.4 Coil Cleaning Maintenance Procedures A. General The following procedure is used for cleaning either evaporator or condenser coil. B. Tools and Equipment Designation Ref. No. Qty Remarks Vacuum Cleaner Comm. Avail. 1 None Coil Cleaner Comm. Avail. A/R Non-acid based C. Coil Cleaning Procedure 1. Use vacuum cleaner to remove large debris from upstream and downstream coil faces. 2. Spray coil cleaner on both coil faces. Wash off with water. 3. Allow coil to dry thoroughly prior to additional maintenance.
TR-134 Revision J September 13, 2013 Page 17 4.5 Expansion Valve Removal and Installation A. General The following procedure is used to remove or install the air conditioning system expansion valve. B. Tools and Equipment Designation Ref. No. Qty Remarks Sealant ES49000-1 A/R None Polyolester Oil Comm. Avail. A/R Viscosity ISO 68 C. Expansion Valve Replacement 1. Discharge system in accordance with Refrigerant Servicing section. 2. Disconnect liquid line from inlet of expansion valve, and cap. Remove the thermal sense bulb from its clamp located on the suction tube of the evaporator and carefully remove insulation covering bulb. 3. Disconnect the fitting that connects the valve to the coil and plug coil fitting. 4. Install new expansion valve and o-ring (for o-ring fitting systems) in the reverse order. 5. Lubricate o-ring with polyolester oil or apply sealant to fitting mating surfaces prior to assembly. 6. Install the thermal sense bulb such that it makes contact with the suction tube along its entire length. When viewing the suction tube extruding out of the evaporator, the sense bulb should be in the three or nine o’clock position (Figure 4-1 and 4-2). Attach the sensor bulb using two zip ties. Insulate the bulb and expansion valve thoroughly with insulation (Figure 4- 3).
TR-134 Revision J September 13, 2013 Page 18 Figure 4-1 Figure 4-2 Figure 4-3
TR-134 Revision J September 13, 2013 Page 19 4.6 Compressor Maintenance Procedures A. General The following procedure is used whenever the compressor is replaced or contamination is suspected. B. Tools and Equipment Designation Ref. No. Qty Remarks None - - None C. Compressor Replacement Flush system and replace compressor per the Refrigerant Servicing section.
TR-134 Revision J September 13, 2013 Page 20 5.0 TROUBLESHOOTING 5.1 General The procedures below present troubleshooting charts for the air conditioning system and the compressor. A diagnoses chart is presented for insufficient air conditioning system cooling. The performance characteristics of an aircrafts particular system are dependent upon the design parameters of the systems components. The performance of any one particular system varies with ambient temperature and humidity. The information below presents possible air conditioning system problems and solutions. CAUTION: Do not operate air conditioning system with condenser air outlet blocked. 5.2 Air Conditioning System Diagnosis Chart Figure 3 shows a procedure for diagnosing air conditioning system problems. Following this procedure will expedite the troubleshooting process.
TR-134 Revision J September 13, 2013 Page 21 Figure 3. Air Conditioning System Diagnosis Chart
TR-134 Revision J September 13, 2013 Page 22 5.3 Air Conditioning System Troubleshooting CONDITION SERVICE PRESSURE GAUGE READING PROBABLE CAUSE CORRECTIVE ACTION INSUFFICIENT REFRIGERANT CHARGE Insufficient cooling. Bubbles appear in sight glass (if so equipped). SUCTION PRESSURE: below normal DISCHARGE PRESSURE: below normal Refrigerant is low, or leaking a little. 1. Leak test. 2. Repair leak. 3. Charge system. Evacuate as necessary and recharge system. ALMOST NO REFRIGERANT No cooling action. A lot of bubbles or something like mist appears in sight glass (if so equipped). SUCTION PRESSURE: much below normal DISCHARGE PRESSURE: much below normal Serious refrigerant leak. Stop compressor immediately. 1. Leak test. 2. Discharge system. 3. Repair Leak(s). 4. Replace receiver drier, if necessary. 5. Check oil level. 6. Evacuate and recharge system. FAULTY EXPANSION VALVE a) Slight cooling. Sweating or frosted expansion valve outlet. b) Insufficient cooling. Sweated suction line. c) No cooling. Sweating or frosted suction line. a) SUCTION PRESSURE: below normal DISCHARGE PRESSURE: below normal b) SUCTION PRESSURE: above normal DISCHARGE PRESSURE: above normal c) SUCTION PRESSURE: above normal DISCHARGE PRESSURE: below normal a) Expansion valve restricts refrigerant. Or, expansion valve is clogged. Or, expansion valve is inoperative. Or, valve stuck closed. Thermal bulb has lost charge. b) Expansion valve allows too much refrigerant through evaporator. Sensing bulb on suction line not well insulated or properly attached to line. c) Faulty expansion valve. a) 1. Discharge system. 2. Replace valve. 3. Evacuate and recharge system. b) 1. Check valve for operation. If suction side does not show a pressure decrease, replace valve. 2. Check security and insulation on sensing bulb. c) 1. Discharge system. 2. Replace valve. 3. Evacuate and recharge system.
TR-134 Revision J September 13, 2013 Page 23 CONDITION SERVICE PRESSURE GAUGE READING PROBABLE CAUSE CORRECTIVE ACTION AIR IN SYSTEM Insufficient cooling. Sight glass (if so equipped) shows occasional bubbles. SUCTION PRESSURE: above normal DISCHARGE PRESSURE: above normal Air mixed with refrigerant in system. 1. Discharge system. 2. Replace receiver drier. 3. Evacuate and charge system. MOISTURE IN SYSTEM After operation for a while, pressure on suction side may show vacuum pressure reading. During this condition, discharge air will be warm. As warning of this, reading shows approx 6 psi oscillation. SUCTION PRESSURE: below normal DISCHARGE PRESSURE: above normal Drier is saturated with moisture. Moisture has frozen at expansion valve. Refrigerant flow is restricted. 1. Discharge system. 2. Replace receiver drier (twice if necessary). 3. Evacuate system completely. (Repeat 30 minute evacuating three times.) 4. Recharge system. FAULTY CONDENSER Insufficient cooling. Bubbles appear in sight glass of drier. Suction line is very hot. SUCTION PRESSURE: above normal DISCHARGE PRESSURE: above normal Condenser air or refrigerant flow is restricted. Check condenser for dirt accumulation. Check for refrigerant overcharge. If pressure remains high in spite of all above actions taken, remove and inspect the condenser for possible oil clogging. HIGH PRESSURE LINE BLOCKED Insufficient cooling. Frosted high pressure liquid line. SUCTION PRESSURE: much below normal DISCHARGE PRESSURE: much above normal Drier clogged, or restriction in high pressure line. 1. Discharge system. 2. Remove receiver drier and replace it. 3. Evacuate and charge system.