Home > AirComm Corporation > Air Conditioner > AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a

AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a

    Download as PDF Print this page Share this page

    Have a look at the manual AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 14   
    4.3  Plumbing System Maintenance Procedures 
     
    A. General 
     
    The following procedures are used to perform typical maintenance on the air 
    conditioning system plumbing.  Procedures are provided for hose or fitting 
    replacement.  New ACC air conditioning systems use swaged hose fittings.  
    Some systems that have been converted from R12 to R134a refrigerant use Barb 
    Lok hose fittings.  Fittings are either o-ring type or use flared connections. 
     
    B. Tools and Equipment 
     
     
    Designation  
    Ref. No.  
    Qty  
    Remarks 
     
     
    R134a Compatible Hose Swaging 
    Kit  
    Available from 
    ACC  
    1  
    None 
     
    Sharp Knife  
    Comm. Avail.  
    1  
    None 
     
    Impact Wrench  
    Comm. Avail.  
    1  
    None 
     
    Light Machine Oil  
    Comm. Avail.  
    A/R  
    None 
     
    Polyolester Oil  
    Comm. Avail.  
    A/R  
    Viscosity ISO 68 
     
    Sealant  
    ES49000-1  
    A/R  
    None 
     
    C.  Hose or Fitting Replacement (Swaged Hose Fittings) 
        
    NOTE:  If it is found that a hose or fitting has a leak, it will be necessary to 
    replace the entire hose assembly.  Follow the Hose Swaging Instruction below: 
     
    1.  Hose should only be cut with a sharp knife.  (Note:  Use of serrated 
    blades or saws to cut hose will leave particles that can contaminate system.) 
    2.  Insert the proper size die in the swaging tool. 
    3.  Insert fitting in swaging tool so that it is centered in the die and hand 
    tighten. 
    4.  Insert hose in fitting until it bottoms (Note:  Indicating hole is in base of 
    fitting). 
    5.  Using impact wrench, tighten nut until die housings contact.  (Note:  It is 
    important to keep hose pushed into fitting while swaging). 
    6.  Reverse impact and back off nut until housing contacts rubber stops.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 15   
    D.  Hose or Fitting Replacement (Barb-Lok Hose Fittings) 
     
    NOTE:  If it is found that a hose or fitting has a leak, it will be necessary to 
    replace the entire hose assembly.  Follow the Hose Barb-Lok Instruction below: 
     
    1.  Hose should only be cut with a sharp knife.  (Note:  Use of serrated 
    blades or saws to cut hose will leave particles that can contaminate system.) 
    2.  Slide the Barb-Lok socket onto the hose fitting with the round end towards 
    the stop.  Apply a few drops of machine oil to nut to ease installation.  (Note:  Do 
    not lubricate fitting barbs.) 
    3.  Push hose on barbed end of fitting until all barbs are covered.  Hose end 
    shall be about 1/8 inch past last barb. 
    4.  Hold hose in place.  Pull socket towards hose and thread onto hose 
    counter-clockwise. Use wrench to turn socket onto hose.  The round end of the 
    socket should be 0.82 inch (or one socket length) from the push-on hose stop. 
    5.  About 1/8 inch of hose should protrude past the socket.  This may be 
    trimmed to improve the appearance of the hose assembly. 
     
    E.  Connection to Components - O-Ring Replacement 
    1.  Place the appropriate o-ring over the tube O end of the fitting.   
    2.  Lubricate o-ring with polyolester oil or sealant prior to assembly. 
    3.  Apply sealant to all fitting mating surfaces prior to assembly. 
     
    F.  Recommended standard dry torque specifications. 
     
    Thread 
    Size O-Ring Flare 
    FT-Lb N-M  FT-Lb N-M 
    5/8” 11-13 15-18 20-25 27-34 
    3/4 15-20 20-27 35-40 47-54 
    7/8” 21-27 29-37 50-60 68-81 
    1 1/16”  28-33  38-45 70-80 95-108 
     
    G.  Connection to Components - Flared Fittings 
    1.  Apply sealant to all fitting mating surfaces prior to assembly. 
     
    H. Receiver/Drier Replacement 
    1.  Replace receiver/drier whenever the compressor is replaced or 
    when the air conditioning system plumbing is left open to the atmosphere for a 
    period of time greater than 10 minutes.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 16   
    4.4  Coil Cleaning Maintenance Procedures 
     
    A. General 
     
    The following procedure is used for cleaning either evaporator or condenser coil. 
    B. Tools and Equipment 
     
     
    Designation  
    Ref. No.  
    Qty  
    Remarks 
     
     
    Vacuum Cleaner  
    Comm. Avail.  
    1  
    None 
     
    Coil Cleaner  
    Comm. Avail.  
    A/R  
    Non-acid based 
     
    C.  Coil Cleaning Procedure 
    1.  Use vacuum cleaner to remove large debris from upstream and 
    downstream coil faces. 
    2.  Spray coil cleaner on both coil faces.  Wash off with water. 
    3.  Allow coil to dry thoroughly prior to additional maintenance.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 17   
    4.5  Expansion Valve Removal and Installation 
     
    A. General 
     
    The following procedure is used to remove or install the air conditioning system 
    expansion valve. 
     
    B. Tools and Equipment 
     
    Designation 
      
    Ref. No.  
    Qty  
    Remarks 
     
    Sealant  
    ES49000-1  
    A/R  
    None 
     
    Polyolester Oil  
    Comm. Avail.  
    A/R  
    Viscosity ISO 68 
     
    C. Expansion Valve Replacement 
     
    1.  Discharge system in accordance with Refrigerant Servicing section. 
    2.  Disconnect liquid line from inlet of expansion valve, and cap. Remove the 
    thermal sense bulb from its clamp located on the suction tube of the 
    evaporator and carefully remove insulation covering bulb. 
    3.  Disconnect the fitting that connects the valve to the coil and plug coil 
    fitting. 
    4.  Install new expansion valve and o-ring (for o-ring fitting systems) in the 
    reverse order.  
    5.  Lubricate o-ring with polyolester oil or apply sealant to fitting mating 
    surfaces prior to assembly. 
    6.  Install the thermal sense bulb such that it makes contact with the suction 
    tube along its entire length. When viewing the suction tube extruding out 
    of the evaporator, the sense bulb should be in the three or nine o’clock 
    position (Figure 4-1 and 4-2).  Attach the sensor bulb using two zip ties.  
    Insulate the bulb and expansion valve thoroughly with insulation (Figure 4-
    3).  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 18   
     
    Figure 4-1 
     
    Figure 4-2 
     
    Figure 4-3 
      
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 19   
    4.6  Compressor Maintenance Procedures 
     
    A. General 
     
    The following procedure is used whenever the compressor is replaced or 
    contamination is suspected. 
     
    B. Tools and Equipment 
    Designation Ref. No. Qty Remarks 
    None - - None 
     
    C. Compressor Replacement 
     
    Flush system and replace compressor per the Refrigerant Servicing section.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 20   
    5.0 TROUBLESHOOTING 
     
    5.1 General 
     
    The procedures below present troubleshooting charts for the air conditioning 
    system and the compressor.  A diagnoses chart is presented for insufficient air 
    conditioning system cooling.  The performance characteristics of an aircrafts 
    particular system are dependent upon the design parameters of the systems 
    components.  The performance of any one particular system varies with ambient 
    temperature and humidity.  The information below presents possible air 
    conditioning system problems and solutions. 
     
    CAUTION:  Do not operate air conditioning system with condenser air outlet 
    blocked. 
     
    5.2  Air Conditioning System Diagnosis Chart 
     
    Figure 3 shows a procedure for diagnosing air conditioning system problems.  
    Following this procedure will expedite the troubleshooting process.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 21   
    Figure 3.  Air Conditioning System Diagnosis Chart  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 22   
    5.3  Air Conditioning System Troubleshooting 
     
     
     CONDITION  
    SERVICE PRESSURE 
    GAUGE READING  
     PROBABLE CAUSE  
    CORRECTIVE ACTION 
    INSUFFICIENT 
    REFRIGERANT 
    CHARGE 
     
    Insufficient cooling.  
    Bubbles appear in sight 
    glass (if so equipped).   SUCTION  
    PRESSURE:  below 
    normal 
     
    DISCHARGE 
    PRESSURE:  below 
    normal Refrigerant is low, or leaking 
    a little. 1.  Leak test. 
    2.  Repair leak. 
    3.  Charge system. 
     
    Evacuate as necessary 
    and recharge system. 
    ALMOST NO 
    REFRIGERANT 
     
    No cooling action.  A lot 
    of bubbles or something 
    like mist appears in sight 
    glass (if so equipped). SUCTION  
    PRESSURE:  much 
    below normal 
     
    DISCHARGE 
    PRESSURE:  much  
    below normal Serious refrigerant leak.  Stop compressor 
    immediately. 
     
    1. Leak test. 
    2. Discharge system. 
    3. Repair Leak(s). 
    4. Replace receiver drier, 
    if necessary. 
    5. Check oil level. 
    6. Evacuate and recharge 
    system. 
    FAULTY EXPANSION 
    VALVE 
     
    a) Slight cooling. 
    Sweating or frosted 
    expansion valve outlet. 
     
     
     
     
     
    b) Insufficient cooling. 
    Sweated suction line. 
     
     
     
     
     
     
     
    c) No cooling. 
    Sweating or frosted 
    suction line.  
     
     
    a) SUCTION  
    PRESSURE:  below 
    normal 
     
    DISCHARGE 
    PRESSURE:  below 
    normal 
     
    b) SUCTION  
    PRESSURE:  above 
    normal 
     
    DISCHARGE 
    PRESSURE:  above 
    normal 
     
     
    c) SUCTION  
    PRESSURE: above 
    normal 
    DISCHARGE 
    PRESSURE: below 
    normal  
     
     
    a) Expansion valve restricts 
     refrigerant.  Or, expansion 
    valve is clogged.  Or, 
    expansion valve is 
    inoperative.  Or, valve stuck 
    closed.  Thermal bulb has 
    lost charge. 
     
    b) Expansion valve allows  
    too much refrigerant through 
    evaporator. 
     
    Sensing bulb on suction line 
    not well insulated or properly 
    attached to line. 
     
     
    c) Faulty expansion valve.  
     
     
    a) 
    1.  Discharge system. 
    2.  Replace valve. 
    3.  Evacuate and recharge 
    system. 
     
     
     
    b) 
    1. Check valve for 
    operation.  If suction side 
    does not show a pressure 
    decrease, replace valve. 
    2. Check security and 
    insulation on sensing bulb. 
     
     
    c) 
    1.  Discharge system. 
    2.  Replace valve. 
    3.  Evacuate and recharge 
    system. 
      
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 23   
     
     CONDITION  
    SERVICE PRESSURE 
    GAUGE READING  
     PROBABLE CAUSE  
    CORRECTIVE ACTION 
    AIR IN SYSTEM 
     
    Insufficient cooling.  
     
    Sight glass (if so 
    equipped) shows 
    occasional bubbles.   SUCTION  
    PRESSURE:  above 
    normal 
     
    DISCHARGE 
    PRESSURE:  above 
    normal Air mixed with refrigerant in 
    system. 1. Discharge system. 
    2. Replace receiver drier. 
    3. Evacuate and charge 
    system. 
     
    MOISTURE IN SYSTEM 
     
    After operation for a 
    while, pressure on 
    suction side may show 
    vacuum pressure 
    reading.  During this 
    condition, discharge air 
    will be warm.  As 
    warning of this, reading 
    shows approx 6 psi 
    oscillation. SUCTION  
    PRESSURE:  below 
    normal 
     
     
    DISCHARGE 
    PRESSURE:  above 
    normal Drier is saturated with 
    moisture.  Moisture has 
    frozen at expansion valve.  
    Refrigerant flow is restricted. 1. Discharge system. 
    2. Replace receiver drier 
     (twice if necessary). 
    3. Evacuate system  
    completely.  (Repeat 30 
    minute evacuating three 
    times.) 
    4. Recharge system. 
     
    FAULTY CONDENSER 
     
    Insufficient cooling. 
     
    Bubbles appear in sight 
    glass of drier. 
     
    Suction line is very hot. 
     
     
     SUCTION  
    PRESSURE:  above 
    normal 
     
     
    DISCHARGE 
    PRESSURE:  above 
    normal Condenser air or refrigerant 
    flow is restricted. Check condenser for dirt 
    accumulation. 
     
    Check for refrigerant 
    overcharge. 
     
    If pressure remains high in 
    spite of all above actions 
    taken, remove and inspect 
    the condenser for possible 
    oil clogging. 
     
    HIGH PRESSURE LINE 
    BLOCKED 
     
    Insufficient cooling.  
     
    Frosted high pressure 
    liquid line.   SUCTION  
    PRESSURE: much  
    below normal 
     
    DISCHARGE 
    PRESSURE:  much 
    above normal Drier clogged, or restriction 
    in high pressure line. 1. Discharge system. 
    2. Remove receiver drier 
    and replace it. 
    3. Evacuate and charge 
    system. 
     
      
    						
    All AirComm Corporation manuals Comments (0)

    Related Manuals for AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a