Home > AirComm Corporation > Air Conditioner > AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a

AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a

    Download as PDF Print this page Share this page

    Have a look at the manual AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 4   
    2.2 Electrical Driven Compressor Systems 
     
    Electrically operated systems use the aircraft electrical system and are operable 
    in most normal flight modes.  Air conditioning may be operated with ground 
    external power or the aircraft electrical system providing voltage to the proper 
    bus. 
     
    The compressor and condenser are manufactured on an assembly pallet. In 
    most cases, the compressor drive and condenser fan drive are both driven by a 
    common, double shafted motor.  The compressor is belt driven from the shortest 
    shaft while the condenser fan is attached directly to the longer motor shaft.  
    Condenser cooling air (ambient air) is drawn over the compressor and drive 
    motor to provide cooling airflow for those components prior to passing through 
    the condenser coil to remove heat from the system.  Some electrically driven 
    systems have separate compressor drive and condenser fan motors.  After 
    passing through the condenser coil, the air is exhausted to the outside.  The 
    compressor takes low pressure refrigerant gas and compresses it to a higher 
    pressure and temperature.    
        
    On the ground, the electrical system allows operation of the air conditioning 
    system from either aircraft generator or from an active GPU prior to engine start. 
    Some system safety features include electrical interlocking and load shedding.  
    In flight, the air conditioning system can be operated from the aircraft electrical 
    system only with aircraft generators on line.  Loss of aircraft generator power will 
    automatically shed the air conditioning system electrical loads except for the 
    minimal loads of the evaporator fans. 
     
    The entire air conditioning refrigerant loop is protected against over pressure and 
    over temperature conditions by two separate safety devices.  The first device is a 
    binary high/low pressure switch that activates in the event of an overpressure 
    and is on the compressor discharge port.  This switch will open at approximately 
    350 PSIG and will interrupt power to the compressor control circuit.  This in turn 
    will de-energize the compressor motor relay and remove power to the 
    compressor motor.  The refrigerant system pressures will then drop. The switch 
    will also interrupt power to the compressor control circuit under low pressure 
    conditions.   The second safety overpressure device is a fuse plug which will vent 
    the system refrigerant safely overboard in the event of a system pressure in 
    excess of 425 psig.  It is located on the receiver/drier.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 5   
    2.3  Engine Driven Compressor Systems 
     
    Engine driven systems use compressors that are engine mounted; or on some 
    rotorcraft, driven off the tail rotor drive shaft.  A pulley via a V type belt turns the 
    compressor.    A clutch mounted on the compressor engages the compressor 
    when the air conditioning system is selected ON. 
     
    The condenser uses a separate fan with electrical motor to supply cooling air.  
    The condenser cooling air (ambient air) is drawn in through a cutout in the 
    fuselage skin of the aircraft and passes through the condenser coil to remove 
    heat from the system.  After passing through the condenser coil and blower, the 
    air is exhausted to the outside of the aircraft.  
     
    The entire air conditioning refrigerant loop is protected against over pressure 
    conditions by two separate safety devices.  The first device is a binary high/low 
    pressure switch.  This switch will open at approximately 350 PSIG and will 
    interrupt power to the compressor clutch at which point the system pressures will 
    drop. The switch will also interrupt power to the compressor clutch under low 
    pressure conditions.   The second overpressure safety device is a fuse plug 
    which will vent the system refrigerant in the event of a system pressure in excess 
    of 425 PSIG.  It is located on the receiver/drier.   
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 6   
    3.0 REFRIGERANT SERVICING 
     
    3.1 General 
     
    The air conditioning system uses refrigerant R134a and the compressor 
    lubricating oil used is Polyolester Oil viscosity grade (ISO) 68.  No other 
    refrigerant or compressor oil should be used. 
     
    Refrigerant R134a is non explosive, non-flammable, non -corrosive, has 
    practically no odor, and is heavier than air.  Although R134a is classified as a 
    safe refrigerant, certain precautions must be observed to personnel and property 
    when working with R134a refrigerant. 
     
    WARNING:   
     
    A.  Liquid R134a, at normal atmospheric pressure and temperature, 
    evaporates so quickly that it tends to freeze anything that it contacts.  Care must 
    be taken to prevent any liquid refrigerant from coming into contact with skin. 
     
    B.  Always wear safety goggles when servicing any part of the refrigerant 
    system to prevent refrigerant from coming into contact with the eyes. 
     
    C.  To avoid explosion, never weld, use a blow torch, solder, steam clean, or 
    use excessive amounts of heat on, or in, the immediate area of the air 
    conditioning system, or refrigerant supply tank, full or empty, while they are 
    closed to atmosphere. 
     
    D.  The refrigerant service cart/container has a safe strength.  However, if 
    handled incorrectly, it will explode.  Therefore, always follow the instruction on 
    the label.  In particular, never store it in a hot location (above 126F, 52C) or 
    drop it. 
     
    CAUTION:  Do not operate air conditioning system with condenser air outlet 
    blocked.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 7   
    3.2 Discharging System 
     
    A. General 
     
    The air conditioning system refrigerant must be discharged prior to disconnecting 
    or removing components in the refrigerant loop.  Federal law prohibits 
    discharging refrigerant into the atmosphere.  Use only an R134a compatible 
    recycling/recovery unit when discharging the air conditioning system. 
     
     
    B. Tools and Equipment 
     
     
    Designation Ref. No.  
    Qty  
    Remarks 
     
     
    Service Pressure Gauge  Comm. Avail.  
    1  
    None 
     
    R134a Compatible 
    Recycling/Recovery 
    Unit Comm. Avail.  
    1  
    None 
     
     
    C. Discharging Procedure 
     
    1)  Connect R134a compatible recycling/recovery unit to the R134a service 
    valves on the aircrafts air conditioning system.  If recovery unit does not 
    have pressure gauges, connect service pressure to air conditioning system. 
     
    2)  After cart oil level has been verified, evacuate the system, per recovery 
    unit’s instructions.  Let the system sit for approximately 5-10 minutes to let 
    any residual refrigerant boil from the system oil. Note the amount of post 
    recovery oil in cart.  The amount of oil in the cart prior to recovery should be 
    subtracted from the amount of oil after recovery. This is the amount of oil 
    that needs to be added to the system before charging. 
     
    3)  Remove recovery unit when discharging is complete.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 8   
    3.3 Evacuating System 
     
    A. General 
     
    The air conditioning system must be evacuated prior to charging the system with 
    refrigerant.  Evacuating the system removes any moisture that may be in the 
    system.  Use only an R134a compatible recycling/recovery unit when evacuating 
    the air conditioning system. 
     
     
    B. Tools and Equipment 
     
     
    Designation  
    Ref. No.  
    Qty  
    Remarks 
     
     
    Service Pressure Gauge  
    Comm. Avail.  
    1  
    None 
     
    R134a Compatible 
    Recycling/Recovery 
    Unit  
    Comm. Avail.  
    1  
    None 
     
     
    C. Evacuating Procedure 
     
    1)  Connect R134a compatible recycling/recovery unit to the R134a service 
    valves on the aircrafts air conditioning system.  If recovery unit does not 
    have pressure gauges, connect service pressure to air conditioning 
    system. 
     
    2)  Evacuate the air conditioning system in accordance with the recovery 
    units instructions for a minimum of 15 minutes. 
     
    3)  Once the air conditioning system has been evacuated, it is then ready 
    for charging with new/recycled R134a refrigerant.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 9   
    3.4 Charging System 
     
    A. General 
     
    Use only R134a refrigerant when charging air conditioning system.  Federal law 
    prohibits discharging refrigerant into the atmosphere.  Use only R134a 
    compatible recycling/recovery unit when charging the air conditioning system. 
     
    B. Tools and Equipment 
     
     
    Designation  
    Ref. No.  
    Qty  
    Remarks 
     
     
    Service Pressure Gauge  
    Comm. Avail.  
    1  
    None 
     
    R134a Compatible 
    Recycling/Recovery 
    Unit  
    Comm. Avail.  
    1  
    None 
     
    Polyolester Oil  
    Comm. Avail  
    A/R  
    Viscosity ISO 68 
     
    C. Charging Procedure 
     
    1)  Connect R134a compatible recycling/recovery unit to the R134a service 
    valves on the aircrafts air conditioning system.  If recovery unit does not have 
    pressure gauges, connect service pressure to air conditioning system. 
     
    2)  Add the amount of compressor oil recovered during discharging.  Add new 
    polyolester oil, viscosity ISO 68 to the compressor oil fill port. 
     
    3)  Charge the air conditioning system in accordance recovery unit’s 
    instructions, until: 
    a. The sight glass just clears of bubbles.  This can also be 
    accomplished by first initially charging the system with 1.5 lbs of 
    refrigerant and then VERY slowly, with the system operating, 
    introduce small amounts of refrigerant in .1 lb increments until the 
    sight glass is clear of bubbles. (If sight glass is present.) 
    b.  The charge pressure reaches the range specified in the Table A.1.  
    (If no sight glass is present) 
     
    NOTE:  Keep the low side closed and the high side open during charging so 
    that liquid R134a passes through the evaporator and evaporates into a gas 
    before entering the compressor.  Liquid R134a entering the compressor can 
    cause permanent damage!  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 10   
    3.5 Flushing System 
     
    A. General 
     
    The following procedure is used to whenever the compressor is replaced and 
    when system contamination is suspected. 
     
    B. Tools and Equipment 
     
    Designation Ref. No. Qty Remarks 
    ACC Hose Coupler Tool  See Procedures  A/R  None 
    Service Pressure Gauge  Comm. Avail.  1  None 
    R134a Compatible 
    Recycling/Recovery Unit Comm. Avail.  1  None 
    Polyolester Oil  Comm. Avail.  A/R  Viscosity ISO 68 
     
    System Flushing Procedure 
     
    1.  Connect the refrigerant recovery cart to the normal service ports. 
     
    2.  Empty the refrigerant recovery cart’s oil collection tube so that it begins with 
    zero oil collected. 
     
    3. Discharge the air-conditioning system and recover the refrigerant per the 
    refrigerant cart’s instructions.  Do not empty the oil collection tube. 
     
    4.  Disconnect the refrigerant recovery cart from the normal service ports. 
     
    5.  Remove the compressor and connect the service valve couplers to the suction 
    and discharge plumbing hoses. 
     
      O-ring Style Coupler P/N’s JBS6020-7 and JBS6020-8. 
      Flare Style Coupler P/N’s JBS6020-9 and JBS6020-10.  
     
    6.  Bypass the binary pressure switch.  If located on the condenser assembly, 
    attach the plumbing hose directly to the condenser.  If located on the 
    compressor then bypass per previous step. 
     
    7.  Remove the receiver/drier bottle from the aircraft and properly dispose.  Attach 
    the hose coupler tool in place of the receiver/drier bottle.  
     
      O-ring Style Coupler P/N JBS6009-1. 
      Flare Style Coupler P/N JBS6020-6.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 11   
    8.  Disconnect all of the expansion valves from the evaporator assemblies.  Attach 
    the hose coupler tool in place of the expansion valves on all evaporator 
    assemblies.  Use caution in handling the expansion valves.  Do not support the 
    expansion valve by its remote bulb tubing.  Do not disconnect the external 
    equalization port fitting if the expansion valve is an externally equalized style 
    (ES26105-1 and ES26106-1). 
     
      O-ring Style Coupler P/N JBS6020-3 
      Flare Style Coupler P/N JBS6020-4 
     
    9.  Connect the refrigerant recovery cart to the service port couplers located where 
    the compressor was removed to create a refrigerant loop with the refrigerant 
    cart. 
     
    10. Evacuate the system thru the HIGH side port only per the refrigerant recovery 
    cart’s instructions for a minimum 10 minutes. 
     
    11. Charge the system thru the LOW side port only with 1.5 to 2 times a normal 
    refrigerant charge of refrigerant.  Do not add any oil to system. 
     
    12. Recover the system thru the HIGH side port only per the refrigerant recovery 
    cart’s instructions. 
     
    13. Repeat previous three steps two additional times. 
     
    14. Disconnect the refrigerant recovery cart from the service ports. 
     
    15. Remove the compressor and drain all of the oil from the compressor into an 
    empty graduated cylinder.  It will be necessary to rotate the clutch plate several 
    times to get as much oil as possible from the compressor. 
     
    16. Empty the refrigerant recovery cart’s oil collection tube into the graduated 
    cylinder with the drained compressor oil.  Inspect the oil for debris 
    contamination and replace compressor if necessary. 
     
    17. New compressors come serviced with 5 ounces of oil and do not require oil 
    adjustment.  If the existing removed compressor is reused or other replacement 
    compressor for which the oil level is unknown, then completely drain the 
    compressor and then add 5 ounces of new polyolester oil ISO grade 68 to the 
    compressor.  Torque the oil plug to 6 to 9 ft-lbs. 
     
    18. Install the compressor.  Use new o-rings. 
     
    19. Inspect the expansion valves for damage and debris.  Replace if any 
    contamination is found.  Use new o-rings.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 12   
    20. Inspect the binary pressure switch for damage and debris.  Flush with dry 
    nitrogen or clean dry compressed air before re-installing.  Use new o-rings. 
     
    21. Install a new receiver/drier bottle.  Do not reuse the old bottle under any 
    circumstance.  Use new o-rings. 
     
    Caution:   Receiver/drier bottles left open to the atmosphere for more than 10 
    minutes must be discarded and replaced with new. 
     
    22. Evacuate the system per the refrigerant recovery cart’s instructions for a 
    minimum 15 minutes. 
     
    23. Add 1 ounces of new polyolester oil ISO grade 68 for each 7 feet of plumbing 
    over 15 feet total length to the system thru the HIGH side port only. 
     
    24. Charge the system per Charging Procedure.  
    						
    							TR-134 
    Revision J 
      
     
      
    September 13, 2013 
    Page 13   
    4.0 GENERAL SERVICING 
     
    4.1 General 
     
    General service procedures are provided to keep the air conditioning system 
    operating at peak efficiency.  Procedures are provided for general maintenance 
    tips, inspection intervals, maintenance of the plumbing system, to repair hoses, 
    and to clean coils.  Procedures are also provided for removal and installation of 
    the expansion valve. 
     
    CAUTION:  Do not operate air conditioning system with condenser air outlet 
    blocked. 
     
    4.2 Inspection Intervals 
     
    A. General 
     
    Periodic inspections of the air conditioning system will keep the system operating 
    at peak efficiency.   The inspections are simple visual inspections requiring a 
    minimal amount of time.  
     
    B. Inspection Intervals 
     
     
    ITEM  
    INSPECT FOR INTERVAL  
    ACTION 
     
    Air Conditioning 
    System 
    Components  
    Dirt , Damage *Every 500 hours 
    and annualy  
    Clean or replace 
    component as 
    necessary 
     
    Compressor Belt  
    Tension, Wear Within 5 hours of 
    installing new belt 
    *Every 500 hours 
    and annualy  
    Tension or replace 
    as necessary 
     
    Sight Glass  
    (if so equipped)  
    Proper refrigerant 
    level When problem is 
    suspected  
    Discharge/charge as 
    necessary per 
    Refrigerant Servicing 
    section 
     
    Evaporator and 
    condenser coils  
    Dirt *Every 500 hours 
    and annualy  
    Clean as necessary 
     
    *Recommended inspection interval maximums.  Actual inspection times should 
    be conducted around the aircrafts existing regularly scheduled maintenance 
    checks. 
    						
    All AirComm Corporation manuals Comments (0)

    Related Manuals for AirComm Corporation Cessna 414 421 Air Conditioning System Service Manual R134a