    							11
    MOUNTING CONNECTION GETTING STARTEDAPPENDIX
    SETUP AFTER 
    INSTALLATION
    Ceiling speaker, ceiling microphone
    ■ Ceiling speaker (NI-LB)                                                   ■ Ceiling microphone (NI-SB)
    Main unitChinese RoHS 
    paperMain unitWood screw 
    (x2)
    15 (9/16”)
    ø180 (7-1/16”)
    ø105 (4-1/8”)
    5 (3/16”)
    HolderChinese RoHS 
    paper
    65 
    (2-9/16”)
     
    Corridor light, reset button
    ■ Corridor light, single bed (NIR-4)
    ■ Corridor light, multiple beds (NIR-4S)                                        ■ Call reset button (NIR-2) 
    Main unit Screw (x2) Main unit Screw (x2)
    21.5 (7/8”)
    120 (4-3/4”)
    70 (2-3/4”)
    120 (4-3/4”)
    70 (2-3/4”)13 (1/2”)
    Chinese RoHS 
    paperChinese RoHS 
    paper
      
    (Front)  (Front)  (Side)  (Side) 
     (Front) 
     (Front) 
     (Side) 
     (Side) 
     (Side)  
    						
    							12
    ■ Corridor light with reset button (NIR-42) 
    Main unit Screw (x4)
    120 (4-3/4”)
    27 (1-1/16”) 116 (4-9/16”)
    Chinese RoHS 
    paper
    ■ Corridor light with buzzer (NIR-4BZ) 
    Main unit Screw (x4)
    120 (4-3/4”)
    27 (1-1/16”) 116 (4-9/16”)
    Chinese RoHS 
    paper
    ■ Corridor light with nameplate, 1 name (NIR-31) 
    Main unit Mounting bracketRoom number 
    plateNameplate
    144 (5-11/16”)
    16 
    (5/8”) 190 (7-1/2”)
    24 (15/16”)
    Screw (x4) Chinese RoHS paper
     (Front) 
     (Front) 
     (Side) 
     (Side) 
     (Front)  (Side)  
    						
    							13
    MOUNTING CONNECTION GETTING STARTEDAPPENDIX
    SETUP AFTER 
    INSTALLATION
    ■ Corridor light with nameplates, 2 names (NIR-32) 
    Main unit Mounting bracketRoom number 
    plateNameplate (x2)
    144 (5-11/16”)
    16 
    (5/8”) 190 (7-1/2”)
    24 (15/16”)
    Screw (x4) Chinese RoHS paper
     
    ■ Corridor light with nameplates, 4 names (NIR-34) 
    Main unit Mounting bracketRoom number 
    plateNameplate (x4)
    144 (5-11/16”)
    16 
    (5/8”) 306 (12-1/16”)
    24 (15/16”)Screw (x4) Chinese RoHS paper
     
     
    Software
    ■ Call log software (NI-SOFT)
    CD-ROM RS232C cableProduct Key code paper/
    Chinese RoHS paper
      
    (Front)  (Side) 
     (Front)  (Side)  
    						
    							14
    MOUNTING
    This section illustrates the mounting procedures for wall- and ceiling-mount equipment.
    ■ Ceiling speaker (NI-LB)
    ■ Ceiling microphone (NI-SB)
    ø105mm (4-3/16”) 66.7mm (2-11/16”)
    NOTE:
    Make sure to mount the ceiling microphone 50 cm (20) apart from the ceiling speaker to prevent audio feedback.
    
    Pay attention to the depth of the unit.
    Use board anchors or concrete plugs as needed on a concrete wall.
    Holder
    Hook
    Connector
    Loop
    Main unit
    Main unit SpringCeiling
    CeilingØ150mm 
    (5-7/8)
    Disconnect the connector, 2 and then make wire 
    connections with other 
    equipment.
    Make a hole of 150mm (5-7/8) 1 in diameter in the ceiling.
    Put the holder into 3 the hole by tilting it, 
    and then position it as 
    shown.
    Hang the loop on the 
    4 hook at one side.Connect the connector to 
    5 the main unit.
    Hang the loop on the 
    6 hook 
    at the other side, and 
    install the main unit so 
    that it is positioned at the 
    center of the hole.
    Wood screw x 2
    (included)
    Central part
    Cut 1 the ceiling so that 
    the central part of the 
    unit fi ts in.
    Make wire 
    2 connections with the 
    other equipment.
    Fasten the unit to the 
    3 wall with the wood 
    screws.
    W: 47mm (1-7/8) Opening dimensions
    H:  38mm 
    (1-1/2)
    D:  40mm 
    (1-9/16) 
    						
    							15
    MOUNTING CONNECTION GETTING STARTEDAPPENDIX
    SETUP AFTER 
    INSTALLATION
    ■ Wall jack (NIR-HP, NIR-1, NIR-MB, NIR-7BS)
      Call button (NIR-6)
      Corridor light (NIR-4, NIR-4S)
      Call reset button (NIR-2)
    The illustration shows the wall jack for NI-RC (NIR-HP).* 
      Bathroom call button (NIR-7W, NIR-7HW)
    The illustration shows the bathroom call button (NIR-7W).* 
    CALL
    Remove the front cover from 1 the main unit.
    Install a single gang box 2 in the wall. Pass the wires 
    through the gang box and 
    make the wire connections 
    with the other equipment.
    83.5mm 
    (3-5/16) Single-gang box
    Screw x 2
    (included)
    Main unit
    Front cover
    Fasten the unit to the single-3 gang box with the screws.
    Attach the front cover 
    4 to the main unit.
    Install a single gang box 2 in the wall. Pass the wires 
    through the gang box and 
    make the wire connections 
    with the other equipment.
    83.5mm (3-5/16) Single-gang box
    Screw x 2
    (included)Main unit
    Front cover
    Fasten the unit to the 3 single-gang box with the 
    screws.
    The screw holes are on the * 
    backside of gray rubber.
    Attach the front cover to the main unit.4 
    CALL
    Remove the front cover 1 from the main unit.
    Insert a fl at head screwdriver 
    into the hole on the bottom of 
    the unit, and then pull the fl at 
    head screwdriver toward you. 
    The front cover opens.
    Flat head 
    screwdriver
    Hole
    HD
    W
    HD
    W
    Opening dimensions without a gang box
    W: 45mm (1-3/4), H: 72mm (2-13/16), 
    D: 54mm (2-1/8)
    Opening dimensions without a gang box
    W: 50mm (1-15/16), H: 70mm (2-3/4), 
    D: 20mm (13/16) 
    						
    							16
    ■ Sub station, surface mount (NI-BA)
    When mounting NI-BA on a wall, follow the procedure shown below.* 
    ■ Sub station, fl ush mount (NI-JA)
    Tighten Special screw x 4 
    (included)46 mm
    (1-13/16)
    Loosen
    Hexagonal wrench
    (included)
    Opening dimensions without a gang box
    W: 90mm (3-9/16), H: 73mm (2-7/8), D: 54mm (2-1/8)Main unit 2-gang box
    Install a 2 gang box in the wall. 1 Pass the wires through the 
    gang box and make the wire 
    connections with the terminal 
    cover open.
    Be sure to route the wires through * 
    inlet.
    Inlet Terminal cover 83.5 mm
    (3-5/16)
    Fasten the main unit to 2 the gang box with the 
    special screws.
    Install a single gang box in the wall. Pass the 1 wires through the gang box and make the wire 
    connections with the other equipment.
    83.5mm (3-5/16)
    Single-gang box
    Screw x 2
    (included) Main unit
    Fasten the mounting bracket to 2 the gang box with the screws.
    Attach the main unit to 
    3 the mounting bracket.
    Mounting bracket 
    (attached to NI-BA when shipped)
    When setting NI-BA on a desk
    Rubber footCable inlet plate
    Cable inlet
    Cable inlet
    Attach the included 4 rubber feet on the back • 
    of NI-BA.
    Route the wires through the cable inlet at the 
    • 
    upper or lower part of NI-BA.
    When routing the wires at the upper part, 
    * 
    remove the cable inlet plate to allow 
    passage of the wires. 
    						
    							17
    MOUNTING CONNECTION GETTING STARTEDAPPENDIX
    SETUP AFTER 
    INSTALLATION
    ■ Wall jack (NIR-HPF)
      Corridor light (NIR-42, NIR-4BZ)
    ■ Corridor light with nameplate (NIR-31, NIR-32, NIR-34)
    The illustration shows the corridor light with nameplates, 4 names (NIR-34).* 
    Mounting bracket 
    (attached to the unit when shipped)
    Main unit
    Screw (for gang box) × 4 (included)Single, 2- or 3-gang box
    Install a gang box in the wall.1 
    NIR-31, NIR-32: 2-gang box(*)
    NIR-34: 3-gang box(*)
    (*): Recommended
    Detach the mounting 2 bracket from the main unit 
    by removing the room 
    number plate and the 
    screw.
    Fasten the mounting 3 bracket to the gang box 
    with the screws.
    StringWires Gang box
    Main unit
    Hang the string of 4 the main unit on a 
    projecting part or a 
    thread on the bracket 
    to suspend the main 
    unit.
    Make wire connections 
    5 with other equipment. 
    Screw 
    (attached) Room number 
    plate46 mm
    (1-13/16) 2-gang box
    Remove the front 1 cover from the 
    main unit.Install a 2 gang box in 2 the wall. Pass the wires 
    through the gang box and 
    make the wire connections 
    with the other equipment.
    83.5mm (3-5/16)
    Screw x 4
    (included)
    Main unit
    Front cover
    Fasten the unit to the 2-gang 3 box with the screws.
    Attach the front cover 
    4 to the main unit.
    The illustration shows the * 
    corridor light with reset 
    button (NIR-42).
    Screw 
    (attached) Room number 
    plate
    Mount the main unit on the 6 mounting bracket, and affi x 
    the main unit to the bracket 
    with the screw. 
    Attach the room number 
    7 plate to the main unit
    Opening dimensions without a gang box
    W: 95mm (3-3/4), H: 75mm (2-15/16), D: 54mm (2-1/8) 
    						
    							18
    CONNECTION
    Connection wiring diagram (outline) 
    The following is an example of basic wiring diagram.
    The wiring methods differ depending on the equipment used. Refer to page 20 to 29 for details about various wiring methods. * 
    E
    1
    M
    2
    3
    4
    5
    10
    12
    19
    20
    11
    SK
    S1
    SK
    S1
    I-G
    RXTX
    Black
    OrangeWhiteGrayOrange/
    White
    BlueYellowRed
    Gray
    White
    PC
    Blue
    Blue
    Blue
    Blue
    22
    29
    30
    21
    32
    39
    40
    E
    M
    31
    34
    33
    Gray White Blue
    Blue
    Red White
    Black
    Black
    Yellow
    RedBlue
    or
    NIR-8NI-LB
    GreenBlack
    Yellow
    RedBlueGreenBlack
    Yellow
    RedBlueGreen
    NI-RC NIR-HP
    NI-RC NIR-HP
    NIR-4
    NIR-2
    Blue Blue
    Black
    OrangeWhiteGrayOrange/
    White
    BlueYellowRed
    Blue
    Blue
    Blue
    BlueCorridor 
    light, single 
    bed 
    (NIR-4)
    Call reset 
    button 
    (NIR-2)
    Ceiling speaker 
    (NI-LB) Master station, 
    40-call (NIM-40B)
    When using the master 
    station, 60-call or 80-call, 
    two power supplies are 
    needed.
     Do not connect two 
    power supplies in 
    parallel.
    • Master station, 
    20-call (NIM-20B)
    • Master station, 
    60-call
    (*)
    • Master station, 
    80-call(*)
    Call extension 
    speaker (IER-2)
    Power supply 
    unit (IS-PU only)
    RS232C 
    cable 
    (included on 
    NI-SOFT)
    Ceiling 
    microphone
    (NI-SB) Wall jack 
    for NIR-8 
    (NIR-1)
    Bedside 
    call switch 
    (NIR-8)
    (6 wall jacks can be 
    connected in total.)
    * Connect to 
    each of the 
    color-coded 
    wires.* Connect to 
    each of the 
    color-coded 
    wires.
    (6 wall jacks can be 
    connected in total.)
    Refer to page 21 for 
    details about wiring to 
    a master station.
    Refer to page 22 for details and examples of 
    using alternative equipment.Refer to page 23 for details and examples of 
    using alternative equipment.Wall jack with 
    microphone 
    for NIR-8 
    (NIR-MB)
    Wall jack for 
    NI-RC (NIR-HP)
    Bedside handheld sub station (NI-RC)
    (*): Special order product. 
      N/A in North America.
    Speaker etc. 
    (3W/20Ω, 
    third party 
    product)
    SP-20N/A
    (*)
    (
    *):  North America 
    only
    (*1)
    (
    *1) 
    						
    							19
    APPENDIX
    MOUNTING CONNECTION GETTING STARTED
    SETUP AFTER 
    INSTALLATION
    Red
    Black
    CALLBlue
    Green
    Blue
    Blue
    Blue
    Blue
    Red
    Black
    Blue
    Red
    Black
    Blue
    CALL
    CALL
    Blue Blue
    Blue
    Blue
    II
    Blue
    Blue
    Green
    Green
    BrownBlack
    Black OrangeRed
    Red Yellow
    Blue Green
    NIR-7W or 
    NIR-7HW
    NIR-7W or 
    NIR-7HW
    NIR-7W or 
    NIR-7HW
    Blue Blue
    Blue
    Blue
    E
    C
    CE
    CS M A
    NIR-4
    NIR-2NIR-4
    NIR-2
    NIR-8NIR-1
    NIR-4
    NIR-2
    CALL
    E
    C
    CE
    CS M A
    ■ Wiring distance
    Wire diameter Maximum distance
    Master station - sub stationØ0.65mm (22 AWG)
    Ø0.9mm (18 AWG)130m (425)
    200m (650)
    Master station - power supply unit Ø0.9mm (18 AWG) 10m (33)
    Master station - call extension 
    speaker (IER-2), speaker etc.Ø0.9mm (18 AWG) 50m (165)
    ■ Master station terminal marking
    E : Common line (for earth ground)
    M
     : Common line (for microphone)
    1
    ...
    10, 
    11...
     : Individual channel line
    Refer to page 28 for details and examples 
    of using alternative equipment.
    Refer to page 27 for 
    details and examples 
    of using alternative 
    equipment.
    Refer to page 26 for details and examples 
    of using alternative equipment.
    Refer to page 24-25 for 
    details and examples 
    of using alternative 
    equipment.
    Refer to page 29 for 
    details about wiring to 
    the corridor light with 
    nameplate (NIR-34, 
    NIR-32 or NIR-31).
    * Up to 3 bathroom 
    call buttons can be 
    connected to a single 
    channel line.
    Bathroom 
    call button 
    (NIR-7W or 
    NIR-7HW) Sub station, 
    surface mount 
    (NI-BA)
    Sub station, 
    fl ush mount 
    (NI-JA)
    Corridor light with 
    nameplates, 4 
    names 
    (NIR-34)■ Meanings of symbols
     : Wire-to-wire connection
     : The wire should be cut and 
    insulated.
    (*1):  • The common line 
    E and individual channel lines should be in the same sheath wiring.
    • The remainder wires in the same sheath wiring should be connected to the common line 
    E of the master station for noise prevention. 
    						
    							20
    Handling cables
    Notes about handling cables
    Cables and connectors are not included with the products.* 
    ■ Notes on cables
    Use PE (polyethylene)-insulated PVC jacketed cable.• 
    Parallel or jacketed conductors, mid-capacitance, non-shielded cable 
    is recommended.
    Never use twisted pair cable or coaxial cable.
    • 
    ■ How to connect or disconnect stranded wires.
    To ensure that the wire wont bend, press the release button while inserting into terminal.• 
       
    8mm(3/8")
    ■ Note about wire-to-wire connection.
    Make wire-to-wire connections securely as shown below.
    e.g.) NI-BA
    Release button
    From a sub stationWire nut
    Cable
    Splice 2 wires with wire nuts, 
    securely protecting from being 
    pulled or crushed. e.g.) NIM-40B
    Release button 
    						