45 The Final Torque Sample graph shows the final torque of each rundown in the collection. For reference, the Parameter Set values for Torque Hi, Torque Lo w, and Torque Target are taken from the first rundown in the collection and plotted as vertical lines. 2.11 AcraVision AcraVision displays the current rundown informat ion in an easy to read screen. If there is a failure in the tightening the Tor que/Angle is displayed in red. Use Record Rundowns to save the Rundown informat ion...
Page 92
46 2.12.1 Serial Test Hyper-terminal like screen that can be used to monitor the serial output messages from the iEC controller 3. Addendum 3.1 Fault codes Fault codes are displayed to inform the operator about what is happening in the Controller and why something doesn’t behave as expected. Figure Add.3.1 Fault Codes 3.2 Trouble Shooting Fault Description
Page 93
47 TID Timeout: No Communication between the tool and controller. This fault condition is usually caused by a problem in the tool ID board. Try connecting another tool to the controller Tool GND: The tool ground loop is broken. This fault condition is usually caused by a problem in the controller or tool. Try the tool and cable on another controller. The fault can be intermittent. Power on Throttle: The System thinks that the thro ttle is being activated or the run command through...
Page 94
48 Locked rotor: The controller has not sensed hall transitions from the motor for a period of time. This is possible if the tool is trying to achieve a high torque at a low speed. Increase the rundown speeds and make sure the tool is calibrated properly. It is also possible that the controller is f aulty. If the tool does not run at all try connecting it to a different controller. Drive Fault : The servo drive is not trying to run the tool. Try the tool on another controller. PSet...