Page 71

 
70
5. APPENDIX 
 
5.1. Sending status information and sensor values using rules 
 
The administrator can create rules (see Settings/Rules) to trigger actions and send personalized 
messages in form of Syslog messages, SNMP traps or emails when an event occurs. Moreover, the 
administrator also has the possibility to complete his messages with status information of an input (a 
power supply or a door contact for example) or the value of a sensor (a temperature sensor for example).  
 
In the...

Page 72

71 
5.2. Ping and Scan Methods 
ePowerSwitch 8XM has two methods to check whether an IP equipment (PC, server, router, Webcam...) 
is still alive: 
 
Address Pinging: 
The first method uses the well-known Ping command whereby a request is sent to a specific IP address. 
The Ping command, which is an echo request, enables you to determine through an ICMP protocol 
(Internet Control Message Protocol) if an IP device is available on the network. If the system reacts to this 
request, ePowerSwitch 8XM knows...

Page 73

 
72
5.3. Technical Data 
 
Network standards: 
IEEE 802.3, 10 / 100 BASE-T 
Network protocols: 
TCP/IP, HTTP/HTTPS 
Network connection: 
RJ-45 connector for STP CAT5  
Max. network cable length 100 meters 
Serial connection: 
RS232, SUB-D 9 female 
SSL Technology: 
Version 2 and 3 
Operating temperature: 
0°C to +40°C 
Operating humidity: 
10% to 80% RH (not condensing) 
Dimensions (LxDxH): 
170 x 110 x 42 mm 
Weight: 
0,63 kg 
Approvals: 
CE, EN55022 & EN55024 
 
 
5.4. Commonly used Ports 
 
TCP 25:...

Page 74

73 
5.5. Syslog Messages: Severity Level Definitions 
 
The Emergency level is the most severe type of message generated by ePowerSwitch 8XM and the 
Debug severity level is the least severe one. 
 
Severity Level 0, Emergency: 
The following messages appear at severity 0: 
- Continuous error! 
- An SMTP Client could not be created 
Severity Level 1, Alert: 
The following messages appear at severity 1: 
- Settings have been reinitialized through the serial connection 
- ePowerSwitch 8XM does not respond...

Page 75

 
74 Severity Level 6, Informational: 
The following messages appear at severity 6: 
- System has been started 
- Date & Time have been synchronized to a Network Time Server 
- User name : Outlet (number) of Master M0 has been switched ON 
- User name : Group (number) has been switched ON 
- Dry Contact Input (number) has been opened 
- Dry Contact Input (number) has been closed 
- Dry Contact Output (number) has been opened 
- Dry Contact Output (number) has been closed 
- Mail subject has been sent to...

Page 76

75 
STATEMENT OF CONFORMITY 
  
 
 
 
 
All modifications reserved 
 
 
 
STATEMENT OF CONFORMITY 
 
 
NEOL S.A.S. declares that this equipment is in compliance with the Electromagnetic 
Compatibility Directive 89/336/EEC and the Low Voltage Directive 73/23/EEC 
 
 
Application of Council Directives:     89/336/EEC, 92/31/EEC,   
                73/23/EEC, 93/68/EEC 
 
Standards to Which Conformity declared: EN 60950, EN 55022, EN 55024 
 
Manufacturers Name and Address:     NEOL S.A.S 
4 Rue Nationale...