Home > York > Furnace > York Model Gy8s User Instructions

York Model Gy8s User Instructions

    Download as PDF Print this page Share this page

    Have a look at the manual York Model Gy8s User Instructions online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1 York manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							035-20465-001 Rev. A (0704)
    USER’S INFORMATION,
    MAINTENANCE AND 
    SERVICE MANUAL
    HIGH EFFICIENCY
    TUBULAR HEAT EXCHANGER SERIES
    MODELS: GY8S / GM8S / LY8S / LM8S / LF8
    (Single Stage Upflow / Horizontal / LoNOx)
    EFFICIENCY
    RATING
    CERTIFIED
    This product was manufactured
    in a plant whose quality system
    is certified/registered as being
    in conformity with ISO 9001.
    The manufacturer recommends that the user read all sec-
    tions of this manual and keep the manual for future refer-
    ence.
     
    SECTION I: USER’S INFORMATION
    SAFETY
    1. The furnace area must be kept clear and free of combustible mate-
    rials, gasoline and other flammable vapors and liquids.
    2. Insulating materials may be combustible. The furnace must be
    kept free and clear of insulating materials. The furnace area must
    be examined when installed in an attic or other insulated space or
    when insulation is added to be sure that the insulation material has
    been kept away from the furnace.
    3. The furnace needs air for combustion in order to operate properly
    and safely. Do not block or obstruct air openings on the furnace,
    air openings to the area where the furnace is installed, or spaces
    around the furnace.
    4. Follow the instructions exactly as shown on the OPERATING
    INSTRUCTION LABEL or the Start-up and Shutdown Instructions
    on Page 3 of this manual when lighting the furnace or turning the
    furnace off.
    5. Should the gas supply fail to shut off or if overheating occurs, shut
    off the gas valve to the furnace before shutting off the electrical
    supply.
    6. Do not use this furnace if any part has been under water. A flood-
    damaged furnace is extremely dangerous. Attempts to use the fur-
    nace can result in fire or explosion. A qualified service agency
    should be contacted to inspect the furnace and replace all gas
    controls, control system parts, electrical parts that have been wet
    or the furnace if deemed necessary.
    FIRE OR EXPLOSION HAZARD - Failure to follow safety
    warnings exactly could result in serious injury, death, or prop-
    erty damage.
    — Do not store or use gasoline or other flammable
    vapors and liquids in the vicinity of this or any other
    appliance.
    —  WHAT TO DO IF YOU SMELL GAS:
    • Do not try to light any appliance.
    • Do not touch any electrical switch; do not use any phone 
    (including cell phone) in your building.
    • Leave the building immediately.
    • Immediately call your gas supplier from a neighbor’s 
    phone. Follow the gas supplier’s instructions.
    • If you cannot reach your gas supplier, call the fire depart-
    ment.
    —  Installation and service must be performed by a quali-
    fied installer, service agency or the gas supplier.
    CONTACT INFORMATION
    • Go to website at www.york.com click on “contact”, then click on “contact form” and follow the instructions.
    • Contact us by mail:
    York International
    Consumer Relations
    5005 York Drive
    Norman, OK 73069
    TABLE OF CONTENTSCONTACT INFORMATION   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
    USER’S INFORMATION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
    SAFETY   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
    INSTRUCTIONS FOR EXAMINING THE FURNACE 
    INSTALLATION   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
    HOW YOUR GAS FURNACE WORKS   . . . . . . . . . . . . . . . . . . . . . . 3
    START-UP AND SHUTDOWN INSTRUCTIONS  . . . . . . . . . . . . . . . 3
    Read the Instructions Below Before Trying to Start the Furnace . . 3
    Operating Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
    To Turn Off the Appliance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
    FURNACE USER MAINTENANCE   . . . . . . . . . . . . . . . . . . . . . . . . . 4
    Air Filters  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
    Removing Filters   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
    Blower Care  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
    Motor Lubrication  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
    SERVICE AND MAINTENANCE MANUAL   . . . . . . . . . . . . . . . . . . . . 5
    SAFETY SECTION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5FURNACE MAINTENANCE SECTION  . . . . . . . . . . . . . . . . . . . . . . .5
    FURNACE CLEANING SECTION  . . . . . . . . . . . . . . . . . . . . . . . . . . .5
    Burner Removal/Cleaning   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
    Cleaning the Heat Exchanger   . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
    SEQUENCE OF OPERATION   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
    Continuous Blower  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
    Intermittent Blower - Cooling   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
    Heating Cycle  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
    Hot Surface Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
    TROUBLESHOOTING   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
    FURNACE CONTROL DIAGNOSTICS  . . . . . . . . . . . . . . . . . . . . . . .6
    DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL   . . . . . .7
    REPLACEMENT PARTS LIST   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
    FIELD INSTALLED ACCESSORIES - NON-ELECTRICAL   . . . . . . .8
    REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . . .10
    WIRING DIAGRAM   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
    LIMITED WARRANTY  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 
    						
    							035-20465-001 Rev. A (0704)
    2Unitary Products Group
    7. NEVER . . .Store flammable materials of any kind near your fur-
    nace. Gasoline, solvents, and other volatile liquids should be
    stored only in approved containers outside your home. These
    materials vaporize easily and are extremely dangerous.
    8. NEVER . . .Store cleaning materials near your furnace. Materials
    such as bleaches, detergents, powdered cleansers, etc., can
    cause corrosion of the heat exchangers. 
    9. NEVER . . . Use the area around your furnace as a storage area
    for items which could block the normal flow of air. This flow of air is
    required for ventilation of the various furnace components.
    INSTRUCTIONS FOR EXAMINING THE FURNACE 
    INSTALLATION
    It is the owner’s responsibility to ensure that an annual inspection of the
    entire heating portion of the unit is made by a qualified service agency.
    Examine the furnace as outlined below in steps “1 - 6” before each
    heating season. Use Figure 3 for visual reference.
    1. Examine the heat exchanger, vent pipe, combustion air passes
    gas, vent connectors and chimney to be sure they are clear and
    free of obstructions.
    2. Examine the vent pipe making sure it is firmly in place, that it
    slopes slightly upward and is physically sound without holes and
    all of the connections are secure.
    3. Examine the return-air duct connections to make sure they are
    physically sound, sealed to the furnace casing, and the ducts ter-
    minate outside the space containing the furnace.
    4. Examine the furnace casing making sure the physical support is
    sound without sagging, cracks or gaps. Examine the furnace base
    making sure it is physically sound without cracks, gaps or sagging
    and has a good seal.
    5. Examine the furnace casing for obvious signs of deterioration.
    6. Examine the burner flames to make sure they are in good adjust-
    ment. Refer to the pictorial sketch shown in Figure 2 as a compari-
    son to the actual flame.  FIGURE 1: Component Locations
    FIRE OR EXPLOSION HAZARD
    This furnace is designed and approved for use with Nat-
    ural Gas and (LP) Propane Gas ONLY. DO NOT BURN
    ANY LIQUID FUEL OR SOLID FUEL IN THIS FURNACE.
    Burning any unapproved fuel will result in damage to the
    furnace heat exchanger, which could result in Fire, Per-
    sonal Injury, and/or Property Damage.
    VENT PIPE
    PRESUURE
    SWITCH
    SILICONE
    TUBE
    INDUCER
    SHIELD
    GAS VALVE
    FLAME
    SENSORINDUCED DRAFT
    ASSEMBLY
    INDUCED DRAFT
    MOTOR
    LIMIT
    SWITCH
    IGNITOR
    MANIFOLD
    PIPE
    SAFETY SHUTOFF
    SWITCH
    CONTROL
    BOARD FLUE
    COLLAR
    ELECTRICAL
    JUNCTION BOX
     FIGURE 2: Burner Flame Drawing
    BLUE CONE PORTION OF FLAME SHOULD
    ENTER HEAT EXCHANGER TUBE
     FIGURE 3: Furnace Examination Checkpoints
    4
    EXAMINE
    FURNACE
    CASING6
    5
    343 1
    6
    EXAMINE
    RETURN AIR
    DUCT
    CONNECTIONREMOVE
    PANEL
    TO EXAMINE
    BURNER
    FLAMES EXTERNAL HEAT EXCHANGER INTERNAL
    VENT COMBUSTION AIR PIPE. MUST
    REMOVE PANEL TO EXAMINE.
    EXAMINE ENTIRE
    FURNACE CASING
    SHOWN IN ALL
    DRAWINGS
    EXAMINE
    RETURN AIR
    DUCT
    CONNECTION
    (side or bottom) REMOVE
    PANEL
    TO EXAMINE
    BURNER
    FLAMESEXAMINE EXTERNAL
    VENT PIPE
    EXAMINE
    FURNACE
    CASING 
    						
    							035-20465-001 Rev. A (0704)
    Unitary Products Group3
    HOW YOUR GAS FURNACE WORKS
    Your furnace is a very easy appliance to take for granted. Season after
    season, it sits there in your home, keeping you warm and comfortable.
    For this reason, you may never have given much thought to the way
    your furnace operates. In order to get the safest and most efficient oper-
    ation from your furnace, you should understand how your furnace does
    its job.
    When you set your thermostat to provide more heat in your home, you
    are starting the heating cycle of the furnace. First, the inducer motor
    starts to purge the heat exchanger of any remaining gases. Next, the
    hot surface ignitor glows and after a warm-up period the gas valve
    opens and ignition occurs. A short time later, the blower starts and dis-
    tributes the warm air throughout the home. When the temperature set-
    ting on your thermostat is reached, the gas valve closes, the main
    burners are turned off, and the blower continues to run until the remain-
    ing warm air in the system is distributed. When the blower stops, the
    heating cycle has ended.
    START-UP AND SHUTDOWN INSTRUCTIONS
    Read the Instructions Below Before Trying to Start the 
    Furnace
    A. This appliance does not have a pilot. It is equipped with an ignition
    device which automatically lights the burner. Do not try to light the
    burner by hand.
    B. BEFORE OPERATING; smell all around the appliance area for
    gas. Be sure to smell next to the floor because some gas is
    heavier than air and will settle on the floor.
    C. Use only your hand to push the gas control switch to the “on” posi-
    tion. Never use tools. If the switch will not operate by hand, don’t
    try to repair it, call a qualified service technician. Force or
    attempted repair may result in a fire or explosion.
    D. Do not use this appliance if any part has been under water. Imme-
    diately call a qualified service technician to inspect the appliance
    and to replace any part of the control system and any gas control,
    which has been under water.
    Operating Instructions:
    1. STOP! Read the safety information above.
    2. Set the thermostat to the lowest setting.
    3. Turn off all electric power to the appliance.
    4. Remove furnace door.
    5. Move gas control switch to the “OFF” position. Do not force. See
    Figure 4.
    6. Wait five (5) minutes to clear out any gas. If you then smell gas,
    STOP! Follow “B” in the safety information above. If you don’t
    smell gas, go to next step.
    7. Move gas control switch to the “ON” position. Do not force. See
    Figure 4.
    8. Replace burner access panel.
    9. Turn on all electric power to the appliance.
    10. Set thermostat to the desired setting. Burner will light, which may
    take 30-60 seconds.
    11. After three (3) trials for ignition, if the appliance will not operate fol-
    low the instructions, “TO TURN OFF THE APPLIANCE” and call
    your service technician or gas supplier.
    To Turn Off the Appliance:
    1. Set the thermostat to lowest setting.
    2. Turn off all electric power to the appliance if service is to be per-
    formed.
    3. Remove burner access panel.
    4. Move gas control switch to the “OFF” position. See Figure 4.
    5. Replace burner access panel.
    NOTE: The spring-loaded safety cut-off switch, mounted under the
    blower deck will automatically cut off the electrical power supply
    to the furnace when the blower panel is removed. As a safety
    precaution, all electrical power and the gas supply to the furnace
    should be turned off before servicing.
    If you do not follow these instructions exactly, a fire or
    explosion may result causing property damage, personal
    injury, and/or loss of life.
    Should overheating occur, or the gas valve fail to shut off,
    turn the external manual gas valve in the gas supply line to
    the furnace to the “off” position and let the furnace cool off
    before shutting off the electrical power supply. Refer to
    Figure 5.
     FIGURE 4: Gas Valve
     FIGURE 5: Upflow Gas Piping
     FIGURE 6:  Horizontal Gas Piping
    INLET
    WRENCH
    BOSS
    INLET
    PRESSURE
    PORT
    ON
    OFF
    ON/OFF SWITCH
    (Shown in ON position)MAIN REGULATOR
    ADJUSTMENTOUTLET OUTLET
    PRESSURE
    PORT
    VENT PORT
    EXTERNAL MANUAL
    SHUTOFF VALVE
    TO GAS
    SUPPLY TO GAS
    SUPPLY
    GROUNDED JOINT UNION
    MAY BE INSTALLED
    INSIDE OR OUTSIDE UNIT. DRIP
    LEG
    MANUAL
    SHUT-OFF
    VA LV E
    DRIP
    LEG
    GAS
    PIPE
    GAS BURNERS
    GAS VALVE
    GAS
    PIPE
    DRIP
    LEGMANUAL
    SHUT-OFF VALVE 
    						
    							035-20465-001 Rev. A (0704)
    4Unitary Products Group
    FURNACE USER MAINTENANCE
    Every time the filters are changed the following items should be visually
    inspected:
    • Check combustion air and vent pipe for blockage or leakage.
    • Check all components to be sure they are in good condition and
    that there are no obvious signs of deterioration.
    • Check the drain lines to make sure there are no cracks or leaks.
    • Check for dirt or lint on any surfaces or on components. Do not try
    to clean any of the surfaces or components. Cleaning of the fur-
    nace and its components must be done by a qualified service pro-
    fessional.
    If, during the inspection of your furnace, you find any of the following
    conditions:
    • Excessive amounts of dust and lint on components.
    • Damaged or deteriorated components or surfaces.
    • Leaks or blockage in the vent pipe passages.
    • Water on any surface inside or outside of the furnace.
    Do not operate the furnace, call a certified dealer / servicing contractor
    to check and / or clean your furnace, or for more information if you have
    questions about the operation of your furnace.
    If all components appear to be in good operating condition, replace the
    front panels. Turn ON the gas and electrical power supplies to the fur-
    nace, and set thermostat to the desired temperature.
    Air Filters
    Dirty filters greatly restrict the flow of air and may cause damage to the
    moving parts of the furnace. If the filters become clogged the heat
    exchangers and blower motor could overheat resulting in a potentially
    dangerous situation. The filters should be checked every 3 months. On
    new construction, check the filters every week for the first four weeks
    and every three weeks after that, especially if the indoor fan is running
    continuously. When replacing the filter(s) you must use filters that are
    the same size as those recommended in Table 1. Never operate your
    furnace without a suitable air filter.
    Removing Filters
    Externally Mounted Air Filters
    The air filter should be located in a rack attached to the casing of the
    furnace or placed in the return air duct. You can gain access to the filter
    by pulling on the door or unscrewing the retaining screw, then slide the
    filter(s) out of its channel. Replace throw away filter(s) with the same
    size new filter(s). Throw away filter(s) may be replaced with cleanable
    filter(s) at this time. Cleanable filter(s) may be cleaned as described in
    the manufacturer instructions or as described below and then re-
    installed.
    To replace the filter after cleaning you must do the following:
    1. Slide filter into place.
    2. Snap the door on or place the door in position and tighten the
    retaining screws, if provided.
    3. Make sure the door is secure to the end of the filter rack.How to Clean your Filter
    High-velocity filters may be cleaned with a vacuum cleaner or washed
    with a garden hose. Be sure to shake off excess water and allow filter to
    completely dry before re-installing the filter.
    Blower Care
    Even with good filters properly in place, blower wheels and motors will
    become dust laden after long months of operation. The entire blower
    assembly should be inspected annually. If the motor and wheel are
    heavily coated with dust, they can be brushed and cleaned with a vac-
    uum cleaner. If the blower cannot be properly cleaned without removing
    it from the furnace, then this service must be performed by a qualified
    service agency.
    Motor Lubrication
    The motors in these furnaces are permanently lubricated, and do not
    require periodic oiling.
    Every time the filters are changed the following items should be visually
    inspected:
    • Check combustion air and vent pipe for blockage or leakage.
    • Check all components to be sure they are in good condition and
    that there are no obvious signs of deterioration.
    • Check the drain lines to make sure there are no cracks or leaks.
    • Check for dirt or lint on any surfaces or on components. Do not try
    to clean any of the surfaces or components. Cleaning of the fur-
    nace and its components must be done by a qualified service pro-
    fessional.
    If, during the inspection of your furnace, you find any of the following
    conditions:
    • Excessive amounts of dust and lint on components.
    • Damaged or deteriorated components or surfaces.
    • Leaks or blockage in the vent pipe passages.
    • Water on any surface inside or outside of the furnace.
    Do not operate the furnace, call a certified dealer / servicing contractor
    to check and / or clean your furnace, or for more information if you have
    questions about the operation of your furnace.
    If all components appear to be in good operating condition, replace the
    front panels. Turn ON the gas and electrical power supplies to the fur-
    nace, and set thermostat to the desired temperature.
    Before proceeding, be sure the area is well ventilated. Turn
    the thermostat OFF. If the blower is running, wait until it
    stops automatically. Turn OFF the gas and electrical power
    supplies to the furnace. Check all metal parts and surfaces
    to be sure they have cooled to room temperature before
    you begin.
    TA B L E  1 :  Filter Sizes
    Cabinet Size Side (in) Side (mm) Bottom (in) Bottom (mm)
    A 16 x 25 40.6 x 63.5 14 x 25 35.6 x 63.5
    A 16 x 25 40.6 x 63.5 14 x 25 35.6 x 63.5
    A 16 x 25 40.6 x 63.5 14 x 25 35.6 x 63.5
    B 16 x 25 40.6 x 63.5 16 x 25 40.6 x 63.5
    C (2) 16 x 25 (2) 40.6 x 63.5 20 x 25 50.8 x 63.5
    B 16 x 25 40.6 x 63.5 16 x 25 40.6 x 63.5
    B 16 x 25 40.6 x 63.5 16 x 25 40.6 x 63.5
    C (2) 16 x 25 (2) 40.6 x 63.5 20 x 25 50.8 x 63.5
    C 16 x 25 40.6 x 63.5 20 x 25 50.8 x 63.5
    C (2) 16 x 25 (2) 40.6 x 63.5 20 x 25 50.8 x 63.5
    D (2) 16 x 25 (2) 40.6 x 63.5 22 x 25 55.9 x 63.5
    Make sure you DO NOT move the clip on weight on the
    indoor fan wheel when cleaning the wheel. This weight is
    used to balance the wheel. Moving the weight will cause
    the fan wheel to vibrate. 
    						
    							035-20465-001 Rev. A (0704)
    Unitary Products Group5
    SECTION II: SERVICE AND MAINTENANCE 
    MANUAL
    SAFETY SECTION
    The following safety rules must be followed when servicing the
    furnace.
    FURNACE MAINTENANCE SECTION
    The furnace should be cleaned and adjusted by a certified dealer or
    qualified service contractor once a year or before the start of every
    heating season. The following items must be cleaned and serviced or
    replaced if there are signs of deterioration.
    1. The vent terminal.
    2. The furnace vent and combustion air intake passageways. Should
    it be necessary to service the vent/air intake system, the manufac-
    turer recommends this service be conducted by a qualified service
    agency. The operation of this appliance requires the reassembly
    and resealing of the vent/air intake system.
    3. The furnace burners, ignitor and flame sensor.
    4. The condensate collection and disposal system. If any disassem-
    bly of components containing flue or vent gases is required, a
    qualified service agency must perform the service.
    FURNACE CLEANING SECTION
    NOTE: The cleaning operations listed below must be performed only by
    a qualified service agency.
    Burner Removal/Cleaning
    The main burners should be checked periodically for dirt accumulation.
    If cleaning is required, follow this procedure:
    1. Turn off the electrical power to the unit.
    2. Turn off the gas supply at the external manual shut-off valve and
    loosen the ground union joint.
    3. Remove the upper access panel and remove the burner box
    cover.
    4. Disconnect wires from flame sensor, rollout switch and HSI igniter.
    Remove igniter carefully, as it is easily broken.
    5. Remove the screws that hold the burner box assembly to the vest
    panel and remove the assembly.
    6. Remove burners from the burner assembly.
    7. Burners may be cleaned by rinsing in hot water.
    8. Reassemble the burners in the reverse order.
    Cleaning the Heat Exchanger
    Lower Heat Exchanger Access
    1. Turn off the electrical power to the unit and turn off gas supply at
    the shutoff valve.
    2. Remove the blower and burner compartment access doors. Dis-
    connect the gas supply piping at the union to permit removal of the
    entire burner and gas control assembly from the vestibule panel.Use the wrench boss on the gas valve when removing or installing
    this piping. See Figure 4.
    3. Unplug the igniter from the wire harness. Disconnect sensor and
    rollout switch wires located on top of the air shield. Identify and
    note the location of all leads for ease of reinstallation. Also discon-
    nect the wires at the side rollout switches (upflow only) and the
    gas valve wires.
    4. Remove the screws holding the burner assembly to the vestibule
    panel and remove this assembly. Handle the assembly carefully
    since it contains the igniter, which is fragile and easily broken. The
    lower portion of the heat exchanger will now be exposed. To clean
    the burner assembly, use a vacuum cleaner, or remove the burn-
    ers as outlined in burner cleaning, and clean in hot water.
    Upper Heat Exchanger Access
    1. Perform steps 1-4 above.
    2. Disconnect vent piping from the vent motor assembly at the top
    panel on the furnace (upflow only). On downflow models, the vent
    pipe is secured to the vent motor outlet with a screw. Remove this
    screw before proceeding.
    3. Unplug the vent motor wires and ground wire. Remove the pres-
    sure switch tubing at the top on the vent motor housing.
    NOTE: It is recommended that replacement gaskets be available
    before removing vent motor.
    1. Remove six mounting screws that hold the vent motor to the
    restrictor plate. The surface is gasketed and the gasket can be
    reused if it is carefully removed. It is necessary to remove this
    assembly to gain access to the restrictor plate mounting holes.
    The assembly may be vacuumed if cleaning is necessary. If any
    vent assembly parts are damaged, replace with an entire new
    assembly (except for gaskets).
    2. Remove the perimeter screws attaching the restrictor plate assem-
    bly to the vestibule panel. The surface is also gasketed. The
    assembly, including the flue baffle plate (rear) may be vacuumed
    or cleaned with hot water if necessary.
    3. The upper portion of the heat exchanger is now accessible. With a
    long flexible wire brush, clean inside each tube at both the top and
    bottom. The brush must pass around the rear heat exchanger
    tubes. Vacuum loose scale and dirt from each tube.
    4. Clean - Replace all components in reverse order. Re-gasket all
    surfaces which required a gasket. Reconnect all wiring. Reattach
    vent pipe and gas supply lines before restoring service to furnace.
    Restore electrical power, check gas supply piping for leaks, and
    then verify furnace operation.
    SEQUENCE OF OPERATION
    The following describes the sequence of operation of the furnace. Refer
    to Figure 1 for component location.
    Continuous Blower
    Cooling/heating thermostats have a fan switch that has an ON and
    AUTO position. In the ON position the thermostat circuit is completed
    between terminals R and G. The motor will operate on the speed tap
    wire that is connected to the “HI COOL” cooling terminal on the control
    board. To obtain a constant air circulation at lower flow rate, change the
    high-speed wire to either the medium speed wire or the low speed wire.
    ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD
    Failure to follow safety warnings exactly could result in
    dangerous operation, serious injury, death or property
    damage.
    Improper servicing could result in dangerous operation,
    serious injury, and death or property damage.
    • Before servicing, disconnect all electrical power to the fur-
    nace. 
    • When servicing controls, label all wires prior to disconnect-
    ing. Reconnect wires correctly. 
    • Verify proper operation after servicing.
    Label all wires prior to disconnection when servicing
    controls. Wiring errors can cause improper and danger-
    ous operation. Verify proper operation after servicing. 
    						
    							035-20465-001 Rev. A (0704)
    6Unitary Products Group
    Intermittent Blower - Cooling
    Cooling/heating thermostats have a fan switch that has an ON and
    AUTO position. In the AUTO position the thermostat circuit is completed
    between terminals R and G when there is a call for cooling. The motor
    will operate on the speed tap wire that is connected to the “HI COOL”
    cooling terminal on the control board. The fan off setting is fixed at 60
    seconds to improve cooling efficiency.
    Heating Cycle
    When the thermostat switch is set on HEAT and the fan is set on AUTO,
    and there is a call for heat, a circuit is completed between terminals R
    and W of the thermostat. When the proper amount of combustion air is
    being provided, the pressure switch will close, the ignition control pro-
    vides a 17-second warm-up period, the gas valve then opens, the gas
    starts to flow, ignition occurs and the flame sensor begins its sensing
    function. The blower motor will energize 30 seconds after the gas valve
    opens, if a flame is detected. Normal furnace operation will continue
    until the thermostat circuit between R and W is opened, which causes
    the ignition system and gas valve to de-energize and the burner flames
    to be extinguished. The vent motor will operate for 15 seconds and the
    blower motor will operate for the amount of time set by the fan-off delay
    jumper located on the control board. See Figure 10. The heating cycle
    is complete, and ready for the start of the next heating cycle.
    If the flame is not detected within 7 seconds of the gas valve opening,
    the gas valve is shut off and a retry operation begins. If the flame is lost
    for 2 seconds during the 10-second stabilization period, the gas valve is
    shut off and a retry operation begins. During a retry operation, the vent
    motor starts a 15 second inter-purge and the ignitor warm-up time is
    extended to 27 seconds. If the flame is established for more than 10
    seconds after ignition during a retry, the control will clear the ignition
    attempt (retry) counter. If three retries occur during a call for heat, the
    furnace will shut down for one hour. If at the end of the one hour shut
    down there is a call for heat, the furnace will initiate a normal start cycle.
    If the problem has not been corrected the furnace will again lockout
    after three retries.
    A momentary loss of gas supply, flame blowout, or a faulty flame probe
    circuit will result in a disruption in the flame and be sensed within 1.0
    seconds. The gas valve will de-energize and the control will begin a
    recycle operation. A normal ignition sequence will begin after a 15 sec-
    ond inter-purge. If during the five recycles the gas supply does not
    return, or the fault condition is not corrected the ignition control will lock-
    out for 60 minutes.During burner operation, a momentary loss of power for 50 milliseconds
    or longer will de-energize the gas valve. When the power is restored,
    the gas valve will remain de-energized and the ignition sequence will
    immediately restart.
    Hot Surface Ignition System
    TROUBLESHOOTING
    The following visual checks should be made before troubleshooting:
    1. Check to see that the power to the furnace and the ignition control
    module is ON.
    2. The manual shut-off valves in the gas line to the furnace must be
    open.
    3. Make sure all wiring connections are secure.
    4. Review the sequence of operation. Start the system by setting the
    thermostat above the room temperature. Observe the system’s
    response. Then use the troubleshooting section in this manual to
    check the system’s operation.
    FURNACE CONTROL DIAGNOSTICS
    The furnace has built-in, self-diagnostic capability. If a system problem
    occurs, a blinking LED shows a fault code. The LED can flash red,
    green or amber to indicate various conditions. It is located behind a
    clear view port in the blower compartment door.
    The control continuously monitors its own operation and the operation
    of the system. If a failure occurs, the LED will indicate the failure code. If
    the failure is internal to the control, the light will stay on continuously. In
    this case, the entire control should be replaced, as the control is not
    field repairable.
    Flash sequence codes 1 through 10 are as follows: LED will turn “on”
    for 1/4 second and “off” for 1/4 second. This pattern will be repeated the
    number of times equal to the code. For example, six “on” flashes equals
    a number 6 fault code. All flash code sequences are broken by a 2 sec-
    ond “off” period.
    SLOW GREEN FLASH: Normal operation.
    SLOW AMBER FLASH: Normal operation with call for heat.
    RAPID RED FLASH: Twinning error, incorrect 24V phasing. Check
    twinning wiring.
    RAPID AMBER FLASH: Flame sense current is below 1.5 microamps.
    Check and clean flame sensor. Check for proper gas flow.
    1 RED FLASH: This indicates that flame was sensed when there was
    not a call for heat. With this fault code the control will turn on both the
    inducer motor and supply air blower. A gas valve that leaks through or
    is slow closing would typically cause this fault.  FIGURE 7: Typical Heat/Cool Speed Tap Connections
    PARK
    PARK
    HI COOL
    HEAT
    EAC
    L1
    XFMR
    HUMNEUTRALS
    YELLOW - MED. LOW SPEED
    BLACK - HIGH SPEED
    BLUE -MED. HIGH SPEED
    FAN OFF
    ADJUSTMENT
    JUMPER
    Y/Y2
    WRG
    C
    HOT SURFACE IGNITION SYSTEM
    Do not attempt to light this furnace by hand (with a
    match or any other means). There may be a potential
    shock hazard from the components of the hot surface
    ignition system. The furnace can only be lit automatically
    by its hot surface ignition system.
    Never bypass any safety control to allow furnace opera-
    tion. To do so will allow furnace to operate under poten-
    tially hazardous conditions.
    Do not try to repair controls. Replace defective controls
    with UPG Source 1 Parts.
    Never adjust pressure switch to allow furnace operation. 
    						
    							035-20465-001 Rev. A (0704)
    Unitary Products Group7
    2 RED FLASHES: This indicates that the normally open pressure
    switch contacts are stuck in the closed position. The control confirms
    these contacts are open at the beginning of each heat cycle. This would
    indicate a faulty pressure switch or miswiring.
    3 RED FLASHES: This indicates the normally open pressure switch
    contact did not close after the inducer was energized. This could be
    caused by a number of problems: faulty inducer, blocked vent pipe, bro-
    ken pressure switch hose or faulty pressure switch.
    4 RED FLASHES: This indicates that a primary or auxiliary limit switch
    has opened its normally closed contacts. With this fault code the control
    will operate the supply air blower and inducer. This condition may be
    caused by: dirty filter, improperly sized duct system, incorrect blower
    speed setting, incorrect firing rate or faulty blower motor.
    5 RED FLASHES: This fault is indicated if the normally closed contacts
    in the rollout switch opens. The rollout control is manually reset. If it has
    opened, check for proper combustion air, proper inducer operation, and
    primary heat exchanger failure or burner problem. Be sure to reset the
    switch after correcting the failure condition.
    6 RED FLASHES: This indicates that after the unit was operating, the
    pressure switch opened 4 times during the call for heat. If the main
    blower is in a “Delay on” mode it will complete it, and any subsequent
    delay off period. The furnace will lock out for one hour and then restart.
    7 RED FLASHES: This fault code indicates that the flame could not be
    established. This no-light condition occurred 3 times (2 retries) during
    the call for heat before locking out. Low gas pressure, faulty gas valve,
    faulty hot surface ignitor or burner problem may cause this. The furnace
    will lock out for one hour and then restart.
    8 RED FLASHES: This fault is indicated if the flame is lost 5 times (4
    recycles) during the heating cycle. This could be caused by low gas
    pressure or faulty gas valve. The furnace will lock out for one hour and
    then restart.
    9 RED FLASHES: Indicates reversed line voltage polarity or grounding
    problem. Both heating and cooling operations will be affected. Check
    polarity at furnace and branch. Check furnace grounding. Check that
    flame probe is not shorted to chassis.
    10 RED FLASHES: Gas valve energized with no call for heat. Check
    gas valve and gas valve wiring.
    11 RED FLASHES: This indicates that a primary or auxiliary limit switch
    has opened its normally-closed contacts and has remained open for
    more than five minutes. This condition is usually caused by a failed
    blower motor or blower wheel.
    STEADY ON RED: Control failure. Replace control board.60-MINUTE AUTOMATIC RESET FROM LOCKOUT: This control
    includes a “watchdog” type circuit that will reset from a lockout condition
    after 60 minutes. Operational faults 6,7,8 will be reset. This provides
    protection to an unoccupied structure if a temporary condition exists
    causing a furnace malfunction. An example would be a low incoming
    gas supply pressure preventing unit operation. When the gas pressure
    is restored, at some point the “watchdog” would restart the unit and pro-
    vide heat for the house.
    NOTE: If a flame is detected the control flashes the LED for 1/8 of a
    second and then enters a flame stabilization period.
    DIAGNOSTIC FAULT CODE STORAGE AND 
    RETRIEVAL
    The control in this furnace is equipped with memory that will store up to
    five error codes to allow a service technician to diagnose problems
    more easily. This memory will be retained even is power to the furnace
    is lost. This feature should only be used by a qualified service tech-
    nician. 
    The control stores up to five separate error codes. If more than five
    error codes have occurred since the last reset, only the five most recent
    will be retained. The furnace control board has a button, labeled LAST
    ERROR that is used to retrieve error codes. This function will only work
    if there are no active thermostat signals. So any call for heating, cooling
    or continuous fan must be terminated before attempting to retrieve error
    codes. 
    To retrieve the error codes, push the LAST ERROR button. The LED on
    the control will then flash the error codes that are in memory, starting
    with the most recent. There will be a two-second pause between each
    flash code. After the error codes have all been displayed, the LED will
    resume the normal slow green flash after a five second pause. To
    repeat the series of error codes, push the button again.
    If there are no error codes in memory, the LED will flash two green
    flashes. To clear the memory, push the LAST ERROR button and hold it
    for more than five seconds. The LED will flash three green flashes when
    the memory has been cleared, then will resume the normal slow green
    flash after a five-second pause.IGNITION CONTROL (P/N 031-01973-000)
    Normal flame sense current is approximately
    3.7 microamps DC (µa)
    Low flame signal warning starts at 1.5 microamps.
    Low flame signal control lockout point is
    0.9 microamps DC (µa) 
    						
    							035-20465-001 Rev. A (0704)
    8Unitary Products Group
    SECTION III: REPLACEMENT PARTS LIST
    FIELD INSTALLED ACCESSORIES - NON-ELECTRICAL
     FIGURE 8: Furnace Control Event Schedule
    Thermostat Calling for HeatThermostat Satisfied
    (Seconds)
    THERMOSTAT
    INDUCER
    IGNITOR
    MAIN VALVE
    HUMIDIFIER
    ELECTRONIC
    AIR CLEANER
    CIRCULATING
    BLOWEROFF
    OFF
    OFF
    OFF
    OFF
    OFF
    OFF
    ON
    ON
    ON
    ONOFF
    OFF
    OFF
    OFFON
    ON
    ON
    OFF
    OFF
    OFFOFF
    OFF
    OFF
    OFF 15 Sec.
    Post
    Purge Fan on Delay
    30 Seconds 0
    2
    17 2252
    0
    60, 90, 120, 180 SEC.
    Selectable Fan Off Delay
    TABLE 2: Field Installed Accessories - Non-electrical
    MODEL NO. DESCRIPTION USED WITH
    1NP0347
    PROPANE (LP) CONVERSION KIT040, 080,100
    1NP0348060, 115, 130
    1PS0301
    HIGH ALTITUDE PRESSURE SWITCH KIT 
    (Does Not Include Orifices)SEE CHART BELOW 1PS0302
    1PS0311
    1PS0312
    1BR0314
    EXTERNAL BOTTOM RETURN FILTER, with High Velocity Filter for Horizontal 
    Application for Upflow Bottom Return Application.14-1/2” CABINETS
    1BR031717-1/2” CABINETS
    1BR032121” CABINETS
    1BR032424-1/2” CABINETS
    1CB0314
    COMBUSTIBLE FLOOR BASE for Downflow Units14-1/2” CABINETS
    1CB031717-1/2” CABINETS
    1CB032121” CABINETS
    1CB032424-1/2” CABINETS
    1SR0302 EXTERNAL SIDE FILTER RACK - with Filter Rack (6 pack) ALL MODELS
    HIGH PRESSURE SWITCH 
    Input (MBH) Output (MBH)2,000 Ft. to 5,500 
    Ft.>5,500 Ft. to10,000 
    Ft.
    40 32 1PS0301 1PS0301
    60 48 1PS0301 1PS0301
    80 64 1PS0302 1PS0302
    100 80 1PS0312 1PS0311
    115 92 1PS0312 1PS0311
    130 104 1PS0312 1PS0311 
    						
    							035-20465-001 Rev. A (0704)
    Unitary Products Group9
    27
    3
    30
    265 10 92224112 29
    8
    23
    12
    7
    17
    19
    21
    13
    1
    16
    154
    4340
    28
    25
    39
    37 6,20
    31
    12A
    7
    3524
    3612
    19
    11 
    						
    							035-20465-001 Rev. A (0704)
    10Unitary Products Group
    ITEM DESCRIPTION
    MOTOR
    1MOTOR,DIRECT DRIVE BLOWER
    2 MOTOR,VENTOR ASS’Y
    ELECTRICAL
    3 CAPACITOR
    4 CONTROL, HIGH LIMIT
    5 CONTROL, FURACE
    6IGNITER
    7 SENSOR, FLAME
    8 SWITCH, AIR PRESSURE   [1LP]
    9 SWITCH, DOOR                     [SW]
    10 TRANSFORMER
    11 VALVE, GAS
    12 CONTROL, LIMIT (Top)
    12ACONTROL, LIMIT (Side, 2 Req’d)
    13CONTROL, AUX LIMIT (2 Req’d)
    14* FUSE
    AIR MOVING
    15 HOUSING, BLOWER
    16 WHEEL, BLOWER
    16A PANEL, FILLER WRAP
    FABRICATED PARTS
    17 SHIELD, SECONDARY AIR
    18* BAFFLE, FLUE
    19 BURNER, MAIN GAS
    20 BRACKET, IGNITER
    21 DECK, BLOWER (Rear)
    22 DECK, FRONT
    23 HEAT EXCHANGER ASS’Y
     (Primary) 
    24 MANIFOLD, GAS
    25 PANEL, VEST ACCESS (Burner)
    26 PAN, BASE
    27 PANEL, BLOWER ACCESS 
    28 PANEL, TOP
    29 WRAPPER, INSULATED
    30 CHANNEL, TOE PLATE
    31 BASE FRAME, SIDE (2 Req’d)
    32* PLATE, RESTRICTOR
    33* SHIELD, INDUCER 
    34 BRACKET, ROLL-OUT SWITCH
    MISCELLANEOUS
    35* FILTER
    36* RACK, FILTER
    37 PLUG HOLE WINDOW CLEAR-.875”
    38 ORIFICE, BURNER
     (Natural #45)
    39 HANDLE, DOOR
    40 COLLAR, FLUE
    41* GROMMET, 1/2” DIA.
    42* GASKET, RESTRICTOR PLATE
    43 TUBING, SILICONE
    44* SPRING, DOOR
    45* WIRING DIAGRAM
    46* WIRING HARNESS
    47* ISOLATOR, TUBE (3 Req’d)
    48* ISOLATOR, WASHER (3 Req’d
    )
    49* ISOLATOR, SLEEVE (3 Req’d)
    50* MOTOR MOUNT
    51* BEZEL/LOGO PLATE ASSY
    52* LO-NOX SCREEN (L-Models only) ITEM DESCRIPTION
    NOTE: *Not Shown
    Major components and suggested stocking items are shown with shaded item number.
    REPLACEMENT PART CONTACT INFORMATION
    This is a generic parts list. To request a complete parts list, refer to the contact information below:
    • Visit our website at www.source1parts.com for the following information:
    1. Search for a part or browse the catalog.
    2. Find a dealer or distributor.
    3. Customer Service contact information.
    a. Click on the “Brand Links” button
    b. Click on the “Customer Service” button
    • You can contact us by mail. Just send a written request to:
    York International
    Consumer Relations
    5005 York Drive
    Norman, OK 73069 
    						
    All York manuals Comments (0)