Home > Toshiba > Communications System > Toshiba Strata Vi Electronic Key Telephone System Installation And Maintenance Manual

Toshiba Strata Vi Electronic Key Telephone System Installation And Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Toshiba Strata Vi Electronic Key Telephone System Installation And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 566 Toshiba manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							1, All models of the External 
    Power Supply Assembly (EPSA) are 
    equipped with a built-in wall mounting 
    bracket, as shown in Figure 1, to allow 
    the EPSA to be mounted on a wall or 
    other flat) vertical surface. 
    1 I 
    SPARE 
    FUSES 
    Unpack and inspect the EPSA 
    and the enclosed hardware. The fol- 
    lowing hardware, which is required to 
    mount and connect the EPSA to the 
    system, is supplied with each EPSA. 
    ANCHOR 
    TOGGLE? 
    FLANGE 
    I 
    TOG&ER 
    NECK LEGS 
    2 T.C. Toggler Wall Fasteners 
    (Figure 2). 
    2 #I4 Hex Head Sheet Metal 
    Screws. 
    1 Toggler Key. 
    1 Template P/N 117260-001 (to 
    space the wall fasteners 
    properly). 
    1 AC Fuse (spare) 
    P/N 
    amp, 
    1. DC Fuse 
    (spare) PIN 
    116438-030 (F2, 10 
    amp, 
    Fast-BLO, 32 VDC). 
    1 16 AWG, 3 wire Jacketed 
    Cable (54 inches). 
    Choose a suitable location on 
    a vertical surface for the EPSA, and 
    attach the P/N 117260-001 template to 
    that location temporarily. Use a spirit 
    level to verify that the indicated 
    drilling points are level. 
    Place punch marks on the 
    mounting surf ace through the 
    1r+cr 
    marked drilling positions on the 
    template. 
    Enlarge the two punch marks 
    an l/&inch drill bit. 
    With a 5/16-inch bit, drill 
    surface to 
    les. 
    Press the anchoring legs of a 
    r together and insert them into 
    one of the anchoring holes, as shown in 
    Figure 3. 
    Insert the toggler into the 
    hole until the neck flange is flush with 
    the mounting surface. If it is difficult 
    to insert it completely by hand, tap it 
    lightly with a hammer.  
    						
    							Insert a toggler key into the 
    small hole in the neck of the fastener, 
    as shown in Figure This should 
    cause the anchoring legs to !fpop’l 
    open. Even if the mounting surface is 
    too thick to permit the legs to open 
    fully, adequate support for the EPSA 
    should be provided when the screws are 
    in place. Remove the toggler key. 
    second hole. 
    Thread the #14 hex head 
    sheet metal screws into the small holes 
    in the center of the togglers. Leave 
    approximately 3/16-inch clearance be- 
    tween the bottom of each screw head 
    and the mounting surface (Figure 5). Align 
    the EPSA mounting 
    bracket’s holes with the sheet metal 
    screws as shown in Figure 6. Place 
    the EPSA against the mounting surface 
    with the screws protruding through the 
    holes. 
    Lower the EPSA so that the 
    narrower portions of the holes slip over 
    the screws and the weight of the EPSA 
    is supported. Tighten the screws. 
    Remove the spare fuses from 
    the hardware carton.  
    						
    							,’ 
    Place the spare 10 amp DC 
    fuse in the center fuse storage clip 
    located on the side panel of the EPSA 
    (Figure 6). 
    Place the spare 5 amp SLO- 
    BLO AC fuse in the clip below the DC 
    fuse clip. 
    Remove and inspect the fuses 
    that were shipped inside the EPSA. If 
    the visual inspection reveals a de- 
    fective fuse, remove the appropriate 
    spare from its storage clip and replace 
    the defective fuse. (Order anot her 
    spare fuse.) 
    The Power Battery Back-up 
    Assembly (PBBU) in Figure 7 is an 
    optional PCB which may be installed in 
    the EPSA 104 to interface with two 
    auxiliary 12V batteries. In the event 
    of an electrical power failure, the 
    PBBU provides an automatic battery 
    power source, permitting a typical 
    STRATA VI system to continue normal 
    operations for up to 12 hours. 
    BATTERY 
    BATTERY 
    PROTECTION 
    FUSE Hi)LDEf 
    i TAN PIN 
    The PBBU contains a voltage 
    sensing circuit which causes an elec- 
    tromechanical relay to connect the 
    back-up battery power supply to the 
    system before the EPSA output voltage 
    drops below 21VDC (at which point 
    system functions would be disrupted and 
    existing calls would be disconnected). 
    When the normal source of 
    electrical power is restored, the volt- 
    age sensing circuit relay will disconnect 
    the standby battery power source. 
    If the standby battery power 
    source output falls below 21VDC while 
    it is connected to the system, the 
    voltage sensing circuit will cause the 
    relay to disconnect the standby battery 
    from the system. 
    The standby battery’ power 
    supply will not reconnect unless: 
    The normal source of electrical 
    power is restored, causing the 
    PBBU to disconnect the battery 
    power supply from the system, or... 
    The “Battery Override” switch 
    ures 7 and 8) is placed in the 
    position, or... 
    The depleted batteries are re- 
    placed by a freshly charged pair 
    and the “Battery Override” switch 
    is turned on and then released. 
    The PBBU also contains cir- 
    cuitry to provide the charge current 
    necessary to maintain the batteries at 
    a satisfactory level of charge while the 
    STRATA VI system is in normal oper- 
    ation. 
    An external fast charger may 
    also be connected across the battery 
    output terminal connections. 
    The PBBU kit contains the 
    following items:  
    						
    							TERMINAL 
    ST RIP 
    C FUSE 
    PBBU-Power battery backup PCB. 
    Fuse-A spare battery protection 
    fuse. 
    Cable Clamp-A 
    7/l 6-in e cable 
    clamp which may be needed to 
    secure the wiring harness inside 
    the EPSA. 
    “PBBU-REV 3”--An adhesive-backed 
    decal to be placed on the front 
    face of the EPSA. 
    Warning Tag-A warning tag to be 
    attached to the EPSA 115VAC 
    power cord. 
    In addition to those items 
    supplied in the PBBIJ kit, the following 
    additional items are needed to install a 
    PBBU in an EPSA: Two Batteries-Two 12V/80 amp- 
    hour, lead-acid, automotive-type, 
    maintenance-free batteries are re- 
    commended. he procedures in 
    Paragraph 
    assume batteries 
    with side-mounted 
    terminals are 
    used. 
    Battery Rack and Separator-A 
    battery rack and separator should 
    be used to secure the batteries to 
    prevent tipping and spilling of bat- 
    tery acid or accidental shorting of 
    the battery terminals. 
    Two-Wire Connecting Cable-A 2- 
    wire connecting cable terminating 
    at one end with 3/8-in, ring ter- 
    minals and at the other end with 
    l/8-in. hooked spade terminals is 
    required to provide the connection  
    						
    							between the batteries and 
    the 
    EPSA. The minimum wire size 
    must be determined by the loop 
    length of the connecting cable as 
    indicated in Table A. 
    12 ft. 16 gauge 
    20 ft. 14 gauge 
    30 ft. 12 gauge 
    50 ft. 10 gauge 
    Single Wire Cable--A 16 AWG sin- 
    gle wire cable, approximately 1% 
    inches in length and equipped with 
    ring terminals, 
    is required to con- 
    nect the two batteries in series. 
    Cable Clamp-A cable clamp should 
    be used to relieve strain on the 
    battery cable to prevent cable 
    movement from affecting the bat- 
    teries. 
    Battery Fuse-A 10 amp, 32V (min- 
    imum) fuse, or a 10 amp DC in- 
    stantaneous tripping circuit breaker 
    is to be located adjacent to the 
    batteries in series with the nega- 
    tive lead of the 2-wire connecting 
    cable. The battery fuse (or cir- 
    cuit breaker) is required to protect 
    the batteries from damage due to a 
    power surge or a short circuit.. 
    Hex Head Bolts-Four 3/8in. hex 
    head bolts are required to connect 
    the cable terminals to the batteries. 
    Washers-Eight 3/8-in. flat washers 
    and four 3/8-in. internal-tooth lock 
    washers are required for the above 
    cable terminal connections. 
    Battery Cabinet-If the batteries 
    are not located in a well-venti- 
    lated closet or other secure area, 
    protected from fire or sparks, a 
    properly ventilated protective eabi- 
    net is required to safeguard them. Verify that the power switch 
    on the MTOU is in the 
    position, 
    and then disconnect the EPSA’s 115 
    VAC power cord.  
    						
    							Remove the terminal stri 
    m the 
    9 
    termin * 
    2. The EPSA cover is secured by 
    seven screws. 
    Viewing the EPSA as if 
    it is wall-mounted, two screws will be 
    located at the rear edge of the top of 
    it, three on the side facing outward 
    and two on the rear edge of the bottom. 
    5 Remove all seven screws. 
    Remove the cover and set it 
    aside. 
    Locate and trace the multi- 
    wire harness in the lower portion of 
    the EPSB (the 
    area away from the 
    built-in mounting bracket). The harness 
    originates from the transformer and the 
    terminals and fuse holders mounted in 
    the control panel, This harness ter- 
    minates in a rust-colored square eon- 
    nectar. 
    The harness is secured to the 
    bottom of the chassis with a cable 
    clamp as shown in Figure 10, Loosen 
    the screw and nut slightly to allow 
    movement of the harness, 
    NICKEL-PLATED 
    HOLE PLUGS 
    Mounted in the EPSA control 
    are two nickel-plated hole plugs. 
    Bend in the retaining tabs on both 
    plugs; remove and discard them. 
    Un-ivrap the PBBU and locate 
    the screw in the PBBU’s mounting 
    bracket (Figure 11). 
    Remove and save 
    the screw. 
    BATTERY 
    OVERRIDE 
    BUTTON 
    I 
    SCREW 
    CONNECTOR 
    Slip the PBBU’s battery pro- 
    tection fuse holder and the battery 
    override button through their respective 
    ports in the control panel (Figure 11). 
    The PBBU’s mounting bracket should be  
    						
    							flush against the rear of the control 
    panel with the fuse holder and override 
    button protruding through it. 
    The 
    harness should flow around the PBBU 
    PCB, with no wires beneath it. 
    Align the two tan-colored 
    PBBU pins with the two holes in the 
    heat sink (Figure 10). 
    Press the pins 
    into the holes until they catch and hold 
    the PBBU PCB. 
    Use the previously removed 
    screw and secure the PBBU mounting 
    bracket to the control panel. See 
    Figure 11. 
    Plug the rust-colored eon- 
    nectar into the nine-hole jack 
    center of the PBBU PCB. 
    force the connector’s prongs into the 
    jack, they are keyed so that they can 
    be mated in only one position. 
    Replace the EPSA cover and 
    secure it with the 
    seven screws 
    originally removed. 
    Press in the battery over- 
    button (Figure 8). 
    If it catches 
    and stays in, press it again to cause it 
    to release and protrude out of the 
    control panel. Out is off, and the 
    position of the button must be in for 
    the EPSA to operate normally. 
    Remove the spare fuse from 
    the PBBU kit. If the original fuse is 
    missing or defective, replace it with 
    the spare. If not, put the spare fuse 
    in the holder located on the side of 
    the EPSA away from the control panel. 
    Remove the warning tag from 
    the kit and tie it to the power cord 
    where it emerges from the EPSA. 
    A l’PBBU-REV 3” decal must 
    be placed on the control panel of the EPSA. 
    Remove the decal from the kit, 
    peel the backing off, and place it on 
    the control panel (Figure 8). 
    Select a location for the 
    batteries near the EPSA. 
    The loop 
    length of the cable connecting them to 
    the EPSA will determine the minimum 
    gauge wire which can be used in the 
    cable. See Table A. 
    Secure the batteries in the 
    battery 
    rack and separator, which 
    should be located in a minimum access 
    area, such as a 
    closet or a well 
    ventilated cabinet. 
    Verify that battery over- 
    utton is in the 
    position (out). 
    Loosen the two screws on the 
    terminal strip identified as 24V/BAT- 
    TERY. 
    Attach the cable’s two spade 
    tips to these connectors. 
    Each wire,  
    						
    							as well as the EPSA terminals, are 
    marked positive (+) or negative (-). 
    See Figure 12. Natch positive to 
    positive and negative to negative. 
    Connect the battery fuse (or 
    circuit breaker) lead to the negative 
    terminal on one battery (Figure 13). 
    CABLE MARKER 
    WASHER/ 
    / 
    HEX HEAD BOLT/ 
    Attach the 
    negative wire 
    from the connecting 
    cable to the 
    r battery. fuse (or circuit breaker). 
    Connect the positive wire to 
    e positive pole of the battery to 
    which the fuse connected (see 
    Figure 12). Connect one end of the sin- 
    gle-wire cable to the positive terminal 
    on the battery with the fuse. Connect 
    the other end to the negative terminal 
    on the battery without the fuse (Figure 
    12). 
    Plug the AC power cord in, 
    and verify that the indicator is 
    lit. 
    lit to indicate the batteries are 
    supplying electrical power as needed. 
    Replace the terminal strip 
    cover and test the STRATA VI system 
    functions under both AC and battery 
    back-up power.  
    						
    							TABLE OF CONTENTS e - a a e a 0 e 0. e . $0 a a e e e e . e . . a. e a. e a 
    INTKODUCTION s . e . . . . e o s o e. a a e a a e e o 0. ~~0*~*.~*~~.* 
    PROGRAitiMING PROCEDUKES o . q e a e. a e a -. . a *. II a -. *. q n. a a 
    GENERAL . . q a . + a s . . e o . . e e s s o e e a a 0. a 
    PREPARATION e a a 0 a. a.. . . . . . . . . . . . . . . . . . . . . . . . . 
    SYSTEM OPTIONS e a + a s a n o . s e . . e **.*.1o*e.*..am*** 
    CO LINE OPTIONS . Q a a e a e . . .e a.. .*,***...eaanaa* 
    STATION OPTIONS . . . o s a +. e . . e a e . o q a e e . . . 0.. e 0. e 
    SYSTEM KECORD SHEETS q . s . e e e o e . . o . . o a e . a o n a 
    TABLE l--SYSTEM, STATION & CO LINE CP’I’IONS . * e . a 
    TABLE 2-TOLL RESTRICTION CLASSIFIC4TION . . a 0 0 a 
    INITIALIZATION e . e . a e e . o . a e . . e . a a a a**~~.*~~o.~* 
    SYSTEM DATA ENTRY e e s . a 0 . a . s e a e e e . 0.. e a.. . . . e . 
    TABLE LIST 
    TABLE 3-INI~I&&d DATA *eD.o.aa*e’.‘,* : : : : : : : : : : : : : 
    TABLE d--SYSTEM ASSIGNMENTS-BASIC 
    TABLE 5-SYSTEM ASSIGNMENTS-OPTIONS’ ‘* ’ 1 1 1 1 1 : 1 1 1 1 
    TABLE &--AUTO RECALL PROM HOLD TIMING 
    TABLE 7--AUTO RELEASE ON HOLD ASSIGNMENT* : ‘.‘: : : : 
    TABLE 8--AUTO RELEASE ON HOLD TIMING ~ ~ ~ e e a. s a. 
    TABLE 9-PBX BACK-UP a o . . e . e e . . 
    a a *. .**s..v.* 
    TABLE lo-PBX ACCESS CODES 
    TABLE ll-TOLL RESTRICTION DISABLE’ : : : . o.ee**e*. 
    *. 0*ee.a.m 
    TABLE 12-TOLL RESTRICTION EXCEPTION CODES , e . . e 
    TABLE 13-STATION CO LINE ACCESS 
    TABLE 14-STATION CLASS 3F SERVICE ‘a*e’ ’ : : : : : : : : : : 
    TABLE 15-TOLL RESTRICTION CLASS . a . : m . 
    TABLE 16-STATION OUTGOING RESTRICTION ~ : : : : : : : : : 
    TABLE 17-CO RINGING ASSIGNMENTS-DAY 
    TABLE 18-C(3 RINGING ASSIGN;VIENTS-NITE ~*a’:e* : : : : : : :  
    						
    All Toshiba manuals Comments (0)

    Related Manuals for Toshiba Strata Vi Electronic Key Telephone System Installation And Maintenance Manual