Home
>
Toshiba
>
Communications System
>
Toshiba Strata Vi Electronic Key Telephone System Installation And Maintenance Manual
Toshiba Strata Vi Electronic Key Telephone System Installation And Maintenance Manual
Have a look at the manual Toshiba Strata Vi Electronic Key Telephone System Installation And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 566 Toshiba manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
1, All models of the External Power Supply Assembly (EPSA) are equipped with a built-in wall mounting bracket, as shown in Figure 1, to allow the EPSA to be mounted on a wall or other flat) vertical surface. 1 I SPARE FUSES Unpack and inspect the EPSA and the enclosed hardware. The fol- lowing hardware, which is required to mount and connect the EPSA to the system, is supplied with each EPSA. ANCHOR TOGGLE? FLANGE I TOG&ER NECK LEGS 2 T.C. Toggler Wall Fasteners (Figure 2). 2 #I4 Hex Head Sheet Metal Screws. 1 Toggler Key. 1 Template P/N 117260-001 (to space the wall fasteners properly). 1 AC Fuse (spare) P/N amp, 1. DC Fuse (spare) PIN 116438-030 (F2, 10 amp, Fast-BLO, 32 VDC). 1 16 AWG, 3 wire Jacketed Cable (54 inches). Choose a suitable location on a vertical surface for the EPSA, and attach the P/N 117260-001 template to that location temporarily. Use a spirit level to verify that the indicated drilling points are level. Place punch marks on the mounting surf ace through the 1r+cr marked drilling positions on the template. Enlarge the two punch marks an l/&inch drill bit. With a 5/16-inch bit, drill surface to les. Press the anchoring legs of a r together and insert them into one of the anchoring holes, as shown in Figure 3. Insert the toggler into the hole until the neck flange is flush with the mounting surface. If it is difficult to insert it completely by hand, tap it lightly with a hammer.
Insert a toggler key into the small hole in the neck of the fastener, as shown in Figure This should cause the anchoring legs to !fpop’l open. Even if the mounting surface is too thick to permit the legs to open fully, adequate support for the EPSA should be provided when the screws are in place. Remove the toggler key. second hole. Thread the #14 hex head sheet metal screws into the small holes in the center of the togglers. Leave approximately 3/16-inch clearance be- tween the bottom of each screw head and the mounting surface (Figure 5). Align the EPSA mounting bracket’s holes with the sheet metal screws as shown in Figure 6. Place the EPSA against the mounting surface with the screws protruding through the holes. Lower the EPSA so that the narrower portions of the holes slip over the screws and the weight of the EPSA is supported. Tighten the screws. Remove the spare fuses from the hardware carton.
,’ Place the spare 10 amp DC fuse in the center fuse storage clip located on the side panel of the EPSA (Figure 6). Place the spare 5 amp SLO- BLO AC fuse in the clip below the DC fuse clip. Remove and inspect the fuses that were shipped inside the EPSA. If the visual inspection reveals a de- fective fuse, remove the appropriate spare from its storage clip and replace the defective fuse. (Order anot her spare fuse.) The Power Battery Back-up Assembly (PBBU) in Figure 7 is an optional PCB which may be installed in the EPSA 104 to interface with two auxiliary 12V batteries. In the event of an electrical power failure, the PBBU provides an automatic battery power source, permitting a typical STRATA VI system to continue normal operations for up to 12 hours. BATTERY BATTERY PROTECTION FUSE Hi)LDEf i TAN PIN The PBBU contains a voltage sensing circuit which causes an elec- tromechanical relay to connect the back-up battery power supply to the system before the EPSA output voltage drops below 21VDC (at which point system functions would be disrupted and existing calls would be disconnected). When the normal source of electrical power is restored, the volt- age sensing circuit relay will disconnect the standby battery power source. If the standby battery power source output falls below 21VDC while it is connected to the system, the voltage sensing circuit will cause the relay to disconnect the standby battery from the system. The standby battery’ power supply will not reconnect unless: The normal source of electrical power is restored, causing the PBBU to disconnect the battery power supply from the system, or... The “Battery Override” switch ures 7 and 8) is placed in the position, or... The depleted batteries are re- placed by a freshly charged pair and the “Battery Override” switch is turned on and then released. The PBBU also contains cir- cuitry to provide the charge current necessary to maintain the batteries at a satisfactory level of charge while the STRATA VI system is in normal oper- ation. An external fast charger may also be connected across the battery output terminal connections. The PBBU kit contains the following items:
TERMINAL ST RIP C FUSE PBBU-Power battery backup PCB. Fuse-A spare battery protection fuse. Cable Clamp-A 7/l 6-in e cable clamp which may be needed to secure the wiring harness inside the EPSA. “PBBU-REV 3”--An adhesive-backed decal to be placed on the front face of the EPSA. Warning Tag-A warning tag to be attached to the EPSA 115VAC power cord. In addition to those items supplied in the PBBIJ kit, the following additional items are needed to install a PBBU in an EPSA: Two Batteries-Two 12V/80 amp- hour, lead-acid, automotive-type, maintenance-free batteries are re- commended. he procedures in Paragraph assume batteries with side-mounted terminals are used. Battery Rack and Separator-A battery rack and separator should be used to secure the batteries to prevent tipping and spilling of bat- tery acid or accidental shorting of the battery terminals. Two-Wire Connecting Cable-A 2- wire connecting cable terminating at one end with 3/8-in, ring ter- minals and at the other end with l/8-in. hooked spade terminals is required to provide the connection
between the batteries and the EPSA. The minimum wire size must be determined by the loop length of the connecting cable as indicated in Table A. 12 ft. 16 gauge 20 ft. 14 gauge 30 ft. 12 gauge 50 ft. 10 gauge Single Wire Cable--A 16 AWG sin- gle wire cable, approximately 1% inches in length and equipped with ring terminals, is required to con- nect the two batteries in series. Cable Clamp-A cable clamp should be used to relieve strain on the battery cable to prevent cable movement from affecting the bat- teries. Battery Fuse-A 10 amp, 32V (min- imum) fuse, or a 10 amp DC in- stantaneous tripping circuit breaker is to be located adjacent to the batteries in series with the nega- tive lead of the 2-wire connecting cable. The battery fuse (or cir- cuit breaker) is required to protect the batteries from damage due to a power surge or a short circuit.. Hex Head Bolts-Four 3/8in. hex head bolts are required to connect the cable terminals to the batteries. Washers-Eight 3/8-in. flat washers and four 3/8-in. internal-tooth lock washers are required for the above cable terminal connections. Battery Cabinet-If the batteries are not located in a well-venti- lated closet or other secure area, protected from fire or sparks, a properly ventilated protective eabi- net is required to safeguard them. Verify that the power switch on the MTOU is in the position, and then disconnect the EPSA’s 115 VAC power cord.
Remove the terminal stri m the 9 termin * 2. The EPSA cover is secured by seven screws. Viewing the EPSA as if it is wall-mounted, two screws will be located at the rear edge of the top of it, three on the side facing outward and two on the rear edge of the bottom. 5 Remove all seven screws. Remove the cover and set it aside. Locate and trace the multi- wire harness in the lower portion of the EPSB (the area away from the built-in mounting bracket). The harness originates from the transformer and the terminals and fuse holders mounted in the control panel, This harness ter- minates in a rust-colored square eon- nectar. The harness is secured to the bottom of the chassis with a cable clamp as shown in Figure 10, Loosen the screw and nut slightly to allow movement of the harness, NICKEL-PLATED HOLE PLUGS Mounted in the EPSA control are two nickel-plated hole plugs. Bend in the retaining tabs on both plugs; remove and discard them. Un-ivrap the PBBU and locate the screw in the PBBU’s mounting bracket (Figure 11). Remove and save the screw. BATTERY OVERRIDE BUTTON I SCREW CONNECTOR Slip the PBBU’s battery pro- tection fuse holder and the battery override button through their respective ports in the control panel (Figure 11). The PBBU’s mounting bracket should be
flush against the rear of the control panel with the fuse holder and override button protruding through it. The harness should flow around the PBBU PCB, with no wires beneath it. Align the two tan-colored PBBU pins with the two holes in the heat sink (Figure 10). Press the pins into the holes until they catch and hold the PBBU PCB. Use the previously removed screw and secure the PBBU mounting bracket to the control panel. See Figure 11. Plug the rust-colored eon- nectar into the nine-hole jack center of the PBBU PCB. force the connector’s prongs into the jack, they are keyed so that they can be mated in only one position. Replace the EPSA cover and secure it with the seven screws originally removed. Press in the battery over- button (Figure 8). If it catches and stays in, press it again to cause it to release and protrude out of the control panel. Out is off, and the position of the button must be in for the EPSA to operate normally. Remove the spare fuse from the PBBU kit. If the original fuse is missing or defective, replace it with the spare. If not, put the spare fuse in the holder located on the side of the EPSA away from the control panel. Remove the warning tag from the kit and tie it to the power cord where it emerges from the EPSA. A l’PBBU-REV 3” decal must be placed on the control panel of the EPSA. Remove the decal from the kit, peel the backing off, and place it on the control panel (Figure 8). Select a location for the batteries near the EPSA. The loop length of the cable connecting them to the EPSA will determine the minimum gauge wire which can be used in the cable. See Table A. Secure the batteries in the battery rack and separator, which should be located in a minimum access area, such as a closet or a well ventilated cabinet. Verify that battery over- utton is in the position (out). Loosen the two screws on the terminal strip identified as 24V/BAT- TERY. Attach the cable’s two spade tips to these connectors. Each wire,
as well as the EPSA terminals, are marked positive (+) or negative (-). See Figure 12. Natch positive to positive and negative to negative. Connect the battery fuse (or circuit breaker) lead to the negative terminal on one battery (Figure 13). CABLE MARKER WASHER/ / HEX HEAD BOLT/ Attach the negative wire from the connecting cable to the r battery. fuse (or circuit breaker). Connect the positive wire to e positive pole of the battery to which the fuse connected (see Figure 12). Connect one end of the sin- gle-wire cable to the positive terminal on the battery with the fuse. Connect the other end to the negative terminal on the battery without the fuse (Figure 12). Plug the AC power cord in, and verify that the indicator is lit. lit to indicate the batteries are supplying electrical power as needed. Replace the terminal strip cover and test the STRATA VI system functions under both AC and battery back-up power.
TABLE OF CONTENTS e - a a e a 0 e 0. e . $0 a a e e e e . e . . a. e a. e a INTKODUCTION s . e . . . . e o s o e. a a e a a e e o 0. ~~0*~*.~*~~.* PROGRAitiMING PROCEDUKES o . q e a e. a e a -. . a *. II a -. *. q n. a a GENERAL . . q a . + a s . . e o . . e e s s o e e a a 0. a PREPARATION e a a 0 a. a.. . . . . . . . . . . . . . . . . . . . . . . . . SYSTEM OPTIONS e a + a s a n o . s e . . e **.*.1o*e.*..am*** CO LINE OPTIONS . Q a a e a e . . .e a.. .*,***...eaanaa* STATION OPTIONS . . . o s a +. e . . e a e . o q a e e . . . 0.. e 0. e SYSTEM KECORD SHEETS q . s . e e e o e . . o . . o a e . a o n a TABLE l--SYSTEM, STATION & CO LINE CP’I’IONS . * e . a TABLE 2-TOLL RESTRICTION CLASSIFIC4TION . . a 0 0 a INITIALIZATION e . e . a e e . o . a e . . e . a a a a**~~.*~~o.~* SYSTEM DATA ENTRY e e s . a 0 . a . s e a e e e . 0.. e a.. . . . e . TABLE LIST TABLE 3-INI~I&&d DATA *eD.o.aa*e’.‘,* : : : : : : : : : : : : : TABLE d--SYSTEM ASSIGNMENTS-BASIC TABLE 5-SYSTEM ASSIGNMENTS-OPTIONS’ ‘* ’ 1 1 1 1 1 : 1 1 1 1 TABLE &--AUTO RECALL PROM HOLD TIMING TABLE 7--AUTO RELEASE ON HOLD ASSIGNMENT* : ‘.‘: : : : TABLE 8--AUTO RELEASE ON HOLD TIMING ~ ~ ~ e e a. s a. TABLE 9-PBX BACK-UP a o . . e . e e . . a a *. .**s..v.* TABLE lo-PBX ACCESS CODES TABLE ll-TOLL RESTRICTION DISABLE’ : : : . o.ee**e*. *. 0*ee.a.m TABLE 12-TOLL RESTRICTION EXCEPTION CODES , e . . e TABLE 13-STATION CO LINE ACCESS TABLE 14-STATION CLASS 3F SERVICE ‘a*e’ ’ : : : : : : : : : : TABLE 15-TOLL RESTRICTION CLASS . a . : m . TABLE 16-STATION OUTGOING RESTRICTION ~ : : : : : : : : : TABLE 17-CO RINGING ASSIGNMENTS-DAY TABLE 18-C(3 RINGING ASSIGN;VIENTS-NITE ~*a’:e* : : : : : : :