READ AND SAVE THESE INSTRUCTIOINS. Please readthese instructionscarefullybeforeattempting toinstall, operate or service the Panasonic Ventilating Fan. Failure to comply with instructions could result in personal injury and/or property damage. Please retain this booklet for future reference. Applicable to Models: FV-05VF2, FV-08VF2, FV-11VF2 (For Contractor Pack) Housing Can FV-05-11VFA2 Motor/Grille Assembly FV-05VFB2 Table of Contents 2Unpacking 2General Safety Information IInstallation( Joist Mounting- )I 6-7 4-5IIInstallation 3Supplied Accessories 3Wiring diagram ( Joist Mounting- )II IIIInstallation( -Joist Mounting )I7 IVInstallation( Between Joist Mounting )8-9 VInstallation( Wooden Header )9 VIInstallation( In Existing Construction )10 Product Service10 FV-08VFB2, FV-11VFB2
UNPACKING Unpack and carefully remove unit from carton. Refer to the following Supplied Accessories list to verify that all parts are present. GENERAL SAFETY INFORMATION 1. Do not install this ventilating fan where air temperature may exceed 40 C (104 F).oo 2. Make sure that the electric service supply voltage is 120 V, 60 Hz. 3. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC) and the Occupation Safety and Health Act (OSHA). 4. Always disconnect the power source before working on or near the fan, motor or junction box. 5. Protect the power cord from sharp edges, oil, grease, hot surfaces, chemicals or other objects. 6. Do not kink the power cord. 7. Do not install the unit where ducts are configured as shown in Fig. A. 8. Provide suction parts with proper ventilation. 9. This unit is UL listed for use over a bathtub or shower when installed in a GFCI protected branch circuit. CAUTION: 1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors. 2. Not for use in cooking area. (Fig .B) 3. This product must be properly grounded.Floor Do not install above or(Cooking area) inside this area 45o45o equipmentCooking Fig. B 2 WARNING: To reduce the risk of fire, electric shock or injury to persons, observe the following: A. Use this unit only in the manner intended by the manufacturer. If you have any questions, please contact to the manufacturer. B. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction. C. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturers guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating Refrigeration and Air Conditioning Engineers (ASHRAE) and the local code authorities. D. The Housing Can FV-05-11VFA2 must be installed with Motor/Grille Assembly FV-05/08/11VFB2 only. F. Ducted fans must always be vented to the outdoors. G. These models are UL listed for tub and shower enclosures. I. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel. J. NEVER place a switch where it can be reached from a tub or shower. E. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities. Fig. A ProhibitionAdaptorProhibitionProhibitionProhibition K. Not to be installed in a ceiling thermally insulated to a value greater than R40. (This is required for installation in Canada only.) H. Solid state controls may cause harmonic distortion which can cause motor humming noise. To reduce the risk of fire or electric shock, do not use this unit with any solid-state control device.
SUPPLIED ACCESSORIES SETS(4 )SUPPLIED ACCESSORIES SETS(4 ) (A) For Motor / Grille Assembly of model: FV-05/08/11VFB2 Quantity Appearance Part name Grille4 (B) For Housing Can of model: FV-05-11VFA2 WIRING DIAGRAM 4 24 4 4 8 4 8 4 Thumb screwLong screw (ST4.2X20) Suspension bracketI Suspension bracketII Screw (ST4.2X8)I Suspension bracketIII Screw (ST4.2X10)II 3 inches adaptor connector (optional part) Quantity Appearance Part name 3 OFFPower Supply AC120V 60Hz Fan body Red Capacitor WhiteJunction box Neutral Earth ground White White Black Green GreenLiveBlack GreenEarth ground Black Switch (not included) ON Earth ground
4 INSTALLATION JOIST MOUNTING-II()INSTALLATION JOIST MOUNTING-II() 1. Before installation, Secure the fan body to adaptor by using thumb screw. (Fig. 1) Fig. 1 2. Insert the suspension bracket into the fan body and adaptor. (select the suspension bracket acc rding to Fig. 2)o Tape IMPORTANT: Adaptor Remove the tape from damper and adaptor before installation.As shown below: Damper 2 Screw (ST4.2X8)I Suspension bracketIIISuspension bracketII If spacing A on center joists is 24 inches, connect suspension bracket and (C4 mark to C4 mark) as shown below :II III 3 inches adaptor connector Connection method for 3 inches adaptor connector Duct tape Fan body Thumb screw Suspension bracketIII Suspension bracketI Fig. 2-3 A = 19.2 inches vertical joists Fan body Suspension bracketI Fig. 2-1Fan body A = 12 inches Suspension bracketISuspension bracketIII Fig. 2-2 A = 16 inches Fan body Fig. 2-4Fan body Suspension bracketI Suspension bracketIII Suspension bracketII A = 24 inches 12 3 Joists A
INSTALLATION JOIST MOUNTING-II( ) CONTINUEDINSTALLATION JOIST MOUNTING-II( ) CONTINUED 5. Remove junction box cover and secure conduit or stress relief to junction box knock-out hole. (Fig. 5) 6. Refer to wiring diagram (page 3). Using wire nuts, connect house power wires to ventilating fan wires: black to black; white to white; green to green; Replace the junction box cover. (Fig. 5) CAUTION:Mount junction box cover carefully so that lead wires are not pinched. 4. Install the suspension bracket to joists by using long screws (ST4.2X20) and secure it to the fan body by using screw (ST4.2X10) (Fig. 4)II 3. Install the suspension bracket and the flange of fan body to joists by using long screws (ST4.2X20) according to Fig. 3. 7. Install a duct and secure it with duct tape or clamps. Junction box coverConduit Wire nut Conduit Junction box Green wires Lead wires Duct Duct tape Fig. 5 5 2 Long screws (ST4.2X20)Screw (ST4.2X10)II 8. Finish ceiling work. Ceiling hole should be aligned with the edge of the flange. (Fig. 6) Fig. 6 Ceiling 10 7/8(275)10 7/8(275) inches (mm) Fan bodyJoist 4 Long screws (ST4.2X20) OthersFig. 3-1 Fan body2 Long screws (ST4.2X20) A = 10 1/4~12 inches 9. Follow the Fig. 12-3, 12-4 (page 9) and Fig. 7 (page 8) of the original installation instruction to complete the motor/grille assembly installation. Fig. 3-2 Joist Fig. 4 Joist Joist
6 INSTALLATION JOIST MOUNTING-II II()INSTALLATION JOIST MOUNTING-II II() 1. Remove adaptor from fan body before starting installation. 2. Insert the suspension bracket into the adaptor and secure it to joists by using long screws (ST4.2X20) (Fig. 7) Keep the distance B (7/8 inch, 21.6mm) for the thickness of ceiling board. 3. Follow step 5 to 7 of the Installation (page 5) to complete the duct work and wiring.I If spacing A between joists is 21 1/4 to 23 1/2 inches, connect suspension bracket and (C4 mark to C4 mark) according to page 4 Select the suspension bracket according to spacing A as shown below.II III suspension bracketsuspension bracketIsuspension bracketIIIsuspension bracket &II III Spacing A between Joists inches (mm)13 1/4~15 1/2 ( 336~394 )16 1/2~18 3/4 ( 419~480 )21 1/4~23 1/2 ( 540~597 ) 4. Insert to fan body (refering to step 2 of Installation , page 4)the suspension bracket in I Make sure that adaptor claws are properly inserted into fan body slots.IMPORTANT: 5. Insert the fan body into joists. (Fig. 8) 2 Long screws (ST4.2X20) B A 7/8 (21.6) 13 1/4~15 1/2 ( 336~394 ) 16 1/2~18 3/4 ( 419~480 ) 21 1/4~23 1/2 ( 540~597 ) Adaptor Slots Adaptor clawsFan body Joist Conduit Junction box cover Duct Duct tape 2 Long screws (ST4.2X20) Adaptor Fig. 7 Fig. 8 Joists inches mm()
Fig. 9 INSTALLATION JOIST MOUNTING-II II( ) CONTINUEDINSTALLATION JOIST MOUNTING-II II( ) CONTINUED 6. Secure the fan body to adaptor by using thumb screw (Fig. 9) 7. Secure to joists by using long screws (ST4.2X20) and secure it to fan body by using screw (ST4.2X10) in vertical direction (Fig. 9)the suspension bracket II 8. Follow step 8~9 of Installation (page 5) to complete the installation work.I INSTALLATION JOIST MOUNTINGIII I-()INSTALLATION JOIST MOUNTINGIII I-() C1 C2 C3 C44 kinds of -joist inches (mm)I 9/16 ( )14.3 11/16 (17.5) 31/32 (24.6) 1 17/32 38.9() Suspension bracket The suspension can comply with different kinds of -joist.III III I bracket 1. Before installation, secure the fan body to adaptor by using thumb screw. (Fig. 1 of page 4) 2. Connect the suspension to fan body. (Fig. 10) (select the hole by checking joist size fix the screw to the frame hole.)bracketIII I- 3. Connect the fan body to the joist. (Fig. 11)I- 4. Follow step 5 to 9 of installation (page 5) to complete the installation work.I C C3 C4 C1 C2 2 Long screws (ST4.2X20) Screw (ST4.2X10)II Receptacle Thumb screw Screw (ST4.2X10)II Suspension bracketIII 4 Long screws (ST4.2X20) Ijoist Fig. 10 Fig. 11 7
A13 1/4~15 3/4 ( 336~400 ) 16 1/2~18 3/4 ( 419~480 ) B7/8 (21.6) 3~5 ( 76~126 ) 5 4/5~7 4/5 ( 148~198 ) Fig.12-1 Fig.12-2 A Fig. 13 INSTALLATION BETWEEN JOIST MOUNTINGIV()INSTALLATION BETWEEN JOIST MOUNTINGIV() 2. Insert the suspension bracket into the bracket cover of adaptor side and the back of the fan body. (Fig.12) (select the suspension bracket according to spacing A as shown below) 1. Before installation, secure the fan body to adaptor by using thumb screw. (Fig.1 of page 4) 8 3. Insert the fan body between joists. Make sure the fan body is level and square (perpendicular)with the joists.(Fig. 13) Keep the distance B (7/8 inch, 21.6mm) for the thickness of ceiling board. 16 inches and 19.2 inches horizontal joist and 19.2 inches vertical joist A = 16 inches and 19.2 inches horizontal joist Suspension bracketI Suspension bracketIIISuspension bracketII A = 19.2 inches vertical joist Suspension bracketIII Suspension bracketIISuspension bracketI inches mm() Junction box Fan bodyJoists Adaptor
9 Fig. 16 Fig. 14 Fig. 15 Fig. 17 INSTALLATION WOODEN HEADEV(R)INSTALLATION WOODEN HEADEV(R) INSTALLATION BETWEEN JOIST MOUNTINGIV( ) CONTINUEDINSTALLATION BETWEEN JOIST MOUNTINGIV( ) CONTINUED 2 Long screws (ST4.2X20) Joist 4 Long screws (ST4.2X20) 2 Screw (ST4.2X10)II (275)(375)10 7/814 3/4 Adaptor inches (mm)Fan bodyJoist Header Joist 2. Install header between joists by using nails or screws. 1. Before installation, secure the fan body to adaptor by using thumb screw. (Fig. 1 of page 4) 4. Secure the suspension bracket to joists by using long screws (ST4.2X20) (Fig. 14, Fig. 15) 5. Secure the suspension bracket to fan body by using screw (ST4.2X10) (Fig. 15)II 6. Follow step 5 to 9 of installation (page 5) to complete the installation work.I 3. Install the fan body and secure it by using long screws (ST4.2X20) (Fig. 16 of page 8, Fig. 17) 4. Follow step 5 to 9 of installation (page 5) to complete the installation work.I Duct 6 Long screws (ST4.2X20) Junction box Lead wires Green wiresWire nut Conduit Adaptor
10 (1) To install the ventilating fan, follow the procedures described in lnstallation . Take the following precautions before installation.II 1. Installation in existing construction. Installing the ventilating fan in an existing building requires an accessible area (attic or crawl space) above the planning installation location or existing ducting and wiring. CAUTION: Check area above planning installation location to be sure that: 1. Duct work can be installed and that area is sufficient for proper ventilation. 2. Wiring can be run to planning location. 3. No wiring or other obstructions shall interfere with installation. INSTALLATION IN EXISTING CONST UCTIONVI(R)INSTALLATION IN EXISTING CONST UCTIONVI(R) (2) Inspect duct work and wiring before proceeding with installation. (3) Plan suitable location for ventilating fan. (next to ceiling joist) (5) First, remove ceiling section according to Fig. 6 of page 5. (6) Install ventilating fan. (4) Before installation, provide inspection and maintenance access at a location that will not interfere with installation work shown in installation .II (1) Inspect duct work and wiring before proceeding with installation. (2) Remove ceiling section according to Fig. 6 of page 5. (3) Install ventilating fan. 2. Installation from accessible area above fan location. Warning Concerning Removal of Covers. The unit should be serviced by qualified technicians only. No service information is provided for customers. Your product is designed and manufactured to ensure a minimum of maintenance. However, should your unit ever require service, a nationwide system of factory service centers and AUTHORIZED INDEPENDENT SERVICE CENTERS is maintained to support your products warranty. (In the U.S.A.,call 1-866-292-7292 to Customer call center.) P ODUCT SE VICERRP ODUCT SE VICERR