Home > Panasonic > Air Conditioner > Panasonic MVA Series Air Handling Unit Mva18 24 30 36 42 48 60 Fbas6hbcp Installation Operation And Maintenance Manual

Panasonic MVA Series Air Handling Unit Mva18 24 30 36 42 48 60 Fbas6hbcp Installation Operation And Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic MVA Series Air Handling Unit Mva18 24 30 36 42 48 60 Fbas6hbcp Installation Operation And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							035-000039-001 Page 11 of 32 MVA IOM 1.3 9-10-2014
    INSTALLATION—SERVICE CLEARANCES 
    						
    							035-000039-001 Page 12 of 32 MVA IOM 1.3 9-10-2014
    Install the unit so that it is level or pitches
    slightly –(1/8 inch) – toward the condensate
    drain connection.
    Anchor the unit to the plenum or platform
    through the bottom flange using 2ea #10 sheet
    metal screws on each side (4 screws total).
    Ceiling Suspension: Mount the unit in ceiling-
    suspended horizontal orientation per suspen-
    sion details (Figure 4). Unit is NOT intended
    to be wall mounted. Consult a qualified struc-
    tural engineer for special mounting considera-
    tions.
    Install the unit so that it pitches slightly –(1/8
    inch) – toward the condensate drain connec-
    tion.
    Condensate Drain
    Install a trapped condensate drain line at unit drain
    connection. All MVA units have 3/4 in. FPT con-
    densate main and auxiliary drain connections.
    Provide adequate trap clearance (trap depth) be-
    neath the unit as indicated in Fig. 3. Provide
    freeze-up protection as required to insure reliable
    condensate drainage. Freeze protection
    measures are customer-supplied and installed.
    Pipe to condensate drain using PVC or copper or
    other suitable material. Pitch drain piping down-
    ward at a minimum slope of 1/8 inch per foot.
    Pipe auxiliary drain to “tell tale” drain location or
    floor drain to clearly indicate when condensate
    drain service is required. Alternately, use a field-
    provided condensate overflow detection device in
    the auxiliary drain connection to provide alarm or
    other controls action when the drain pan fills to the
    level of the auxiliary drain.
    Placing Unit In Ductwork
    1. Utilize flexible transitions on supply and return
    connections to reduce noise and vibration trans-
    mission to the structure.
    INSTALLATION
    WARNING
    INSURE THAT THE UNIT IS ADE-
    QUATELY SUPPORTED FROM
    STRUCTURE TO PREVENT DAMAGE
    OR INJURY CAUSED BY FALLING
    EQUIPMENT! If uncertain about how
    to connect to the structure, consult a
    qualified structural engineer.
    Fig. 3 — Condensate Drain
    2. W hen the connecting return air duct is
    smaller than the coil inlet opening, construct
    the transition piece so that the vertical and
    horizontal dimensions of the transition piece
    do not increase more then one inch for eve-
    ry seven inches of length of the transition
    piece.
    2. Provide at least three feet of straight
    duct work preceding the unit inlet.
    Duct Insulation and Vapor Proofing:
    Properly select and install duct insulation as
    required by the application.
    All externally insulated duct work must have
    an adequate vapor seal for summer opera-
    tion. This is particularly important where the
    duct is exposed to highly humid conditions
    in such places as attics, vented crawl spac-
    es, unconditioned basements, and utility
    rooms. The vapor seal prevents condensa-
    tion of moisture in the insulating material
    and subsequent loss of its insulating value.
    NOT TO SCALE
    MAINTAIN THESE DIMENSIONS FOR ADEQUATE TRAPSEAL:A = 3.5” MINIMUMB = 2.0” MINIMUM
    NOTES:1. CONDENSATE DRAIN PIPING RECOMMENDATIONS:A. MINIMUM 3/4” Φ PIPE SIZE B. COPPER OR PVC PIPE MATERIALC. USE DIELECTRIC UNION FOR DISSIMILAR METALS.D. INSULATE PER PROJECT SPECIFICATIONS.2. PAD OR PLENUM HEIGHT AS REQUIRED TO INSTALLTRAP AND CONDENSATE DRAIN PIPING.3. AVOID BLOCKING FILTER SERVICE ACCESS W HENINSTALLING CONDENSATE DRAIN PIPING. 
    						
    							035-000039-001 Page 13 of 32 MVA IOM 1.3 9-10-2014
    Figure 4
    CEILING SUSPENSION DETAILS 
    						
    							035-000039-001 Page 14 of 32 MVA IOM 1.3 9-10-2014
    INSTALLATION
    CAUTION
    Direct-expansion coils are shipped pressurized
    with dry nitrogen. Release pressure from the coil
    through valves in protective caps before remov-
    ing caps.
    Do not leave piping open to the atmosphere un-
    necessarily. Water and water vapor are detri-
    mental to the refrigerant system. Until the piping
    is complete, recap the system and charge with
    nitrogen at the end of each workday. Clean all
    piping connections before soldering joints.
    Failure to follow these procedures could result in
    personal injury or equipment damage.
    Refrigerant Piping
    Refrigerant Coils: Direct-expansion coils
    have liquid and suction line connections
    through the front of the cabinet.CAUTION:
    Use proper care when brazing including use
    of heat sink (wet cloth or other method) to pre-
    vent damage to liquid line and suction line
    components.
    Size and install refrigerant lines in accordance
    with the condensing unit manufacturer’s in-
    structions. Provide insulation on the suction
    line, to prevent condensation. Provide insula-
    tion on the liquid line if unit to be used for heat
    pump service or if otherwise required.
    Electric Heater Accessory
    The electric heater may be factory-installed or
    field-installed. See Figures 5 through 8.
    Removal Procedure:
    To remove the electric heater,
    1. Disconnect and lock out electrical power
    from the unit. Remove heater access panel.
    Disconnect power wires from the power
    switch—DANGER! - MAKE SURE there is no
    voltage on these wires before disconnecting!
    2. Disconnect 2 harness connectors at the
    blower deck.
    3. Remove 2 screws holding heater support
    feet to the blower deck.
    4. Remove 4 screws that mount the heater to
    the heater bulkhead. Handle heater carefully
    to avoid damaging the wire heating elements.
    Remove heater from the unit.
    DANGER
    WARNING:Hazardous voltage.Only qualified
    personnel must install the electrical service. Dis-
    connect and Lock Out all incoming power sources
    before connecting to electrical service.
    WARNING:This appliance must be permanently
    grounded in accordance with the National Electrical
    Code and local code requirements.
    WARNING: For use with copper conductors only.
    Fig. 5 — Heater Accessory Installed
    (right side panel not shown)
    Fig. 6 — Heater Accessory Installed
    (right side and heater access panels
    not shown)
    System Design Regulation
    When connecting MVA units in the VRF sys-
    tem (mix or all),keep indoor/outdoor unit
    capacity ratio with the range of 50% to
    130%.For other conditions, refer to the VRF
    System standard piping design regulations. 
    						
    							035-000039-001 Page 15 of 32 MVA IOM 1.3 9-10-2014
    INSTALLATIONDANGER
    WARNING:Hazardous voltage.Only qualified
    personnel must install the electrical service. Dis-
    connect and Lock Out all incoming power sources
    before connecting to electrical service.
    Install Procedure:
    To install the electric heater,
    1. Disconnect and lock out electrical power from
    the unit. Remove heater access panel. Discon-
    nect field power wires from the unit power wires.
    DANGER! - MAKE SURE there is no voltage
    supply to the unit before proceeding!
    2. Disconnect and discard 1 harness connector at
    the blower deck.
    3. Remove blank plate from heater access panel
    (covers square hole for breaker style power
    switches).
    4. Remove SAT sensor and sensor holder from
    heater bulkhead and reposition on unit discharge
    ductwork routing through auxiliary SAT sensor
    hole on top panel.
    5. Install SAT 3 feet after the first 90 degree turn
    in the discharge ductwork.
    6. Remove plate on the heater bulkhead (4
    screws).
    7. Install heater by carefully supporting the heater
    and inserting it into the opening in the heater bulk-
    head. NOTE: Make sure to guide the pin into the
    hole at the back of the heater shroud. Secure the
    heater to the bulkhead with 4 screws.
    8. Connect 2 wiring harnesses (male) to the
    Fig. 7 — Heater Accessory Removal
    (right side and heater access panels
    not shown for clarity)
    matching female receptacles in the blower deck.
    9. Connect field wiring to the breaker-style power
    switches on the front of the heater.WARNING! Be
    sure to provide the appropriate wire size and
    branch circuit protection as required by the unit
    nameplate!
    10. Install the heater access panel.
    11. Install the silicone cover “boot” over the top of
    the power switches. This protects them from dust
    buildup. The switches may be activated through the
    flexible boot material.
    12. Mark the nameplate label with the matching
    heater kW rating. Label is located on the exterior of
    the front top panel.
    13. Update EEPROM settings to values shown in
    the table. Refer to test run manual for detailed in-
    Fig. 8 — Heater
    Accessory
    Installed
    PIN
    HEATERSHROUD
    HEATERACCESSPANELCOVERBOOT
    HEATERSHROUD
    RIGHTSIDE
    HEATERASSEMBLY
    HEATERBULKHEAD
    POWERSWITCH(ES)
    Item Code New Settings
    07 0001
    38 0002
    3C -001 
    						
    							035-000039-001 Page 16 of 32 MVA IOM 1.3 9-10-2014
    Typical wiring diagrams are shown on the following
    pages FOR REFERENCE. Always refer to the wir-
    ing diagram on the air handling unit for actual wir-
    ing.
    NOTE: CHECK MOTOR RATING PLATE FOR
    CORRECT LINE VOLTAGE.
    Connect electrical service to unit. Refer to unit wir-
    ing diagram.
    Power Wiring
    For power supply connection, route field power wir-
    ing L1 and L2 and connect either:
    1. Unit W ithout EH: to field-provided and installed
    disconnect switch and from switch to power
    entry (unit side) and to unit power leads inside
    the unit electrical section; or
    2. Unit W ith EH: into the unit through power entry
    (unit side) and then to the factory installed pow-
    er switch inside the electrical section (see Fig-
    ure 9). Note: power switch looks like a circuit
    breaker butdoes not provide overload pro-
    tection. Power switch provided only with elec-
    tric heater (field kit or factory installed). NOTE:
    When electric heat greater than 10kW is pro-
    vided, two power supply circuits are required,
    as shown on the wiring diagram.
    Refer to nameplate or Electrical Ratings (page 30)
    for FLA, maximum overcurrent protection device
    (MOPD) and minimum circuit ampacity (MCA). Also
    refer to wiring diagram affixed to unit to make con-
    trol and power wiring connections. For new heater
    installation, mark the nameplate label with the
    matching heater kW rating. Label is located on the
    exterior of the front top panel.
    NOTE: Installer is responsible for power wiring and
    branch circuit over current protection.
    Control Voltage Wiring
    Control voltage wiring may enter the unit at the con-
    trol box located behind the blower access door, or
    DANGER
    NEVER enter an enclosed fan cabinet or reach into
    a unit while the fan is running.
    LOCK OPEN AND TAG the fan motor power dis-
    connect switch before working on a fan. Take fuses
    with you and note removal on tag. Electric shock
    can cause personal injury or death.
    LOCK OPEN AND TAG the electric heat coil power
    disconnect switch before working on or near heat-
    ers.
    Failure to follow these warnings could lead to per-
    sonal injury or death.
    DANGER
    WARNING:Hazardous voltage.Only qualified
    personnel must install the electrical service. Dis-
    connect and Lock Out all incoming power sources
    before connecting to electrical service.
    WARNING:This appliance must be permanently
    grounded in accordance with the National Electrical
    Code and local code requirements.
    WARNING: For use with copper conductors only.
    INSTALLATION-ELECTRICAL
    Figure 9
    Unit with Electric Heat
    CAUTION
    Use only copper conductors for field-installed elec-
    trical wiring. Unit terminals are not designed to
    accept other types of conductors.
    Do not allow wiring to touch the refrigerant tubing,
    compressor, or any moving parts of the fan.
    Make wiring connections in accordance with the
    system wiring system diagram and these instruc-
    tions. Wrong wiring may cause improper operation
    or unit damage!
    Unauthorized changes in the internal wiring can be
    very dangerous. The manufacturer will accept no
    responsibility for any damage or malfunction that
    occurs as a result of such unauthorized changes.
    other convenient location. Control voltage wiring
    leads exit the bottom of the control box and are
    ready for field-connection.
    CAUTION!To prevent malfunction of the air condi-
    tioner caused by electrical noise, route control wiring
    and inter-unit control wiring SEPARATELY FROM
    THE POWER WIRING!
    POWERSWITCH 
    						
    							035-000039-001 Page 17 of 32 MVA IOM 1.3 9-10-2014
    DANGER
    WARNING:Hazardous voltage.Only qualified
    personnel must install the electrical service. Dis-
    connect and Lock Out all incoming power sources
    before connecting to electrical service.
    WARNING:This appliance must be permanently
    grounded in accordance with the National Electrical
    Code and local code requirements.
    WARNING: For use with copper conductors only.
    INSTALLATION-ELECTRICAL
    General
    Provide strain relief where field wiring passes
    through cabinet. Wiring within the cabinet has
    been positively located and supported so that it
    does not pass over sharp metal edges or come in
    contact with moving parts. After servicing, position
    wiring properly in the original supports.
    All field-installed wiring, including the electrical
    ground, MUST comply with the National Electrical
    Code (NEC) as well as applicable local codes. In
    addition, all field wiring must conform to the Class
    II temperature limitations described in the NEC.
    Refer to factory wiring diagrams installed in the
    unit. Use the MCA and MOPD from the nameplate
    or electric heat nameplate or Electrical Ratings
    (page 30) to size power supply wiring and overcur-
    rent protection device. Installation must comply
    with NEC and local codes.
    For communicating controls, refer to Figures 10
    through 13 for max lengths, sizing and intercon-
    nections. Refer to the condensing unit opera-
    tion manual for more details.
    Figure 10
    Building System Wiring Diagram
    (multiple indoor & outdoor units)
    ( A ) In t e r- u n it ( b e t we e no u t d o o r a n d in d o o r u n it s )c o n t ro l wirin g
    ( B ) R e mo t e c o n t ro l wirin g
    AWG #18 (0.7 5 mm2) AWG #18 (0 .7 5 mm2)
    Ma x. 3 ,2 80 ft. Max. 1,6 40 ft.
    ( C ) C o n t ro l wirin g f o r g ro u pc o n t ro l( D ) In t e r- o u t d o o r u n itc o n t ro l wirin g
    AWG #18 (0.7 5 mm2) AWG #18 (0 .7 5 mm2)
    Ma x. 6 50 ft. (To ta l) Ma x. 9 80 ft.
    Contr ol w ir ing
    NOTE:See table below for wire requirementsfor lines above marked “A”, “B”, “C” and “D”.
    CAUTION
    Loose wiring may cause the terminal to overheat
    or result in unit malfunction or cause a fire hazard.
    Insure that all wiring is tightly connected! 
    						
    							035-000039-001 Page 18 of 32 MVA IOM 1.3 9-10-2014
    INSTALLATION-ELECTRICAL
    Figure 11
    Inter-Unit Control Wiring
    Do not install the inter-unit control wiring
    in a way that forms a loop.
    Figure 12
    Inter-Unit Control Wiring
    Do not install inter-unit control wiring with splic-
    es or “star branch” pattern. Star branch wiring
    causes misaddress setting errors.
    If branching the inter-unit control wiring,
    the number of branch points should be
    16 or fewer. (Branches less than 3.3 ft.
    are not included in the total branch num-
    ber.)
    Figure 13
    Branched Inter-Unit Control Wiring 
    						
    							035-000039-001 Page 19 of 32 MVA IOM 1.3 9-10-2014
    INSTALLATION-ELECTRICAL (cont’d)
    TYPICAL WIRING DIAGRAM—
    Unit sizes 18 & 24
    TYPICAL WIRING—MVA18, MVA24 
    						
    							035-000039-001 Page 20 of 32 MVA IOM 1.3 9-10-2014
    INSTALLATION-ELECTRICAL (cont’d)
    TYPICAL WIRING DIAGRAM—
    Unit sizes 30, 36, 42, 48 & 60
    TYPICAL WIRING—MVA30, MVA36,
    MVA42, MVA48, MVA60 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic MVA Series Air Handling Unit Mva18 24 30 36 42 48 60 Fbas6hbcp Installation Operation And Maintenance Manual