    Have a look at the manual Panasonic Mva Series Air Handling Unit 035 000039 001 Installation Operation And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							035-000039-001 Page 31 of 38 MVA IOM 1.0 4-25-2014
    MVA Electrical Data
    240208240208240208240208240208240208240208240208240208
    3.0 3.0 n/a n/a 3.8 3.8 n/a n/a 15 15 n/a n/a 141.0 0.8 4.2 3.6 0.0 0.0 7.2 6.6 n/a n/a 9.0 8.3 n/a n/a 15 15 n/a n/a 143.0 2.3 12.5 10.8 0.0 0.0 15.5 13.8 n/a n/a 19.4 17.3 n/a n/a 20 20 n/a n/a 125.0 3.8 20.8 18.1 0.0 0.0 23.8 21.1 n/a n/a 29.8 26.3 n/a n/a 30 30 n/a n/a 106.0 4.5 25.0 21.7 0.0 0.0 28.0 24.7 n/a n/a 35.0 30.8 n/a n/a 35 35 n/a n/a 88.0 6.0 33.3 28.9 0.0 0.0 36.3 31.9 n/a n/a 45.4 39.9 n/a n/a 50 40 n/a n/a 89.5 7.1 39.6 34.3 0.0 0.0 42.6 37.3 n/a n/a 53.2 46.6 n/a n/a 60 50 n/a n/a 6
    3.6 3.6 n/a n/a 4.5 4.5 n/a n/a 15 15 n/a n/a 141.0 0.8 4.2 3.6 0.0 0.0 7.8 7.2 n/a n/a 9.7 9.0 n/a n/a 15 15 n/a n/a 143.0 2.3 12.5 10.8 0.0 0.0 16.1 14.4 n/a n/a 20.1 18.0 n/a n/a 25 20 n/a n/a 105.0 3.8 20.8 18.1 0.0 0.0 24.4 21.7 n/a n/a 30.5 27.1 n/a n/a 35 30 n/a n/a 86.0 4.5 25.0 21.7 0.0 0.0 28.6 25.3 n/a n/a 35.8 31.6 n/a n/a 40 35 n/a n/a 88.0 6.0 33.3 28.9 0.0 0.0 36.9 32.5 n/a n/a 46.2 40.6 n/a n/a 50 45 n/a n/a 89.5 7.1 39.6 34.3 0.0 0.0 43.2 37.9 n/a n/a 54.0 47.4 n/a n/a 60 50 n/a n/a 614.5 10.9 39.6 34.3 20.8 18.1 43.2 37.9 20.8 18.1 54.0 47.4 26.0 22.6 60 50 30 25 6
    4.9 4.9 n/a n/a 6.1 6.1 n/a n/a 15 15 n/a n/a 14
    1.0 0.8 4.2 3.6 0.0 0.0 9.1 8.5 n/a n/a 11.3 10.6 n/a n/a 15 15 n/a n/a 143.0 2.3 12.5 10.8 0.0 0.0 17.4 15.7 n/a n/a 21.8 19.7 n/a n/a 25 20 n/a n/a 105.0 3.8 20.8 18.1 0.0 0.0 25.7 23.0 n/a n/a 32.2 28.7 n/a n/a 35 30 n/a n/a 106.0 4.5 25.0 21.7 0.0 0.0 29.9 26.6 n/a n/a 37.4 33.2 n/a n/a 40 35 n/a n/a 88.0 6.0 33.3 28.9 0.0 0.0 38.2 33.8 n/a n/a 47.8 42.2 n/a n/a 50 45 n/a n/a 89.5 7.1 39.6 34.3 0.0 0.0 44.5 39.2 n/a n/a 55.6 49.0 n/a n/a 60 50 n/a n/a 614.5 10.9 39.6 34.3 20.8 18.1 44.5 39.2 20.8 18.1 55.6 49.0 26.0 22.6 60 50 30 25 619.5 14.6 39.6 34.3 41.7 36.1 44.5 39.2 41.7 36.1 55.6 49.0 52.1 45.1 60 50 60 50 6
    6.0 6.0 n/a n/a 7.5 7.5 n/a n/a 15 15 n/a n/a 141.0 0.8 4.2 3.6 0.0 0.0 10.2 9.6 n/a n/a 12.7 12.0 n/a n/a 15 15 n/a n/a 143.0 2.3 12.5 10.8 0.0 0.0 18.5 16.8 n/a n/a 23.1 21.0 n/a n/a 25 25 n/a n/a 10
    5.0 3.8 20.8 18.1 0.0 0.0 26.8 24.1 n/a n/a 33.5 30.1 n/a n/a 35 35 n/a n/a 106.0 4.5 25.0 21.7 0.0 0.0 31.0 27.7 n/a n/a 38.8 34.6 n/a n/a 40 35 n/a n/a 88.0 6.0 33.3 28.9 0.0 0.0 39.3 34.9 n/a n/a 49.2 43.6 n/a n/a 50 45 n/a n/a 89.5 7.1 39.6 34.3 0.0 0.0 45.6 40.3 n/a n/a 57.0 50.4 n/a n/a 60 60 n/a n/a 614.5 10.9 39.6 34.3 20.8 18.1 45.6 40.3 20.8 18.1 57.0 50.4 26.0 22.6 60 60 30 25 619.5 14.6 39.6 34.3 41.7 36.1 45.6 40.3 41.7 36.1 57.0 50.4 52.1 45.1 60 60 60 50 6
    7.6 7.6 n/a n/a 9.5 9.5 n/a n/a 15 15 n/a n/a 14
    1.0 0.8 4.2 3.6 0.0 0.0 11.8 11.2 n/a n/a 14.7 14.0 n/a n/a 15 15 n/a n/a 143.0 2.3 12.5 10.8 0.0 0.0 20.1 18.4 n/a n/a 25.1 23.0 n/a n/a 30 25 n/a n/a 105.0 3.8 20.8 18.1 0.0 0.0 28.4 25.7 n/a n/a 35.5 32.1 n/a n/a 40 35 n/a n/a 86.0 4.5 25.0 21.7 0.0 0.0 32.6 29.3 n/a n/a 40.8 36.6 n/a n/a 45 40 n/a n/a 88.0 6.0 33.3 28.9 0.0 0.0 40.9 36.5 n/a n/a 51.2 45.6 n/a n/a 60 50 n/a n/a 69.5 7.1 39.6 34.3 0.0 0.0 47.2 41.9 n/a n/a 59.0 52.4 n/a n/a 60 60 n/a n/a 614.5 10.9 39.6 34.3 20.8 18.1 47.2 41.9 20.8 18.1 59.0 52.4 26.0 22.6 60 60 30 25 619.5 14.6 39.6 34.3 41.7 36.1 47.2 41.9 41.7 36.1 59.0 52.4 52.1 45.1 60 60 60 50 6
    Notes:*1. Minimum W ire Gauge is based upon Circuit 1 ampacity and the use of 75C wire at the unit.2. 14.5kW and 19.5kW Heating units require two supply circuits.3. MVA18/24 use ECM 5.0 motor. MVA30/36/42/48/60 use ECM-VE motor.
    NONE
    CIRCUIT 1MVAUnitSize
    MOTORFLA240-208V
    NONE NONE NONE
    NONE
    NONE
    18/243.0
    60
    NONE NONE
    MINW IRESIZEAW G*CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2
    MINIMUM CIRCUITAMPACITYCIRCUIT 2
    ELECTRIC HEAT AMPS
    42
    48
    7.6
    NONE NONE
    30/36
    NONE NONE
    4.9
    3.6
    UNIT FLA Ma x imum Ove rcurre ntProte ctive De vice (A)
    6.0
    NONE NONE
    NONE
    TOTALELECTRICHT (KW )
    UNIT ELECTRICAL RATINGS 
    						
    							035-000039-001 Page 32 of 38 MVA IOM 1.0 4-25-2014
    UNIT DIMENSIONSMVA18-60 Elec Heat Ready
    RH Drain Connections—Configuration B 
    						
    							035-000039-001 Page 33 of 38 MVA IOM 1.0 4-25-2014
    UNIT DIMENSIONSMVA18-60 Elec Heat Ready
    LH Drain Connections—Configuration T 
    						
    							035-000039-001 Page 34 of 38 MVA IOM 1.0 4-25-2014
    UNIT DIMENSIONSMVA18-60 Elec Heat Ready
    RH Return — Configuration R 
    						
    							035-000039-001 Page 35 of 38 MVA IOM 1.0 4-25-2014
    UNIT DIMENSIONSMVA18-60 Elec Heat Ready
    LH Return — Configuration L 
    						
    							035-000039-001 Page 36 of 38 MVA IOM 1.0 4-25-2014
    THIS PAGE INTENTIONALLY LEFT BLANK 
    						
    							035-000039-001 Page 37 of 38 MVA IOM 1.0 4-25-2014
    MVA Series Air Handling Unit
    Start-up Report
    STARTUP REPORT
    Group Checklist Item Yes No
    Electrical/
    Operational
    Does electrical service correspond to unit nameplate?
    -Nameplate Supply Voltage/Phase: Rated_________ Measured___________
    -Nameplate Rated FLA motor current: Rated_______ Measured__________
    Does all field wiring conform to unit wiring diagram?
    Is field-provided freeze protection present? (if required)
    Is fan wheel turning the correct direction?
    Is the filter clean?
    Structural
    Is unit properly supported?
    Is unit installed level (necessary for proper condensate drainage)?
    Is properly sized condensate trap present?
    Is the condensate disposal system operating correctly?
    Is auxiliary external condensate drain pan installed or auxiliary drain connection
    utilized as recommended by IOM? (not required for valid warranty)
    PipingCheck
    Is the DX system charged per the condensing unit instructions?
    Is unit piping correct and insulated to prevent condensation?
    Are the refrigerant pipe lines properly insulated?
    Are there any leaks detected: interior to unit or at connections?
    CRITICAL!For Horizontal Unit Orientation: Is the EEV in vertical orientation?
    Job Name City
    Sales Order # Unit Tag
    Model Number Serial Number
    Installer Quantity of Units 
    						
    							035-000039-001 Page 38 of 38 MVA IOM 1.0 4-25-2014
    MVA Series Air Handling Unit
    Installation, Operation and Maintenance Manual 
    						