Home
>
Panasonic
>
Air Conditioner
>
Panasonic Mva Series Air Handling Unit 035 000039 001 Installation Operation And Maintenance Manual
Panasonic Mva Series Air Handling Unit 035 000039 001 Installation Operation And Maintenance Manual
Have a look at the manual Panasonic Mva Series Air Handling Unit 035 000039 001 Installation Operation And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
035-000039-001 Page 11 of 38 MVA IOM 1.0 4-25-2014 INSTALLATION—SERVICE CLEARANCES
035-000039-001 Page 12 of 38 MVA IOM 1.0 4-25-2014 INSTALLATION—SERVICE CLEARANCES- SIDE RETURN FILTER DETAILS
035-000039-001 Page 13 of 38 MVA IOM 1.0 4-25-2014 Install the unit so that it is level or pitches slightly –(1/8 inch) – toward the condensate drain connection. Anchor the unit to the plenum or platform through the bottom flange using 2ea #10 sheet metal screws on each side (4 screws total). Ceiling Suspension: Mount the unit in ceiling- suspended horizontal orientation per suspen- sion details (Figure 4). Unit is NOT intended to be wall mounted. Consult a qualified struc- tural engineer for special mounting considera- tions. Install the unit so that it pitches slightly –(1/8 inch) – toward the condensate drain connec- tion. Condensate Drain Install a trapped condensate drain line at unit drain connection. All MVA units have 3/4 in. FPT con- densate main and auxiliary drain connections. Provide adequate trap clearance (trap depth) be- neath the unit as indicated in Fig. 3. Provide freeze-up protection as required to insure reliable condensate drainage. Freeze protection measures are customer-supplied and installed. Pipe to condensate drain using PVC or copper or other suitable material. Pitch drain piping down- ward at a minimum slope of 1/8 inch per foot. Pipe auxiliary drain to “tell tale” drain location or floor drain to clearly indicate when condensate drain service is required. Alternately, use a field- provided condensate overflow detection device in the auxiliary drain connection to provide alarm or other controls action when the drain pan fills to the level of the auxiliary drain. Placing Unit In Ductwork 1. Utilize flexible transitions on supply and return connections to reduce noise and vibration trans- mission to the structure. INSTALLATION WARNING INSURE THAT THE UNIT IS ADE- QUATELY SUPPORTED FROM STRUCTURE TO PREVENT DAMAGE OR INJURY CAUSED BY FALLING EQUIPMENT! If uncertain about how to connect to the structure, consult a qualified structural engineer. Fig. 3 — Condensate Drain 2. W hen the connecting return air duct is smaller than the coil inlet opening, construct the transition piece so that the vertical and horizontal dimensions of the transition piece do not increase more then one inch for eve- ry seven inches of length of the transition piece. 2. Provide at least three feet of straight duct work preceding the unit inlet. Duct Insulation and Vapor Proofing: Properly select and install duct insulation as required by the application. All externally insulated duct work must have an adequate vapor seal for summer opera- tion. This is particularly important where the duct is exposed to highly humid conditions in such places as attics, vented crawl spac- es, unconditioned basements, and utility rooms. The vapor seal prevents condensa- tion of moisture in the insulating material and subsequent loss of its insulating value. NOT TO SCALE MAINTAIN THESE DIMENSIONS FOR ADEQUATE TRAPSEAL:A = 3.5” MINIMUMB = 2.0” MINIMUM NOTES:1. CONDENSATE DRAIN PIPING RECOMMENDATIONS:A. MINIMUM 3/4” Φ PIPE SIZE B. COPPER OR PVC PIPE MATERIALC. USE DIELECTRIC UNION FOR DISSIMILAR METALS.D. INSULATE PER PROJECT SPECIFICATIONS.2. PAD OR PLENUM HEIGHT AS REQUIRED TO INSTALLTRAP AND CONDENSATE DRAIN PIPING.3. AVOID BLOCKING FILTER SERVICE ACCESS W HENINSTALLING CONDENSATE DRAIN PIPING.
035-000039-001 Page 14 of 38 MVA IOM 1.0 4-25-2014 Figure 4 CEILING SUSPENSION DETAILS
035-000039-001 Page 15 of 38 MVA IOM 1.0 4-25-2014 INSTALLATION CAUTION Direct-expansion coils are shipped pressurized with dry nitrogen. Release pressure from the coil through valves in protective caps before remov- ing caps. Do not leave piping open to the atmosphere un- necessarily. Water and water vapor are detri- mental to the refrigerant system. Until the piping is complete, recap the system and charge with nitrogen at the end of each workday. Clean all piping connections before soldering joints. Failure to follow these procedures could result in personal injury or equipment damage. Refrigerant Piping Refrigerant Coils: Direct-expansion coils have liquid and suction line connections through the front of the cabinet.CAUTION: Use proper care when brazing including use of heat sink (wet cloth or other method) to pre- vent damage to liquid line and suction line components. Size and install refrigerant lines in accordance with the condensing unit manufacturer’s in- structions. Provide insulation on the suction line, to prevent condensation. Provide insula- tion on the liquid line if unit to be used for heat pump service or if otherwise required. Electric Heater Accessory The electric heater may be factory-installed or field-installed. See Figures 5 through 8. Removal Procedure: To remove the electric heater, 1. Disconnect and lock out electrical power from the unit. Remove heater access panel. Disconnect power wires from the power switch—DANGER! - MAKE SURE there is no voltage on these wires before disconnecting! 2. Disconnect 2 harness connectors at the blower deck. 3. Remove 2 screws holding heater support feet to the blower deck. 4. Remove 4 screws that mount the heater to the heater bulkhead. Handle heater carefully to avoid damaging the wire heating elements. Remove heater from the unit. DANGER WARNING:Hazardous voltage.Only qualified personnel must install the electrical service. Dis- connect and Lock Out all incoming power sources before connecting to electrical service. WARNING:This appliance must be permanently grounded in accordance with the National Electrical Code and local code requirements. WARNING: For use with copper conductors only. Fig. 5 — Heater Accessory Installed (right side panel not shown) Fig. 6 — Heater Accessory Installed (right side and heater access panels not shown)
035-000039-001 Page 16 of 38 MVA IOM 1.0 4-25-2014 INSTALLATIONDANGER WARNING:Hazardous voltage.Only qualified personnel must install the electrical service. Dis- connect and Lock Out all incoming power sources before connecting to electrical service. Install Procedure: To install the electric heater, 1. Disconnect and lock out electrical power from the unit. Remove heater access panel. Discon- nect field power wires from the unit power wires. DANGER! - MAKE SURE there is no voltage supply to the unit before proceeding! 2. Disconnect and discard 1 harness connector at the blower deck. 3. Remove blank plate from heater access panel (covers square hole for breaker style power switches). 4. Remove SAT sensor and sensor holder from heater bulkhead and reposition on unit discharge ductwork routing through auxiliary SAT sensor hole on top panel. 5. Install SAT 3 feet after the first 90 degree turn in the discharge ductwork. 6. Remove plate on the heater bulkhead (4 screws). 7. Install heater by carefully supporting the heater and inserting it into the opening in the heater bulk- head. NOTE: Make sure to guide the pin into the hole at the back of the heater shroud. Secure the heater to the bulkhead with 4 screws. 8. Connect 2 wiring harnesses (male) to the matching female receptacles in the blower deck. Fig. 7 — Heater Accessory Removal (right side and heater access panels not shown for clarity) 9. Connect field wiring to the breaker-style power switches on the front of the heater.WARNING! Be sure to provide the appropriate wire size and branch circuit protection as required by the unit nameplate! 10. Install the heater access panel. 11. Install the silicone cover “boot” over the top of the power switches. This protects them from dust buildup. The switches may be activated through the flexible boot material. 12. Mark the nameplate label with the matching heater kW rating. Label is located on the exterior of the front top panel. 13. Update EEPROM settings to values shown in the table. Refer to test run manual for detailed in- structions for changing the EEPROM settings. Fig. 8 — Heater Accessory Installed PIN HEATERSHROUD HEATERACCESSPANELCOVERBOOT HEATERSHROUD RIGHTSIDE HEATERASSEMBLY HEATERBULKHEAD POWERSWITCH(ES) Item Code New Settings 07 0001 38 0002 3C -001
035-000039-001 Page 17 of 38 MVA IOM 1.0 4-25-2014 Typical wiring diagrams are shown on the following pages FOR REFERENCE. Always refer to the wir- ing diagram on the air handling unit for actual wir- ing. NOTE: CHECK MOTOR RATING PLATE FOR CORRECT LINE VOLTAGE. Connect electrical service to unit. Refer to unit wir- ing diagram. Power Wiring For power supply connection, route field power wir- ing L1 and L2 and connect either: 1. Unit W ithout EH: to field-provided and installed disconnect switch and from switch to power entry (unit side) and to unit power leads inside the unit electrical section; or 2. Unit W ith EH: into the unit through power entry (unit side) and then to the factory installed pow- er switch inside the electrical section (see Fig- ure 9). Note: power switch looks like a circuit breaker butdoes not provide overload pro- tection. Power switch provided only with elec- tric heater (field kit or factory installed). NOTE: When electric heat greater than 10kW is pro- vided, two power supply circuits are required, as shown on the wiring diagram. Refer to nameplate or Electrical Ratings (page 30) for FLA, maximum overcurrent protection device (MOPD) and minimum circuit ampacity (MCA). Also refer to wiring diagram affixed to unit to make con- trol and power wiring connections. For new heater installation, mark the nameplate label with the matching heater kW rating. Label is located on the exterior of the front top panel. NOTE: Installer is responsible for power wiring and branch circuit over current protection. Control Voltage Wiring Control voltage wiring may enter the unit at the con- trol box located behind the blower access door, or DANGER NEVER enter an enclosed fan cabinet or reach into a unit while the fan is running. LOCK OPEN AND TAG the fan motor power dis- connect switch before working on a fan. Take fuses with you and note removal on tag. Electric shock can cause personal injury or death. LOCK OPEN AND TAG the electric heat coil power disconnect switch before working on or near heat- ers. Failure to follow these warnings could lead to per- sonal injury or death. DANGER WARNING:Hazardous voltage.Only qualified personnel must install the electrical service. Dis- connect and Lock Out all incoming power sources before connecting to electrical service. WARNING:This appliance must be permanently grounded in accordance with the National Electrical Code and local code requirements. WARNING: For use with copper conductors only. INSTALLATION-ELECTRICAL Figure 9 Unit with Electric Heat CAUTION Use only copper conductors for field-installed elec- trical wiring. Unit terminals are not designed to accept other types of conductors. Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan. Make wiring connections in accordance with the system wiring system diagram and these instruc- tions. Wrong wiring may cause improper operation or unit damage! Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or malfunction that occurs as a result of such unauthorized changes. other convenient location. Control voltage wiring leads exit the bottom of the control box and are ready for field-connection. CAUTION!To prevent malfunction of the air condi- tioner caused by electrical noise, route control wiring and inter-unit control wiring SEPARATELY FROM THE POWER WIRING! POWERSWITCH
035-000039-001 Page 18 of 38 MVA IOM 1.0 4-25-2014 DANGER WARNING:Hazardous voltage.Only qualified personnel must install the electrical service. Dis- connect and Lock Out all incoming power sources before connecting to electrical service. WARNING:This appliance must be permanently grounded in accordance with the National Electrical Code and local code requirements. WARNING: For use with copper conductors only. INSTALLATION-ELECTRICAL General Provide strain relief where field wiring passes through cabinet. Wiring within the cabinet has been positively located and supported so that it does not pass over sharp metal edges or come in contact with moving parts. After servicing, position wiring properly in the original supports. All field-installed wiring, including the electrical ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must conform to the Class II temperature limitations described in the NEC. Refer to factory wiring diagrams installed in the unit. Use the MCA and MOPD from the nameplate or electric heat nameplate or Electrical Ratings (page 30) to size power supply wiring and overcur- rent protection device. Installation must comply with NEC and local codes. For communicating controls, refer to Figures 10 through 13 for max lengths, sizing and intercon- nections. Refer to the condensing unit opera- tion manual for more details. Figure 10 Building System Wiring Diagram (multiple indoor & outdoor units) ( A ) In t e r- u n it ( b e t we e no u t d o o r a n d in d o o r u n it s )c o n t ro l wirin g ( B ) R e mo t e c o n t ro l wirin g AWG #18 (0.7 5 mm2) AWG #18 (0 .7 5 mm2) Ma x. 3 ,2 80 ft. Max. 1,6 40 ft. ( C ) C o n t ro l wirin g f o r g ro u pc o n t ro l( D ) In t e r- o u t d o o r u n itc o n t ro l wirin g AWG #18 (0.7 5 mm2) AWG #18 (0 .7 5 mm2) Ma x. 6 50 ft. (To ta l) Ma x. 9 80 ft. Contr ol w ir ing NOTE:See table below for wire requirementsfor lines above marked “A”, “B”, “C” and “D”. CAUTION Loose wiring may cause the terminal to overheat or result in unit malfunction or cause a fire hazard. Insure that all wiring is tightly connected!
035-000039-001 Page 19 of 38 MVA IOM 1.0 4-25-2014 INSTALLATION-ELECTRICAL Figure 11 Inter-Unit Control Wiring Do not install the inter-unit control wiring in a way that forms a loop. Figure 12 Inter-Unit Control Wiring Do not install inter-unit control wiring with splic- es or “star branch” pattern. Star branch wiring causes misaddress setting errors. If branching the inter-unit control wiring, the number of branch points should be 16 or fewer. (Branches less than 3.3 ft. are not included in the total branch num- ber.) Figure 13 Branched Inter-Unit Control Wiring
035-000039-001 Page 20 of 38 MVA IOM 1.0 4-25-2014 INSTALLATION-ELECTRICAL (cont’d) TYPICAL WIRING DIAGRAM— Unit sizes 18 & 24 TYPICAL WIRING—MVA18, MVA24