Page 81
20.1. Test operation • • • • Always be sure to use a properly-insu lated tool to operate the switch on the circuit board. (Do not use your finger or a metallic object). • • • • Never turn on the power supply until all installa tion work has been completed. • • • • Turn on the circuit breaker before test operation extends past 6 hours. (The crankcase heater will become energized, which will warm the compressor and prevent liquid compression.) • • • • For three-phase...
Page 85
21 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH 21.1. Energy save setting Open the cover remote control unit and confirm the presence of the [ RP1] marking. Energy save setting method should be different for with [ RP1] marking and without [RP1] marking. 85
Page 86
22 GROUP CONTROL 1 Setting group for 1 remote control unit • • • • W hen using a remote control thermostat, the thermostat setting is used for all indoor units in the group. • • • • During group control, up to a maximum of 16 indoor units can be connected. (Do not mix heat pump units and cooling only units.) • • • • Do not mix manua l settings and automatic settings. (Manual settings take priority.) • • • • The master unit and slave units can all be centrally...
Page 87
If test operation does not proceed correctly Carry out test operation after approximately 6 hours have passed since the power was turned on (crankcase heater is energized). If operation is started by using the remote control within 1 minute of turning on the power, the outdoor unit settings will not be made correctly and correct operation will not be possible. If the following symptoms occur after turning on the power, check the wiring connections once more. • • • • For standard installation...
Page 88
1. The main power is turned on while the transmission wires between the indoor unit(s) are not connected (open circuit at section A) Symptom: Nothing abnormal appears on the remote control display . If operation is then started in this condition, the combination of the 43BB outdoo r unit and the 40U indoor unit (master unit) will cause abnormal operation to occur. ↓ If operation continues, an abnormality will occur on the refrigeration cycle and operation will stop. − − − − Remote control. . ....
Page 89
1. The main power is turned on while the transmission wires between the indoor unit and the outdoor unit are not connected (open circuit at section A). Symptom: Operation of indoor unit No. 1 and indoor unit No. 3 is possible. However, “CHECK” flashes in the remote control unit display for 3-5 minutes after the main power is turned on. − − − − Remote control. . . “CHECK” flashes. − − − − Indoor unit No. 2 . . . LED2 on the printed circuit board flashes (both master and slave units)....
Page 90
1. Automatic address setting (no need to have dip-switch set) If the wiring connected properly as above example, the address is set automatically by the main powersupply. An indoor unit with remote control will be set as the master. If the power source is installe d to indoor units and outdoor separately, turn on the switch as the following procedure: outdoo r unit, indoor unit with control, and other indoor units. When theslave units do not operate (when address cannot be set) Important: The address...