Panasonic Cu W18bbp5 Cu 24bbp5 Cu W34bbp8 Cu W43bbp8 Series Repair Manual
Panasonic Cu W18bbp5 Cu 24bbp5 Cu W34bbp8 Cu W43bbp8 Series Repair Manual
Here you can view all the pages of manual Panasonic Cu W18bbp5 Cu 24bbp5 Cu W34bbp8 Cu W43bbp8 Series Repair Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 1
1 SERVICE INFORMATION 3 2 FEATURES 4 3 SPECIFICATION (HEAT PUMP TYPE) 10 4 SPECIFICATION (COOLING ONLY TYPE) 16 5 TECHNICAL DRAWING 23 6 CIRCUITDIAGRAM 31 7 OPERATING INSTRUCTION 46 8 REFRIGERATION CYCLE 48 9 OPERATIO N RANGE 51 10 PIPE LENGTH 52 11 OPERATING CHARACTERISTIC 54 12 FAN PERFORMANCE 55 13 SAFETYDEVICE 59 14 COMPONENT SPECIFICATION 60 © 2002 Matsushita Air-Conditioning Corp. Sdn. Bhd. (183914D). All rights reserved. Unauthorized copying and distribution is a...
Page 3
1 SERVICE INFORMATION Notice of Address setting for NEW Cassette / NEW Outdoor Unit. The new Ceiling / New Outdoor models are possible to have address setting fortwin / triplecontrol or group control by automatic when main powersupply is switched on. (Manual address setting is also possible by using Dip switch on Indoor unit P.C. board.) However,this address setting isonly possible when made proper wiring connection and also Indoor unit should be original virgin unit . 1.1. Example of trouble at test...
Page 4
2.1. Variety of excellent features 2.1.1. Compact design, height 27 cm • • • • The height has been reduced to 27 cm (for 2.5HP to 5.0HP), the equipment can be installe d in limited spaces. 2.1.2. Versatile installation • • • • The indoor unit is designed in order that air will also enter from below, for easier installa tion under different conditions. • • • • The equipment has two drain outlets on the right and left side for adoption to the installa tion conditions in the...
Page 5
[Product features] 2.2.1. Low-noise design improves in surrounding areas 1. The noise-suppressing winglet fan is a result of new research into vane design theory. The unique curved shape suppresses the generation of vortexes, thus reduces air flow noise. 2. The adoption of double -orifice rings reduces air passage resistance. 3. Strengthening of the noise insulation materials in the compressor and the sealing-in of mechanical noise allows vibration noise to be greatly enclosed and suppressed. 4. The...
Page 6
2.3.1. Pipes that are one size larger can also be connected for renewal • • • • If renewing the system, existing refrigerant pipes can be utilized so that only the indoor units and outdoo r units need to be replaced. • • • • For example, liquid and gas pipes from 10years ago can be connected to current pipes with the same size for one size larger. Effective utilization of materials reduces working time and trouble. (Adaptor sockets are not supplie d.) 2.3.2. Additional refrigerant...
Page 7
2.3.8. Centralized draining method • • • • Even when multiple outdoo r units are installe d to a wall, the drain outlets can be concentrated into a single drain pipe. This makes installa tion easier and also improve appearance. 2.4. A brand-new control method using the latest in technology 2.4.1. Powersupplywiring is also easier Power supply wiring and other wiring tasks can be carried out more easily. • • • • Twin non-polar wires used to connect indoor and outdoo r units. • • •...
Page 8
Twin combination table 2.5. New refrigerant Series [R407C] pipe installation 2.5.1. Procedure • • • • The new refrigerant (R407C) has a different composition to the previously-used refrigerant (R22), so some contents and method of pipe installa tion and charging work are different from before. Care should be taken whencarrying out this work. 2.5.2. Installation and precautions 2.5.2.1. Before installation 1. Determine the installa tion division. 2. Check the refrigerant to be used....
Page 9
11. Air-tightness test. For the final check, there should be no pressure drop when 3.3 MPa is applied for 24 hours. 12. Vacuum drying. Vacuum draw time60 min. or more * Vacuum pump capacity 60 l/min. or higher • • • • Drawing the vacuum will remove any moisture. • • • • The pressure after vacuum drawing should be 755 mmHg or less. • • • • Use a special vacuum pump (with backflow-prevention mechanism). • • • • Gas must never be used for air purging. 13. Additio nal...
Page 10
3 SPECIFICATION (HEAT PUMP TYPE) 3.1. CS-W18BD3P / CU-W18BBP5 ITEM / MODELIndoor UnitOutdoor unit Main BodyCS-W18BD3PCU-W18BBP5 Cooling CapacitykW5.00 (BTU/h)(17,100) Heating CapacitykW5.60 (BTU/h)(19,000) Refrigerant Charge-lessm30 Standard Air Volume for High Speedm3/minHi 17 cfmHi 600 External Static PressuremmAqHi 5- PaHi 49 Air InletBackward SuctionBack sided Suction Air OutletFront blow-outFront blow-out Outside Dimension (H x W x D)mm290 x (780 + 100) x 650900 x 900 x 320 Net Weightkg (lbs)34...