REMARKS B: BLUEP: PINK BR: BROWNR: RED BL: BLACKW: WHITE G: GREENY: YELLOW GRY: GRAYY/G: YELLOW/GREEN O: ORANGE Resistance of Indoor Fan Motor Windings MODELCS-XC9CK CS-XC12CK CONNECTIONCWA921060CWA921181 BLUE-YELLOW371.0Ω390Ω YELLOW-RED386.6Ω390Ω Note: Resistance at 20°C/25°C of ambient temperature. Resistance of Outdoor Fan Motor Windings MODELCU-XC9CK CONNECTIONCWA951088CWA951114 BLUE-YELLOW217.3Ω259Ω YELLOW-RED198.5Ω235Ω MODELCU-XC12CK CONNECTIONCWA951116 BLUE-YELLOW230Ω YELLOW-RED255Ω Note: Resistance at 20°C of ambient temperature. Resistance of Compressor Windings MODELCU-XC9CKCU-XC12CK CONNECTION2PS146D3AA042KS206D5AF04 C-R3.941Ω2.234Ω C-S3.499Ω2.630Ω Note: Resistance at 20°C/25°C of ambient temperature. 7 Wiring Diagram 14
8 Operation Details 8.1. Indoor Fan Speed Control • Auto Fan Speed Control When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table. • Manual Fan Speed Control Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection button at the remote control. 15
Cooling in operation according to Remote Control setting. Time Delay Safety Control (3 minutes) 7 minutes Time Save Control Starting Current Control Anti-Freezing Control • If the temperature of the indoor heat exchanger falls continuously below 2°C for 4 minutes or more, the compressor turns off to protect the indoor heat exchanger from freezing. The fan speed setting remains the same. • Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery). 3 minutes waiting of TimeDelay Safety Controlis valid for Cooling Operation. Compressor Reverse Rotation Protection Control 8.2. Cooling Mode Operation • When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON. • When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes. • The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor ON temperature and OFF temperature. • When the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6 second later. • If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor heat exchanger is 2.5°C or less for 2minutes, compressor will stopand restartautomatically. (Time DelaySafety Controlis valid) sT = Intake air temperature - Indoor heat exchanger temperature This is to protect reverse rotation of the compressor when there is a instantaneous power failure. 16
Automatic Fan Speed Mode Cooling Operation Time Diagram When Automatic Fan Speed is selected at Remote Control during cooling operation. • Fan speed rotates in the range of Hi to Me. • Deodorizing Control. 17
Quiet Operation Control (For Cooling Mode or cooling region of Soft Dry Mode) • Purpose of this operation is to provide quite cooling operation compare to normal operation. • When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates, the sound level will be automatically decreased 2 dB (Lo), decreased 3 dB (Hi, Me), against the present sound level operation. • Quiet setting of fan speed rpm refer to Indoor Fan Speed Control. • Dew formation become severe at Quiet Lo cool, therefore Quiet Lo coolis operated only 1h 30 min (1h QLo, 30 min QLo + 50). After that, it goes back to Lo cool (However Quiet LED remains on). • Manual Fan Speed:- − RPM control during Lo cool − RPM control during Hi & Me cool • Auto Fan Speed:- • Quiet Mode Operation will stop if:- − Quiet mode button is pressed again. − Stopped by ON/OFF switch. − Timer OFF activates. − When change mode to Air Circulation mode. 18
Time Delay Safety Control Starting Current Control Anti-Freezing Control Compressor Reverse Rotation Protection Control Automatic Fan Speed Mode 8.3. Soft Dry Mode Operation • The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and then Soft Dry operation will start. • During Soft Dry operation, the Indoor Fan will operate at Lo- speed. • The operation will be switched on and off for up to 10 minutes “ON” and 6 minutes “OFF”. Once Soft Dry operation is turned off, it stops for 6 minutes. • Once the compressor stops, it will not start for 3 minutes during Cooling operation. • Same as Starting Current Control for Cooling Mode operation. • Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor stops.) • Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting is valid during compressor stops.) When Automatic Fan Speed is selected at Remote Control during Soft Dry operation. • Fan speed off and on at Lo- speed. • Deodorizing Control. 19
Soft Dry Operation Time Diagram Quiet Operation Control (For Dry region of Soft Dry Mode) 20