    REFRIGERANT ADDITIONAL CHARGE
     1. Piping installation by standard piping
     
        • 
    • •  • 
    At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 30m.
    (Refer to the following table)
    But when the piping length exceed s 30m, additio nal charge is required according to the following table.
    Example:
    CU-W50B BP8
    In case of 50m long pipe (one way), the amoun t of refrigerant to be replenished is: (50 - 30) x 50 = 1,000g
    Q
    Coolingonly type(50Hz)
    Model NameStandard piping specification
    CU-Liquid piping (dia.mm)Gas piping (dia.mm)Gas charge- less length (m)Additional gas volume (g/m)
    V50BBP89.5219.053050
    Q
    Heat pumptype(50Hz)
    Model NameStandard piping specification
    CU-Liquid piping (dia.mm)Gas piping (dia.mm)Gas charge- less length (m)Additional gas volume (g/m)
    W50BBP89.5219.053050
     
        • 
    • •  • 
    Please do not decrease the gas piping size. (It causes the breakdown of the compressor).
     
        • 
    • •  • 
    The equivalent piping length and the cooling and heating capacity change rate are same as the standard piping specification.
    31 
    						
    							11 OPERATING CHARACTERISTIC
    HEAT PUMPMODEL
    ModelMain Power SourceCompressor MotorIndoor Unit
    Fan MotorOutdoor unit
    Fan MotorELECTRICAL DATA
    (50Hz)
    VoltageFrequencyS.C.R.C. (A)IPT (kW)R.C.IPTR.C.IPTF.C. (A)IPT (kW)
    (V)(Hz)(A)COOL /
    HEATCOOL /
    HEAT(A)(kW)(A)(kW)COOL /
    HEATCOOL /
    HEAT
    HEATCS-W50BB4P38050698.57 / 8.574.94 / 5.040.910.190.990.229.20 / 9.205.35 / 5.45
    PUMPCU-W50BBP840050698.55 / 8.554.91 / 5.010.930.211.020.239.20 / 9.205.35 / 5.45
    MODEL41550698.53 / 8.534.88 / 4.980.960.221.040.259.20 / 9.205.35 / 5.45
    COOLING ONLY MODEL
    COOLINGCS-W50BB4P38050698.574.940.910.190.990.229.205.35
    ONLYCU-V50BBP840050698.554.910.930.211.020.239.205.35
    MODEL41550698.534.880.960.221.040.259.205.35
    Legend : S.C. = Starting Current, R.C. = Runnin g Current, IPT = Power Consumption
    32 
    						
    							12 FAN PERFORMANCE
    33 
    						
    							13 SAFETY DEVICE
    INDOOR UNIT
    Heat pump model
    Indoor unitCS-W50BB4P
    Cooling only model
    For Fan Motor Protection,OFF°C135
    Internal Protector (49F)ON°C85
    For Control Protection, FuseCUTA3.15
    OUTDOOR UNIT
    Outdoor UnitHeat pump model50HzCU-
    W50BBP8
    Cooling
    only50HzCU-
    V50BBP8
    model60Hz-
    For Refrigerant Cycle,OFFMPa (*1)3.1
    High Pressure Switch (63H1)ONMPa (*1)2.3
    ForOFFA15
    Compressor(Heat pump)
    Over CurrentOFFA15
    Protection(Cooling only model)50Hz
    A-
    60Hz
    RESET-Automatic
    Discharge Temp.Compressor°C120
    Protection,OFF
    Discharge Temp.
    Thermistor (Th1)
    Liquid Compression Protection, Crankcase HeaterInput powerW34~41
    CompressorOFF°C145
    Protection,50Hz
    Internal°C-
    Protector60Hz
    ON°C 50Hz61
    °C 60Hz-
    Trip time50Hz3-10sec/
    48A
    60Hz-
    For Fan Motor Protection,OFF°C135
    Internal Protector (49F)ON°C85
    Heating Pressure Switch (HeatOFFMPa (*1)2.50
    Pump Only) (Fan Speed) (63H2)ONMPa (*2)2.05
    Cooling Control,ControlTh30°C ----- High speed
    Heat ExchangermethodTh < 30°C ------5 speed step control
    Outlet Temp.
    Thermistor (Th2)
    For Control Protection, FuseCUTA6.3
    (*1) MPa = 10.2 kgf/cm2(*2) Head Thermostat only for CU-A28BBP8 / CU-C28BB P8
    34 
    						
    							14 COMPONENT SPECIFICATION
    Compressor
    ModelsHeat pump model50HzCU-W50BBP8
    Cooling only50HzCU-V50BBP8
    model
    60Hz-
    Compressor Modelsingle-phase-
    3-phaseR68KCE-TFD
    Compressor TypeSCROLL
    No. of Cylinders1
    Revolutionr/min2,900
    Piston Diplacementm3/h16.18
    Motor TypeStarting MethodDirect on-line Starting
    Rated OutputkW4.1
    Poles2
    Insulation ClassE
    OilTypeMMMAPOE
    ChargeL1.8
    Evaporator
    ModelsCS-W50BB4P
    Tube MaterialCopper tube
    Outer Diametermm7.0
    Thicknessmm0.27
    Row3
    No. of Tubes/Row12
    Fin MaterialAluminium
    Thicknessmm0.105
    Fin PitchNO./inch19
    Fin SurfaceZ Slit fin
    Total Face Aream20.464
    FanTypeTurbo fan
    No. of /Unit1
    Fan MotorStarting MethodDirect on-line Starting
    Rated OutputkW0.095
    Poles6
    PhaseSingle-Phase
    Insulation ClassE
    Condenser
    ModelsHeat pump modelCU-W50BBP8
    Cooling only modelCU-V50SBBP8
    Tube MaterialCopper tube
    Outer Diametermm9.52
    Thicknessmm0.3
    Row2
    No. of Tubes/Row46
    Fin MaterialAluminium
    Thicknessmm0.105
    Fin PitchNO./inch14
    Fin SurfaceX-Louvre fin
    Total Face Aream21.05
    FanTypePropeller Fan
    No.of /Unit2
    FanStarting MethodDirect on-line Starting
    MotorRated OutputkW0.055 x 2
    Poles6
    PhaseSingle-Phase
    Insulation ClassE
    35 
    						
    							15 CAPACITY AND POWER CONSUMPTION
    15.1. HEATING PERFORMANCE
    ModelHeating capacities are based on conditions below.
    CS-W50BB4PO3 phase, 50Hz, 400V
    OIndoor temperature 20°C D.B.T.
    OOutdoor temperature 7°C D.B. 6°C W.B.T.
    OStandard air volume 31m
    3/min
    CU-W50BBP8
    Heating capacity 14.0 kW
    Inlet AirOutdoor Temperatu re(°C W.B.T.)
    External Static Presser
    (Pa) Air Volume (m3/min)Entering Air
    D.B.T. (°C)-6°C0°C6°C12°C
    H.C.IPTH.C.IPTH.C.IPTH.C.IPT
    1511.683.8214.004.3616.85.1819.56.10
    31m3/min2011.044.0313.204.6316.05.4519.26.32
    2510.404.2512.484.9115.25.7218.46.52
    H.C.= Heating Capacity
    IPT= Power Consumption
    36 
    						
    							15.2. COOLING PERFORMANCE
    CS-W50BB4P
    ModelCooling capacities are based on conditions below.
    CS-W50BB4PO3 phase, 50Hz, 400V
    OIndoor temperature 27°C D.B.T., 19°C W.B.T.
    OOutdoor temperature 35°C D.B.T.
    OStandard air volume 31m
    3/minCooling capacity 14.0 kW
    Cooling capacityCooling power consumption
    Indoor Air Temp.Outdoor Temperatu re (°C D.B.T.)Indoor Air Temp.Outdoor Temperatu re (°C D.B.T.)
    25303540432530354043
    TCTCTCTCTCIPTIPTIPTIPTIPT
    D.B.TW.B.TkWkWkWkWkWD.B.T.W.B.T.kWkWkWkWkW
    1714.5714.0013.1712.1811.47174.264.615.025.515.84
    231915.3914.9114.1513.1912.5223194.514.895.335.846.19
    2216.8116.3615.6114.6013.91224.885.285.756.316.69
    1714.4013.8413.0412.0911.41174.264.615.015.485.80
    251915.4114.8814.0713.1112.4225194.544.905.345.836.18
    2216.8016.2915.4914.4313.78224.905.295.766.296.67
    1714.2213.6812.9112.0011.36174.274.605.015.445.77
    271915.4314.8414.0013.0212.3227194.564.926.355.826.16
    2216.7916.2215.3714.2813.65224.935.315.786.286.66
    1714.1913.6812.8812.1011.50174.244.594.955.315.54
    291915.4014.8414.0113.1212.4729194.534.915.295.685.92
    2216.7216.1515.2714.3013.64225.005.405.826.256.51
    1714.1713.6911.9712.1611.59174.234.584.915.235.38
    321915.3714.8414.0113.1912.5732194.524.905.245.585.75
    2216.6716.1015.2614.3113.64225.045.475.856.236.57
    37 
    						
    							16 DISCHARGE AND SUCTION PRESSURE
    16.1. SATURATION TEMPERATURE OF DISCHARGE AND SUCTION
    PRESSURE
    O
    OO O
    Commonness TO ALL THE MODELS
    O
    OO O
    SATURATIONTEMPERATURE OF DISCHARGE AND SUCTION PRESS URE
    *For intake temperature, consult the pressure - Enthalpy Table (R407C) at the end.