    							20.1. Test operation
     
        • 
    • •  • 
    Always be sure to use a properly-insu lated tool to operate
    the switch on the circuit board. (Do not use your finger or a
    metallic object).
     
        • 
    • •  • 
    Never turn on the power supply until all installa tion work has
    been completed.
     
        • 
    • •  • 
    Turn on the circuit breaker before test operation extends
    past 6 hours.
    (The crankcase heater will become energized, which will
    warm the compressor and prevent liquid compression.)
     
        • 
    • •  • 
    For three-phase models, check that the phase is not
    reversed.
    (Outdoor unit printed circuit board)
    During outdoor unit emergency operation or test operation, the
    LEDs on the printed circuit board will flash.
    To cancel test operation, press the TEST or RUN button once
    more while test operation is being carried out.
    (Test operation will stop automatically after 30 minutes have
    passed.)
    NOTE:
     1. These units are equipped with connection error prevention
    circuits. If the units do not operate, it is possible that the
    connection error prevention circuits have operated. In such
    cases, check that the drive wires (connected to terminals [1]
    and [2]) and the control wires (connected to terminals [3]
    and [4]) are connected correctly. If they are connected
    incorrectly, connect them correctly. Normal operation
    should then commence.(If the phase is reversed, the LED on the printed circuit
    board will flash.)
     
        • 
    • •  • 
    Check that the voltage is 198 V or higher when starting the
    unit. (The unit will not operate if the voltage is less than
    198V.)
     
        • 
    • •  • 
    Carry out test operation for 5 minutes or more using the
    remote control or the switch on the outdoor unit printed
    circuit board.
     
        • 
    • •  • 
    Always carry out cooling first during test operation, even
    during the warm season.
    (If heating is carried out first, problems with operation of the
    compressor will result.)
     2. Do not short the remote control unit wires to each other.
    (The protection circuit will be activated and the units will not
    operate.)
    Once the cause of the short is eliminated, normal operation
    will then be possible.
    20 TEST OPERATION AND SELF DIAGNOSIS
    20.2. Test operation from the outdoor unit
    81 
    						
    							20.3. Test operation using the wired remote control
    82 
    						
    							83 
    						
    							
     
    Self-diagnosis error code table
    84 
    						
    							21 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH
    21.1. Energy save setting
    Open the cover remote control unit and confirm the presence of the [ RP1] marking.
    Energy save setting method should be different for with [ RP1] marking and without [RP1] marking.
    85 
    						
    							22 GROUP CONTROL
    1 Setting group for 1 remote control unit
     
        • 
    • •  • 
    W hen using a remote control thermostat, the thermostat setting is used for all indoor units in the group.
     
        • 
    • •  • 
    During group control, up to a maximum of 16 indoor units can be connected. (Do not mix heat pump units and cooling only
    units.)
     
        • 
    • •  • 
    Do not mix manua l settings and automatic settings. (Manual settings take priority.)
     
        • 
    • •  • 
    The master unit and slave units can all be centrally controlled during group control.
    Automatic setting for group control
     
        • 
    • •  • 
    If the power supplie s for indoor units which are connected are turned on simultaneousl y, the indoor unit numbe rs will be
    determined automatically after approximately 1 minute. (DIP switch settings are not necessary.)
    NOTE:
     
        • 
    • •  • 
    Correct wiring connections are basic requirements for automatic setting. If the wires are connected incorrectly when the power
    is turned on, the settings will not be made correctly and operation will not be possible.
     
        • 
    • •  • 
    W hen address numbe rs are set automatically , you will not know which address numbe r corresponds to which indoor unit.
     
        • 
    • •  • 
    Do not turn off the power supply for at least 1 minute duringautomatic address setting, otherwise the settings will not be made
    correctly.
    Automatic address resetting for group control
    After setting DIP switches 1 to 4 to OFF and stop operation. Then press the “AIR SWING AUTO”, “OPERATION MODE” and “Air
    conditioner No.” switches simultaneousl y. Then addresses will be momentarily reset, and then automatic address setting will be
    carried out once more.
    Switching the thermistor
     
        • 
    • •  • 
    The temperature detection thermistor used for detecting the air temperature and changing between COOL and HEAT
    operation can be switched between the thermistor at the indoor unit and the thermistor at the remote control unit box.
    However, do not switch to the remote control unit thermistor if using two remote control units.
     1. While operation is stopped, press and hold the STOP/RUN switch, and then press the UP andDOWN
    switches together.
     2. DO or 01 will appear in the time display .
     3. Press theFORWARD orBACK timer switches to switch thedisplay between 00 and 01 . 00 ... Indoor unit setting
    (factory default ) 01 ... Remote control unit setting
     4. Press the RESERVE switch. (Be sure to press the RESERVE switch so that normal operation mode can be resumed.)
     
        • 
    • •  • 
    Repeat the procedure in steps (1) to (4) to change the setting again.
    86 
    						
    							If test operation does not proceed correctly
    Carry out test operation after approximately 6 hours have passed
    since the power was turned on (crankcase heater is energized). If
    operation is started by using the remote control within 1 minute of
    turning on the power, the outdoor unit settings will not be made
    correctly and correct operation will not be possible.
    If the following symptoms occur after turning on the power,
    check the wiring connections once more.
     
        • 
    • •  • 
    For standard installation
    (System example)
     1. The main power is turned on while the indoor-outdoo r
    transmission wires are not connected (open circuit at
    section A)
    Symptom:
    Remote control unit . . . “CHECK” flashes
    NOTE:
    Indoor unit. . . LED2 on printed circuit board flashes
    Outdoor unit. . . LED3 and LED7 on printed circuit
    board flash
     2. The main power is turned on while the indoor-outdoo r
    power supply wires are not connected (open circuit at
    section B)
    Symptom:
    Remote control unit . . . Display of “No power supply”
    NOTE:
    Indoor unit...Nodisplay
    Outdoor unit. . . LED3 and LED7 on printed circuit
    board flash
     3. The main power is turned on while the remote control
    unit connection cord is not connected (open circuit at
    section C)Symptom:
    Remote control unit . . . Display of “No power supply”
    NOTE:
    Indoor unit . . . LED1 on printed circuit board stays
    illuminated
    Outdoor unit . . . LED1 on printed circuit board stays
    illuminated
    (When remote controldisplay shows “Power supply ”)
    (When remote controldisplay shows “No power supply ”)
    Remedy
     1. Turn off the main power.
    ↓
     2. Conne ct the disconnected wire correctly.
    ↓
     3. Turn the main power back on.
    ↓
     4. After 1 minute, start operation using the remote control.
    (Indoor unit . . . Operation will start according to the
    remote control setting.)
    (Outdoor unit...Operation will start after 3-5 minutes.)
    NOTE:
    The “CHECK” display on theremote control and the
    flashing of LEDs on the printed circuit boards will not occur
    immediately. They will appear 3-6 minutes after the main
    power is turned on.
    23 TROUBLE SHOOTING
    87 
    						
    							 1. The main power is turned on while the transmission
    wires between the indoor unit(s) are not connected
    (open circuit at section A)
    Symptom:
    Nothing abnormal appears on the remote control
    display . If operation is then started in this condition, the
    combination of the 43BB outdoo r unit and the 40U
    indoor unit (master unit) will cause abnormal operation
    to occur.
    ↓
    If operation continues, an abnormality will occur on the
    refrigeration cycle and operation will stop.
     
        − 
    − −  − 
    Remote control. . . “CHECK” flashes
     
        − 
    − −  − 
    Indoor unit (master). . . The LEDs on the printed
    circuit board flash and operation stops
     
        − 
    − −  − 
    Indoor unit (slave) . . . LED1 on the printed circuit
    board illuminates and the unit does not operate at all
     
        − 
    − −  − 
    Outdoor unit . . . The LEDs on the printed circuit
    board flash and operation stops
     2. The main power is turned on while the power supply
    wires between the indoor unit(s) are not connected
    (open circuit at section B)
    Symptom:
    Same as above. If operation continues, an abnormality
    will occur on the refrigeration cycle and operation will
    stop.
    ↓
     
        − 
    − −  − 
    Remote control. . . “CHECK” flashes
     
        − 
    − −  − 
    Indoor unit (master). . . The LEDs on the printed
    circuit board flash
     
        − 
    − −  − 
    Indoor unit (slave) . . . The LEDs on the printed
    circuit board do not illuminate and the unit does not
    operate at all
     
        − 
    − −  − 
    Outdoor unit . . . The LEDs on the printed circuit
    board flash and operation stops 3. The main power is turned on while the remote control
    connection cord is not connected (open circuit at section
    C)
    Symptom:
     
        − 
    − −  − 
    Remote control unit . . . Display of “No powersupply ”
     
        − 
    − −  − 
    Indoor unit (master). . . LED1 on the printed circuit
    board stays illuminated and the unit does not
    operate
     
        − 
    − −  − 
    Indoor unit (slave) . . . LED1 on the printed circuit
    board stays illuminated and the unit does not
    operate
     
        − 
    − −  − 
    Outdoor unit . . . LED1 on the printed circuit board
    stays illuminated and the unit does not operate
    Remedy
     1. Turn off the main power.
    ↓
     2. Conne ct the disconnected wires correctly.
    ↓
     3. Turn the main power back on.
    ↓
     4. After 1 minute, start operation using the remote control.
    (Indoor units . . . Operation will start according to the
    remote control setting.)
    (Outdoor unit...Operation will start after 3-5 minutes.)
    If slave units do not operate even after the wiring has been
    corrected (automatic addressing is not possible)
     1. Check that DIP switches 1 to 4 and DIP switch 8 are all
    set to OFF, and then stop operation.
    ↓
     2. Press the ADDRESS RESET button(SW3) at the
    outdoo r unit for approximately 4 seconds
    (The self-diagnosis LEDS 2 to 8 will illuminate in order,
    and the system is reset once they are all illuminated.)
    The above procedure cannot be used to carry out automatic
    address resetting during group control.
    88 
    						
    							 1. The main power is turned on while the transmission
    wires between the indoor unit and the outdoor unit are
    not connected (open circuit at section A).
    Symptom:
    Operation of indoor unit No. 1 and indoor unit No. 3 is
    possible.
    However, “CHECK” flashes in the remote control unit
    display for 3-5 minutes after the main power is turned
    on.
     
        − 
    − −  − 
    Remote control. . . “CHECK” flashes.
     
        − 
    − −  − 
    Indoor unit No. 2 . . . LED2 on the printed circuit
    board flashes (both master and slave units).
     
        − 
    − −  − 
    Outdoor unit No. 2 . . . LED3 and LED7 on the
    printed circuit board flash.
     2. The main power is turned on while the power supply
    wires between the indoor units are not connected (open
    circuit at section B).
    Symptom:
    Operation of indoor unit No. 1 and indoor unit No. 3 is
    possible.
    However, if operation is then started in this condition,
    the combination of the 28BB outdoo r unit and the 14BB
    indoor unit (master unit) will cause abnormal operation
    of indoor unit No. 2 to occur.
    ↓
    If operation continues, an abnormality will occur on the
    refrigeration cycle and aoperation will stop.
     
        − 
    − −  − 
    Remote control . . . “CHECK” flashes (indoor unit
    No. 2 abnormality).
     
        − 
    − −  − 
    Indoor unit No. 2 . . . LED2 on the printed circuit
    board flashes (both master and slave units).
     
        − 
    − −  − 
    Outdoor unit No. 2 . . . The LEDs on the printed
    circuit board flash.
     3. The main power is turned on while the remote control
    connection cord is not connected (open circuit at section
    C).Symptom:
    Nothing abnormal appears on the remote control
    display , and operation of indoor unit. No. 1 and indoor
    unit No. 2 is possible.
    However, indoor unit No. 3 cannot be operated.
    Remedy
     1. Turn off the main power.
    ↓
     2. Conne ct the disconnected wires correctly.
    ↓
     3. Turn the main power back on.
    ↓
     4. After 1 minute, start operation using the remote control.
    (Indoor units . . . Operation will start according to the
    remote control setting.)
    (Outdoor units...Operation will start after 3-5 minutes.)
    If slave units do not operate even after the wiring has been
    corrected (automatic addressing is not possible)
     1. Check that DIP switches 1 to 4 and DIP switch 8 are all
    set to OFF, and then stop operation.
    ↓
     2. Press the “AIRSWING AUTO”, “OPERATION ” and “A/C
    No.” buttons simultaneousl y.
    The addresses will be momentarily reset, and then
    automatic address setting will be carried out once more.
    The above procedure cannot be used to carry out automatic
    address resetting of twin/triple control.
    (Note on automatic address setting)
    The printed circuit boards automatically store the connected
    system configuration when power is supplie d. As a result,
    once the power has been turned on for these printed circuit
    boards, the units can not be changed about within the
    system, even if the units are of the same model and have
    same capacity.
    89 
    						
    							 1. Automatic address setting (no need to have dip-switch set)
    If the wiring connected properly as above example, the address is set automatically by the main powersupply. An indoor unit
    with remote control will be set as the master. If the power source is installe d to indoor units and outdoor separately, turn on the
    switch as the following procedure: outdoo r unit, indoor unit with control, and other indoor units.
    When theslave units do not operate (when address cannot be set)
    Important: The address for the group control cannot be reset, using the above mentioned procedure.
     2. Manua l address setting (by dip-switchDSW1)
    When you set theaddress manua lly, set the dip-switch of the PC board in the indoor unit as follow:
    90 
    						