3.3. CS-W28BD2P / CU-W28BBP8 ITEM / MODELIndoor UnitOutdoor unit Main BodyCS-W28BD2PCU-W28BBP8 Cooling CapacitykW7.10 (BTU/h)(24,200) Heating CapacitykW8.00 (BTU/h)(27,300) Refrigerant Charge-lessm30 Standard Air Volume for High Speedm3/minHi 20 cfmHi 706 External Static PressuremmAqHi 10- PaHi 98 Air InletBackward SuctionBack sided Suction Air OutletFront blow-outFront blow-out Outside Dimension (H x W x D)mm290 x (1000 + 100) x 500900 x 900 x 320 Net Weightkg (lbs)43 (95)82 (181) Piping ConnectionRefrigerantGasmm (inch)O.D Ø 15.88 (5/8) Flared Type Liquidmm (inch)O.D Ø 9.52 (3/8) Flared Type DrainmmFemale screw RC1 (PT1)I.DØ 20 x 1 CompressorType, Number of Set-Hermetic-1 (Rotary), 1 Starting Method-Direct on-line starting MotorType-2-pole 3-phase induction motor Rated OutputkW-2.0 FanType, Number of SetSirocco fanProp. fan Air Volume ControlThree-Step and Auto mode- (Remote Control) MotorType4-pole single phase induction motor6-pole single phase induction motor Rated OutputkW0.150.05 Air-heat ExchangerLouvre-fin typeX-Louvre-fintype Refrigerant ControlCapillary tubeCapillary tube Refrigerant Oil (Charged)L-MEL56 (1.3) Refrigerant (Charged)kg (oz)-R407C 3.3 (116) Running AdjustmentControl SwitchWired RemoteControl- Room Temperatu reThermosta t (Main Body)- Safety DevicesHead thermostat for compressor, Internal thermostat for F.M, Crankcase heater, High pressure switch, Current Transformer Noise LeveldB (A)Hi 41 Lo 37Cooling 53, Heating 54 Power level dBHi 56 Lo 52Cooling 66, Heating 67 1. Coolin g capacities are based on indoor temp. 27°C D.B. (80.6°F D.B.), 19.0°CW.B.(66.2°F W.B.) and outdoor air temp. 35°C D.B. (95°F D.B.), 24°CW.B.(75.2°F W.B.) 2. Heating capacities are based on indoor temp. 20°C D.B. (68.0°F D.B.) and outdoor air temp. 7°C D.B. (44.6°F D.B.), 6°CW.B. (42.8°F D.B.) ELECTRICAL DATA (50Hz) MODEL / ITEMCS-W28BD2P/CU-W28BBP8 Condition by JIS B 8615 VoltsV380400415 Phase3N3N3N Input PowerkWCool2.722.722.72 Heat2.862.862.86 Running CurrentACool4.64.64.6 Heat4.54.54.5 Starting CurrentA282930 Power Factor%Cool908582 Heat979288 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. PanasonicPower sourceAC, 3N~380V, 400V, 415V 50Hz 11
3.4. CS-W34BD2P / CU-W34BBP8 ITEM / MODELIndoor UnitOutdoor unit Main BodyCS-W34BD2PCU-W34BBP8 Cooling CapacitykW10.00 (BTU/h)(34,100) Heating CapacitykW11.20 (BTU/h)(38,200) Refrigerant Charge-lessm30 Standard Air Volume for High Speedm3/minHi 33 cfmHi 1165 External Static PressuremmAqHi 15- PaHi 147 Air InletBackward SuctionBack sided Suction Air OutletFront blow-outFront blow-out Outside Dimension (H x W x D)mm360 x (1000 + 100) x 6501220 x 900 x 320 Net Weightkg (lbs)56 (123)97 (214) Piping ConnectionRefrigerantGasmm (inch)O.D Ø 15.88 (5/8) Flared Type Liquidmm (inch)O.D Ø 9.52 (3/8) Flared Type DrainmmFemale screw RC1 (PT1)I.DØ 20 x 1 CompressorType, Number of Set-Hermetic-1 (Scroll), 1 Starting Method-Direct on-line starting MotorType-2-pole 3-phase induction motor Rated OutputkW-3.0 FanType, Number of SetSirocco fanProp. fan Air Volume ControlThree-Step and Auto mode- (Remote Control) MotorType4-pole single phase induction motor6-pole single phase induction motor Rated OutputkW0.250.05 x 2 Air-heat ExchangerLouvre-fin typeX-Louvre-fintype Refrigerant ControlCapillary tubeCapillary tube Refrigerant Oil (Charged)L-MMMAPOE (1.3) Refrigerant (Charged)kg (oz)-R407C 3.2 (113) Running AdjustmentControl SwitchWired RemoteControl- Room Temperatu reThermosta t (Main Body)- Safety DevicesInternal protector for compressor, Internal thermostat for F.M, Crankcase heater, High pressure switch, Current Transformer Noise LeveldB (A)Hi 47 Lo 43Cooling 56, Heating 58 Power level dBHi 62 Lo 58Cooling 69, Heating 71 1. Coolin g capacities are based on indoor temp. 27°C D.B. (80.6°F D.B.), 19.0°CW.B.(66.2°F W.B.) and outdoor air temp. 35°C D.B. (95°F D.B.), 24°CW.B.(75.2°F W.B.) 2. Heating capacities are based on indoor temp. 20°C D.B (68.0°F D.B.) and outdoor air temp. 7°C D.B. (44.6°F D.B.), 6°C W.B. (42.8°F D.B.) ELECTRICAL DATA (50Hz) MODEL / ITEMCS-W34BD2P/CU-W34BBP8 Condition by JIS B 8615 VoltsV380400415 Phase3N3N3N Input PowerkWCool3.883.883.88 Heat4.074.074.07 Running CurrentACool6.26.26.2 Heat6.56.56.5 Starting CurrentA394142 Power Factor%Cool959087 Heat959087 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. PanasonicPower sourceAC, 3N~380V, 400V, 415V 50Hz 12
3.5. CS-W43BD2P / CU-W43BBP8 ITEM / MODELIndoor UnitOutdoor unit Main BodyCS-W43BD2PCU-W43BBP8 Cooling CapacitykW12.50 (BTU/h)(42,600) Heating CapacitykW14.0 (BTU/h)(47,700) Refrigerant Charge-lessm30 Standard Air Volume for High Speedm3/minHi 36 cfmHi 1271 External Static PressuremmAqHi 15- PaHi 147 Air InletBackward SuctionBack sided Suction Air OutletFront blow-outFront blow-out Outside Dimension (H x W x D)mm360 x (1000 + 100) x 6501220 x 1100 x 320 Net Weightkg (lbs)58 (128)114 (251) Piping ConnectionRefrigerantGasmm (inch)O.D Ø 19.05 (3/4) Flared Type Liquidmm (inch)O.D Ø 9.52 (3/8) Flared Type DrainmmFemale screw RC1 (PT1)I.DØ 20 x 1 CompressorType, Number of Set-Hermetic-1 (Scroll), 1 Starting Method-Direct on-line starting MotorType-2-pole 3 phase induction motor Rated OutputkW-3.75 FanType, Number of SetSirocco fanProp. fan Air Volume ControlThree-Step and Auto mode- (Remote Control) MotorType4-pole single phase induction motor6-pole single phase induction motor Rated OutputkW0.350.055 x 2 Air-heat ExchangerLouvre-fin typeX-Louvre-fintype Refrigerant ControlCapillary tubeCapillary tube Refrigerant Oil (Charged)L-MMMAPOE (2.0) Refrigerant (Charged)kg (oz)-R407C 3.6 (127) Running AdjustmentControl SwitchWired RemoteControl- Room Temperatu reThermosta t (Main Body)- Safety DevicesInternal protector for compressor, Internal thermostat for F.M, Crankcase heater, High pressure switch, Current Transformer Noise LeveldB (A)Hi 48 Lo 44Cooling 56, Heating 58 Power level dBHi 63 Lo 59Cooling 69, Heating 71 1. Coolin g capacities are based on indoor temp. 27°C D.B. (80.6°F D.B.), 19.0°CW.B.(66.2°F W.B.) and outdoor air temp. 35°C D.B. (95°F D.B.), 24°CW.B.(75.2°F W.B.) 2. Heating capacities are based on indoor temp. 20°C D.B. (68.0°F D.B.) and outdoor air temp. 7°C D.B. (44.6°F D.B.), 6°CW.B. (42.8°F D.B.) ELECTRICAL DATA (50Hz) MODEL / ITEMCS-W43BD2P/CU-W43BBP8 Condition by JIS B 8615 VoltsV380400415 Phase3N3N3N Input PowerkWCool4.494.494.49 Heat4.664.664.66 Running CurrentACool7.87.87.8 Heat8.08.08.0 Starting CurrentA585858 Power Factor%Cool878380 Heat898481 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. PanasonicPower sourceAC, 3N~380V, 400V, 415V 50Hz 13
4 SPECIFICATION (COOLING ONLY TYPE) 4.1. CS-W24BD2P / CU-V24BBP5 ITEM / MODELIndoor UnitOutdoor unit Main BodyCS-W24BD2PCU-V24BBP5 Cooling CapacitykW6.30 (BTU/h)(21,500) Refrigerant Charge-lessm30 Standard Air Volume for High Speedm3/minHi 18- cfmHi 636 External Static PressuremmAqHi 10- PaHi 98 Air InletBackward SuctionBack sided Suction Air OutletFront blow-outFront blow-out Outside Dimension (H x W x D)mm290 x (1000 + 100) x 500900 x 900 x 320 Net Weightkg (lbs)43 (95)80 (176) Piping ConnectionRefrigerantGasmm (inch)O.D Ø 15.88 (5/8) Flared Type Liquidmm (inch)O.D Ø 6.35 (1/4) Flared Type DrainmmFemale screw RC1 (PT1)I.DØ 20 x 1 CompressorType, Number of Set-Hermetic-1 (Rotary), 1 Starting Method-Direct on-line starting MotorType-2-pole single phase induction motor Rated OutputkW-1.9 FanType, Number of SetSirocco fanProp. fan Air Volume ControlThree-Step and Auto mode- (Remote Control) MotorType4-pole single phase induction motor6-pole single phase induction motor Rated OutputkW0.150.05 Air-heat ExchangerLouvre-fin typeX-Louvre-fintype Refrigerant ControlCapillary tubeCapillary tube Refrigerant Oil (Charged)L-MEL56 (1.3) Refrigerant (Charged)kg (oz)-R407C 2.8 (99) Running AdjustmentControl SwitchWired RemoteControl- Room Temperatu reThermosta t (Main Body)- Safety DevicesInternal protector for compressor, Internal thermostat for F.M, Crankcase heater, High pressure switch, Current Transformer Noise LeveldB (A)Hi 40 Lo 3652 Power level dBHi 55 Lo 5165 1. Coolin g capacities are based on indoor temp. 27°C D.B (80.6°F D.B.), 19.0°CW.B.(66.2°F W.B.) and outdoor air temp. 35°C D.B. (95°F D.B.), 24°CW.B.(75.2°F W.B.) ELECTRICAL DATA (50Hz) MODEL / ITEMCS-W24BD2P/CU-V24BBP5 Condition by JIS B 8615 VoltsV220230240 PhaseSingleSingleSingle Input PowerkWCool2.562.562.56 Running CurrentACool11.7011.2010.80 Starting CurrentA646668 Power Factor%Cool999999 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. PanasonicPower sourceAC, 1~220V, 230V, 240V 50Hz 14
4.2. CS-W24BD2P / CU-V24BBP8 ITEM / MODELIndoor UnitOutdoor unit Main BodyCS-W24BD2PCU-V24BBP8 Cooling CapacitykW6.30 (BTU/h)(21,500) Refrigerant Charge-lessm30 Standard Air Volume for High Speedm3/minHi 18- cfmHi 636 External Static PressuremmAqHi 10- PaHi 98 Air InletBackward SuctionBack sided Suction Air OutletFront blow-outFront blow-out Outside Dimension (H x W x D)mm290 x (1000 + 100) x 500900 x 900 x 320 Net Weightkg (lbs)43 (108)90 (198) Piping ConnectionRefrigerantGasmm (inch)O.D Ø 15.88 (5/8) Flared Type Liquidmm (inch)O.D Ø 6.35 (1/4) Flared Type DrainmmFemale screw RC1 (PT1)I.DØ 20 x 1 CompressorType, Number of Set-Hermetic-1 (Rotary), 1 Starting Method-Direct on-line starting MotorType-2-pole 3-phase induction motor Rated OutputkW-1.9 FanType, Number of SetSirocco fanProp. fan Air Volume ControlThree-Step and Auto mode- (Remote Control) MotorType4-pole single phase induction motor6-pole single phase induction motor Rated OutputkW0.150.05 Air-heat ExchangerLouvre-fin typeX-Louvre-fintype Refrigerant ControlCapillary tubeCapillary tube Refrigerant Oil (Charged)L-MEL56 (1.3) Refrigerant (Charged)kg (oz)-R407C 2.8 (99) Running AdjustmentControl SwitchWired RemoteControl- Room Temperatu reThermosta t (Main Body)- Safety DevicesInternal protector for compressor, Internal thermostat for F.M, Crankcase heater, High pressure switch, Current Transformer Noise LeveldB (A)Hi 40 Lo 3652 Power level dBHi 55 Lo 5165 1. Coolin g capacities are based on indoor temp. 27°C D.B. (80.6°F D.B.), 19.0°CW.B.(66.2°F W.B.) and outdoor air temp. 35°C D.B. (95°F D.B.), 24°CW.B.(75.2°F W.B.) ELECTRICAL DATA (50Hz) MODEL / ITEMCS-W24BD2P/CU-V24BBP8 Condition by JIS B 8615 VoltsV380400415 Phase3N3N4N Input PowerkWCool2.422.422.42 Running CurrentACool4.104.104.10 Starting CurrentA272829 Power Factor%Cool908582 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. PanasonicPower sourceAC, 3N~380V, 400V, 415V 50Hz 15
4.3. CS-W28BD2P / CU-V28BBP5 ITEM / MODELIndoor UnitOutdoor unit Main BodyCS-W28BD2PCU-V28BBP5 Cooling CapacitykW7.10 (BTU/h)(24,200) Refrigerant Charge-lessm30 Standard Air Volume for High Speedm3/minHi 20- cfmHi 706 External Static PressuremmAqHi 10- PaHi 98 Air InletBackward SuctionBack sided Suction Air OutletFront blow-outFront blow-out Outside Dimension (H x W x D)mm290 x (1000 + 100) x 500900 x 900 x 320 Net Weightkg (lbs)43 (95)81 (179) Piping ConnectionRefrigerantGasmm (inch)O.D Ø 15.88 (5/8) Flared Type Liquidmm (inch)O.D Ø 9.52 (3/8) Flared Type DrainmmFemale screw RC1 (PT1)I.DØ 20 x 1 CompressorType, Number of Set-Hermetic-1 (Rotary), 1 Starting Method-Direct on-line starting MotorType-2-pole single phase induction motor Rated OutputkW-2.0 FanType, Number of SetSirocco fanProp. fan Air Volume ControlThree-Step and Auto mode- (Remote Control) MotorType4-pole single phase induction motor6-pole single phase induction motor Rated OutputkW0.150.05 Air-heat ExchangerLouvre-fin typeX-Louvre-fintype Refrigerant ControlCapillary tubeCapillary tube Refrigerant Oil (Charged)L-MEL56 (1.3) Refrigerant (Charged)kg (oz)-R407C 3.3 (116) Running AdjustmentControl SwitchWired RemoteControl- Room Temperatu reThermosta t (Main Body)- Safety DevicesInternal protector for compressor, Internal thermostat for F.M, Crankcase heater, High pressure switch, Current Transformer Noise LeveldB (A)Hi 41 Lo 3756 Power level dBHi 56 Lo 5266 1. Coolin g capacities are based on indoor temp. 27°C D.B (80.6°F D.B.), 19.0°CW.B.(66.2°F W.B.) and outdoor air temp. 35°C D.B. (95°F D.B.), 24°CW.B.(75.2°F W.B.) ELECTRICAL DATA (50Hz) MODEL / ITEMCS-W28BD2P/CU-V28BBP5 Condition by JIS B 8615 VoltsV220230240 PhaseSingleSingleSingle Input PowerkWCool2.862.862.86 Running CurrentACool13.112.512.5 Starting CurrentA687072 Power Factor%Cool999995 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. PanasonicPower sourceAC, 1~220V, 230V, 240V 50Hz 16
4.4. CS-W28BD2P / CU-V28BBP8 ITEM / MODELIndoor UnitOutdoor unit Main BodyCS-W28BD2PCU-V28BBP8 Cooling CapacitykW7.10 (BTU/h)(24,200) Refrigerant Charge-lessm30 Standard Air Volume for High Speedm3/minHi 20- cfmHi 706 External Static PressuremmAqHi 10- PaHi 98 Air InletBackward SuctionBack sided Suction Air OutletFront blow-outFront blow-out Outside Dimension (H x W x D)mm290 x (1000 + 100) x 500900 x 900 x 320 Net Weightkg (lbs)43 (95)81 (179) Piping ConnectionRefrigerantGasmm (inch)O.D Ø 15.88 (5/8) Flared Type Liquidmm (inch)O.D Ø 9.52 (3/8) Flared Type DrainmmFemale screw RC1 (PT1)I.DØ 20 x 1 CompressorType, Number of Set-Hermetic-1 (Scroll), 1 Starting Method-Direct on-line starting MotorType-2-pole 3 phase induction motor Rated OutputkW-2.0 FanType, Number of SetSirocco fanProp. fan Air Volume ControlThree-Step and Auto mode- (Remote Control) MotorType4-pole single phase induction motor6-pole single phase induction motor Rated OutputkW0.150.05 Air-heat ExchangerLouvre-fin typeX-Louvre-fintype Refrigerant ControlCapillary tubeCapillary tube Refrigerant Oil (Charged)L-MEL56 (1.3) Refrigerant (Charged)kg (oz)-R407C 3.3 (116) Running AdjustmentControl SwitchWired RemoteControl- Room Temperatu reThermosta t (Main Body)- Safety DevicesInternal protector for compressor, Internal thermostat for F.M, Crankcase heater, High pressure switch, Current Transformer Noise LeveldB (A)Hi 41 Lo 3753 Power level dBHi 56 Lo 5266 1. Coolin g capacities are based on indoor temp. 27°C D.B. (80.6°F D.B.), 19.0°CW.B.(66.2°F W.B.) and outdoor air temp. 35°C D.B. (95°F D.B.), 24°CW.B.(75.2°F W.B.) ELECTRICAL DATA (50Hz) MODEL / ITEMCS-W28BD2P/CU-V28BBP8 Condition by JIS B 8615 VoltsV380400415 Phase3N3N4N Input PowerkWCool2.722.722.72 Running CurrentACool4.604.604.60 Starting CurrentA282930 Power Factor%Cool908582 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. PanasonicPower sourceAC, 3N~380V, 400V, 415V 50Hz 17
4.5. CS-W34BD2P / CU-V34BBP8 ITEM / MODELIndoor UnitOutdoor unit Main BodyCS-W34BD2PCU-V34BBP8 Cooling CapacitykW10.00 (BTU/h)(34,100) Refrigerant Charge-lessm30 Standard Air Volume for High Speedm3/minHi 33- cfmHi 1162 External Static PressuremmAqHi 15- PaHi 147 Air InletBackward SuctionBack sided Suction Air OutletFront blow-outFront blow-out Outside Dimension (H x W x D)mm360 x (1000 + 100) x 6501220 x 900 x 320 Net Weightkg (lbs)56 (123)95 (209) Piping ConnectionRefrigerantGasmm (inch)O.D Ø 19.05 (3/4) Flared Type Liquidmm (inch)O.D Ø 9.52 (3/8) Flared Type DrainmmFemale screw RC1 (PT1)I.DØ 20 x 1 CompressorType, Number of Set-Hermetic-1 (Scroll), 1 Starting Method-Direct on-line starting MotorType-2-pole 3 phase induction motor Rated OutputkW-3.0 FanType, Number of SetSirocco fanProp. fan Air Volume ControlThree-Step and Auto mode- (Remote Control) MotorType4-pole single phase induction motor6-pole single phase induction motor Rated OutputkW0.250.05 x 2 Air-heat ExchangerLouvre-fin typeX-Louvre-fintype Refrigerant ControlCapillary tubeCapillary tube Refrigerant Oil (Charged)L-MMMAPOE (1.3) Refrigerant (Charged)kg (oz)-R407C 3.2 (113) Running AdjustmentControl SwitchWired RemoteControl- Room Temperatu reThermosta t (Main Body)- Safety DevicesInternal protector for compressor, Internal thermostat for F.M, Crankcase heater, High pressure switch, Current Transformer Noise LeveldB (A)Hi 47 Lo 4356 Power level dBHi 62 Lo 5869 1. Coolin g capacities are based on indoor temp. 27°C D.B. (80.6°F D.B.), 19.0°CW.B.(66.2°F W.B.) and outdoor air temp. 35°C D.B. (95°F D.B.), 24°CW.B.(75.2°F W.B.) ELECTRICAL DATA (50Hz) MODEL / ITEMCS-W34BD2P/CU-V34BBP8 Condition by JIS B 8615 VoltsV380400415 Phase3N3N3N Input PowerkWCool3.883.883.88 Running CurrentACool6.26.26.2 Starting CurrentA394142 Power Factor%Cool959087 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. PanasonicPower sourceAC, 3N~380V, 400V, 415V 50Hz 18
4.6. CS-W43BD2P / CU-V43BBP8 ITEM / MODELIndoor UnitOutdoor unit Main BodyCS-W43BD2PCU-V43BBP8 Cooling CapacitykW12.50 (BTU/h)(42,600) Refrigerant Charge-lessm30 Standard Air Volume for High Speedm3/minHi 36- cfmHi 1271 External Static PressuremmAqHi 15- PaHi 147 Air InletBackward SuctionBack sided Suction Air OutletFront blow-outFront blow-out Outside Dimension (H x W x D)mm360 x (1000 + 100) x 6501220 x 1100 x 320 Net Weightkg (lbs)58 (128)111 (245) Piping ConnectionRefrigerantGasmm (inch)O.D Ø 19.05 (3/4) Flared Type Liquidmm (inch)O.D Ø 9.52 (3/8) Flared Type DrainmmFemale screw RC1 (PT1)I.DØ 20 x 1 CompressorType, Number of Set-Hermetic-1 (Scroll), 1 Starting Method-Direct on-line starting MotorType-2-pole 3-phase induction motor Rated OutputkW-3.75 FanType, Number of SetSirocco fanProp. fan Air Volume ControlThree-Step and Auto mode- (Remote Control) MotorType4-pole single phase induction motor6-pole single phase induction motor Rated OutputkW0.350.055 x 2 Air-heat ExchangerLouvre-fin typeX-Louvre-fintype Refrigerant ControlCapillary tubeCapillary tube Refrigerant Oil (Charged)L-MMMAPOE (2.0) Refrigerant (Charged)kg (oz)-R407C 3.60 (127) Running AdjustmentControl SwitchWired RemoteControl- Room Temperatu reThermosta t (Main Body)- Safety DevicesInternal protector for compressor, Internal thermostat for F.M, Crankcase heater, High pressure switch, Current Transformer Noise LeveldB (A)Hi 48 Lo 4456 Power level dBHi 63 Lo 5969 1. Coolin g capacities are based on indoor temp. 27°C D.B. (80.6°F D.B.), 19.0°CW.B.(66.2°F W.B.) and outdoor air temp. 35°C D.B. (95°F D.B.), 24°CW.B.(75.2°F W.B.) ELECTRICAL DATA (50Hz) MODEL / ITEMCS-W43BD2P/CU-V43BBP8 Condition by JIS B 8615 VoltsV380400415 Phase3N3N3N Input PowerkWCool4.494.494.49 Running CurrentACool787.87.8 Starting CurrentA585858 Power Factor%Cool878380 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. PanasonicPower sourceAC, 3N~380V, 400V, 415V 50Hz 19
5 TECHNICAL DRAWING CS-W24BD2P, CS-W28BD2P OUTSIDE DIMENSIONS 20