Home
>
Panasonic
>
Air Conditioner
>
Panasonic Cs C9gkzw Cs C12gkzw Cu C9gkzw Cu C12gkzw Repair Manual
Panasonic Cs C9gkzw Cs C12gkzw Cu C9gkzw Cu C12gkzw Repair Manual
Have a look at the manual Panasonic Cs C9gkzw Cs C12gkzw Cu C9gkzw Cu C12gkzw Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
21 11.2. Indoor Unit 11.2.1. How To Fix Installation Plate The mounting wall is strong and solid enough to prevent it from the vibration. The centre of installation plate should be at more than 450 mm at right and left of the wall. The distance from installation plate edge to ceiling should more than 67 mm. From installation plate left edge to units left side is 74 mm. From installation plate right edge to units right is 94 mm. 1. Mount the installation plate on the wall with 5 screws or more. (If mounting the unit on the concrete wall, consider using anchor bolts.) • Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a level gauge. 2. Drill the piping plate hole with ø70 mm hole-core drill. • Line according to the left and right side edge of the instal- lation plate. The meeting point of the extended line is the centre of the hole. Another method is by putting measur- ing tape at position as shown in the diagram above. The hole centre is obtained by measuring the distance namely 150 mm and 125 mm for left and right hole respectively. • Drill the piping hole at either the right or the left and the hole should be slightly slanted to the outdoor side. 11.2.2. To Drill A Hole In The Wall And Install A Sleeve Of Piping 1. Insert the piping sleeve to the hole. 2. Fix the bushing to the sleeve. 3. Cut the sleeve until it extrudes about 15 mm from the wall. 4. Finish by sealing the sleeve with putty or caulking compound at the final stage. 11.2.3. Indoor Unit Installation For the right rear piping For the right and right bottom piping : : :For left side piping, piping connection for liquid should be about 15 mm from this line. For left side piping, piping connection for gas should be about 45 mm from this line. For left side piping, piping connection cable should be about 800 mm from this line. Caution When the wall is hollow, please be sure to use the sleeve for tube ass’y to prevent dangers caused by mice biting the connecting cable.
22 For the embedded piping Pull out the piping and drain hose How to keep the coverInsert the connecting cable Install the Indoor unit Secure the Indoor Unit (This can be used for left rear piping & left bottom piping also.)
23 • How to pull the piping and drain hose out, in case of the embedded piping. • In case of left piping how to insert the connecting cable and drain hose. 11.2.4. Connect The Cable To The Indoor Unit 1. The inside and outside connecting cable can be connected without removing the front grille. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 × 1.5mm 2 flexible cord, type designation 245 IEC 57 or heavier cord. • Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively. • Earth lead wire shall be longer than the other lead wires as shown in the figure for the electrical safety in case of the slipping out of the cord from the anchorage.• Secure the cable onto the control board with the holder (clamper). 11.3. Outdoor Unit 11.3.1. Install The Outdoor Unit • After selecting the best location, start installation according to Indoor/Outdoor Unit Installation Diagram. 1. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). 2. When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails. 11.3.2. Connecting The Piping Connecting The Piping To Indoor Unit Please make flare after inserting flare nut (locate at joint portion of tube assembly) onto the copper pipe. (In case of using long piping) Connect the piping • Align the center of piping and sufficiently tighten the flare nut with fingers. • Further tighten the flare nut with torque wrench in specified torque as stated in the table. Model A B C D CU-C9GKZ 474 87 18.5 261 CU-C12GKZ 570 105 18.5 320
24 Connecting The Piping To Outdoor Unit Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut (locate at valve) onto the copper pipe. Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table.CUTTING AND FLARING THE PIPING 1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe. 3. Please make flare after inserting the flare nut onto the copper pipes. 11.3.3. Air Purging Of The Pipings And Indoor Unit The remaining air in the Refrigeration cycle which contains moisture may cause malfunction on the compressor. 1. Remove the caps from the 2-way and 3-way valves. 2. Remove the service-port cap from the 3-way valves. 3. To open the valve, turn the valve stem of 2-way valve counter-clockwise approx. 90° and hold it there for ten seconds, then close it. 4. Check gas-leakage of the connecting portion of the pipings. * For the left pipings, refer to item 4(A). Model Piping size (Torque) Gas Liquid CU-C9GKZ 3/8” [42 N•m] 1/4” [18 N•m] CU-C12GKZ 1/2” [55 N•m] 1/4” [18 N•m]
25 4(A). Checking gas leakage for the left piping 11.3.4. Connect The Cable To The Outdoor Unit 1. Remove the control board cover from the unit by loosening the screw. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 × 1.5 mm 2 flexible cord, type designation 245 IEC 57 or heavier cord. 3. Secure the cable onto the control board with the holder (clamper). 4. Cable connection to the power supply (220-240V, 50Hz) through knife switch (Disconnecting means). • Connect the approved polychloroprene sheathed power supply cable (1.5 mm 2), type designation 245 IEC 57 or heavier cord to the terminal board, and connect the other end of the cable to knife switch (Disconnecting means).Note: Knife switch (Disconnecting means) should have more than 3.5 mm contact gap. • Secure the cable onto the control board with the holder (clamper). 11.3.5. Pipe Insulation 1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. 2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with thickness 6mm or above. (1) * Connect the manifold gauge to the service port of 3-way valve. * Measure the pressure. (2) * Keep it for 5-10 minutes. * Ensure that the pressure indicated on the gauge is the same as that of measured during the first time.
26 12 Operation and Control 12.1. Cooling Operation • Cooling operation can be set using remote control. • This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control. • The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C. • During cooling operation, the compressor will stop running and restart as shown in below figure. 12.1.1. Cooling Operation Time Diagram
27 12.2. Soft Dry Operation • Soft Dry operation can be set using remote control. • Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room. • This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control. • When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be turned “OFF” for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the setting temperature as shown in below figure. • However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the indoor unit will start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON” point. 12.2.1. Soft Dry Operation Time Diagram
28 12.3. Automatic Operation • Automatic operation can be set using remote control. • This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature. • After judged the temperature, the operation mode is determined by referring to the below standard. • Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting temperature as shown in below table. • The setting temperature for all the operations can be changed one level up or one level down from the standard temperature as shown in below table by pressing on the temperature up or temperature down button at remote control. • The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open the circuit of JX1 at indoor electronic controller.
29 12.4. Operation Control 12.4.1. Restart Control (Time Delay Safety Control) •When the thermo-off temperature (temperature which compressor stops to operate) is reached during:- - Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation. - Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation. • If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation stop, although the unit is turn on again within the period. •This phenomenon is to balance the pressure inside the refrigerant cycle. 12.4.2. 7 Minutes Time Save Control •The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the compressor ON temperature (A) and compressor OFF temperature (B) during the period. • This phenomenon is to reduce the built up humidity inside a room. 12.4.3. 60 Seconds Forced Operation •Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the remote control is permitted. •The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and return back to the outdoor unit. 12.4.4. Starting current Control •When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to operate at 1.6 second later. •The reason of the difference is to reduce the starting current flow.
30 12.4.5. Freeze Preventive Control • To protect indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form return to compressor. • This control will activate when the temperature of indoor heat exchanger falls below 2°C continuously for more than 4 minutes. • The current fan speed will change to freeze prevention speed after 70 seconds compressor on. When indoor pipe temperature reaches certain temperature for 5 sec. the speed will be increased as in below figure. • Compressor will turn off when indoor temperature falls below 2°C for more than 4 minutes. It will restart again when indoor heat exchanger temperature rises to 10°C. • Restart control (Time Delay Safety Control) will be applied in this control. 12.4.6. Compressor Reverse Rotation Protection Control • If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor heat exchanger is 2.5°C or less for continuous 2 minutes, compressor will stop and restart automatically. • Time Delay Safety Control is activated before the compressor restart. •This is to prevent compressor from rotate reversely when there is an instantaneous power failure.