Home > Panasonic > Air Conditioner > Panasonic Cs C9dkzw Cu 2c18dkh Cu 3c20dkh Repair Manual

Panasonic Cs C9dkzw Cu 2c18dkh Cu 3c20dkh Repair Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Cs C9dkzw Cu 2c18dkh Cu 3c20dkh Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							 1. The inside and outside connecting cable can be connected
    without removing the front grille.
     2. Connecting cable between indoor unit and outdoor unit
    shall be approved polychloroprene sheathed 4 × 1.5 mm
    2
    flexible cord, typedesignation 245 IEC 57 or heavier cord.
     • Ensure the color of wires of outdoor unit and the
    terminal Nos. are the same to the indoor’s respectively.
     • Earth lead wire shall be longer than the other lead wires
    as shown in the figure forthe electrical safetyin case of
    the slipping out of the cord from the anchorage.
     • Secure the cable onto the control board with the holder
    (clamper).
    INSTALLATION OFSUPER ALLERU-BUSTER FILTER
     1. Open the front panel.
     2. Remove the air filters.
     3. Remove Supersonic air purifying device.
     4. Open the Supersonicair purifying device frame.
     5. Insert the super alleru-buster filter and close the Supersonic
    air purifying device frame as shown in illustration at right.
    10.5.5. CONNECT THE CABLE TO THE INDOOR UNIT
    41
    CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH 
    						
    							HOW TO TAKE OUT FRONT GRILLE
    Please follow the steps below to take out front grille if
    necessary such as when servicing.
     1. Open the intake grille and remove the screw at the front of
    the front grille.
     2. Set the vertical airflow direction louver to the horizontal
    position.
     3. Slide down the 2 caps on the front grille as shown in the
    illustration below, and then remove the 2 mounting screws.
     4. Pull the lower section of the front grille towards you to
    remove the front grille.
    When reinstalling the front grille, first set the vertical
    airflow direction louver to the horizontal position and
    then carry out above steps 2 -3 in the reverse order.
    AUTO SWITCH OPERATION
    The below operations will be performed by pressing the
    “AUTO” switch.
     1. AUTO OPERATION MODE
    The Auto operation will be activated immediately once the
    Auto Switch is pressed.
     2. TEST RUN OPERATION (FOR PUMP DOWN/SERV ICING
    PURPOSE)
    The Test Run operation will be activated if the Auto Switch
    is pressed continuously for more than 5 sec. A “pep” sound
    will occur at the fifth sec., inorder to identifythe starting of
    Test Run operation
     3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
    The ON/OFF of Remote Controller receiving sound can be
    change over by the following steps:
     a. Release the Auto Switch after Test Run operation is
    activated.
     b. Then, within 20 sec. after (a), press Auto Switch for
    more than 5 sec.
    A “beep” “beep” sound will occur at the fifth sec., then
    release the Auto switch.
     c. Within 20 sec. after (b), press Auto Switch again.
    Everytime Auto Switch is pressed(within 20 sec.
    interval), remote controller receiving sound status will be
    reversed between ON and OFF.
    Long “beep” sound indicates that remote controller
    receiving sound is OFF.
    Short “beep” sound indicates that remote controller
    receiving sound is ON.
    42
    CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH 
    						
    							10.6. Outdoor unit
    10.6.2. INSTALL THE OUTDOOR UNIT
     • After selecting the best location, start installation according
    to Indoor/Outdoor Unit Installation Diagram.
     1. Fix the unit on concreteor rigid frame firmly and horizontally
    by bolt nut. (ø10 mm).
     2. When installing at roof, please consider strong wind and
    earthquake. Please fasten theinstallation standfirmly with
    bolt or nails.
    10.6.3. CONNECTING THE PIPING
    Connecting The Piping To Indoor Unit
    Please make flare after inserting flare nut (locate at joint portion
    of tube assembly) onto the copper pipe. (In case of using long
    piping)
    Connect the piping
     • Align the center of piping and sufficiently tighten the flare
    nut with fingers.
     • Further tighten the flare nut with torque wrench in specified
    torque as stated in the table.
    Connecting the Piping to Outdoor Unit
     1. Align the center of the piping and sufficiently tighten the
    flare nut with fingers.
     2. Finally, tighten the flare nut with torque wrench until the
    wrench clicks.
     • W hen tightening the flare nut with torque wrench,
    ensure the direction for tightening follows the arrow on
    the wrench.
    MODELPiping size (Torque)
    GasLiquid
    CS-C9DKZW3/8” (42 N.m)1/4” (18 N.m)
    10.6.1. SELECT THE BEST LOCATION
    (Refer to “Select the best location” section)
    CautionThe CU-3C20DKH/C9DKZW have different cooling capacities depending on the connection to A1,A2and/or B on CU-
    3C20DKH individually.
    (Refer to SPECIFICATIONS on CATALOG)
     1. The Cooling Capacity of Indoor Unit connecting “B” on CU-3C20DKH (Called B unit) is different from that of A
    1and A2Units.
     2. A
    1and A2Units share the same compressor, their cooling capacities thus change depending on whether one, the other,
    or both of the units is in use.
     3. Reflect the B or A (A
    1and/or A2) on the Indoor Unit for later reference.
    43
    CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH 
    						
    							CUTTING AND FLARING THE PIPING
     1. Please cut using pipe cutter and then remove the burrs.
     2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
    Turn the piping end down to avoid the metal powder entering the pipe.
     3. Please make flare after inserting the flare nut onto the copper pipes.
    10.6.4. AIR PURGING OF THE PIPING AND INDOOR UNIT
    1) Checking gas leakage
     1. Remove the service-portcap from both3-wayvalves.
     2. Connect the manifold gauge set tothe service port ofLiquid side3-way valve.
     3. Connect the charging cylinder to the manifold gauge set and open the valve of the cylinder.
     4. Open the low pressure side valve of the manifold gauge of approx. 10 seconds and then close.
     5. Check a gas leakage of theconnecting portion of pipings with the gas-leak detector.
    
     1. Measure the pressure.
     2. Keep it for 5-10 minutes.
     • Ensure if the pressure indicated on the gauge is as same as that measured at first time.
    44
    CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH 
    						
    							The air which contains remaining moisture in the refrigeration
    cycle may cause a malfunction on the compressor.
     1. To purge the air, push the pin on the gas side 3-way valve
    for three seconds using with a hexagonal wrench and set it
    free for one minute.
     • Repeat this three times.
     2. To balance the refrigerant, close the low pressure side
    valve on the manifold gauge and release a refrigerant from
    the piping through service port until the gauge indicates
    0.49 ~ 0.294 MPa.
     3. Set theboth 3-wayvalves to open position with the
    hexagonal wrench for the unit operation.
    2) Air purging
    10.6.5. CONNECT THE CABLE TO THE OUTDOOR UNIT
     1. Remove the control board cover from the unit by loosening the screw.
     2. Connecting cable between indoor unit and outdoor unitshall be approved polychloroprenesheathed flexiblecord, type
    designation 245 IEC 57 or heavier cord (4 × 1.5 mm
    2).
    Power supply cord cable use 3 × 1.5 mm
    2flexible cord, typedesignation 245 IEC 57 or heavier cord.
     3. Secure the cable onto the control board with the holder (clamper).
     4. Confirm the SW1 Switchat AUTO position. (CU-3C20DKH)
     5. Attach the control board cover back to the original position with the screw.
    45
    CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH 
    						
    							10.6.6. PIPE INSULATION
    CHECK THEDRAINAGE
     • Open front panel and remove air filters.
    (Drainage checking can be carriedout without removing the
    front grille.)
     • Pour a glass of water into the drain tray-styrofoam.
     • Ensure that water flows out from drain hose of the indoor
    unit.
    EVALUATION OF THEPERFORMANCE
     • Operate the unit at cooling operation mode for fifteen
    minutes or more.
     • Measure the temperature of the intake and discharge air.
     • Ensure the difference between the intake temperature and
    the discharge is more than 8°C.
    CHECK ITEMS
    Is there any gas leakage at flare nut connections?
    Has the heat insulation been carried out at flare nut
    connection?
    Is the connecting cable being fixed to terminal board firmly?
    Is the connecting cable being clamped firmly?
    Is the drainage OK?
    (Refer to “Check the drainage” section)
    Is the earth wire connection properly done?
    Is the indoor unit properly hooked to the installation plate?
    Is the power supplyvoltage complied with rated value?
    Is there any abnormal sound?
    Is the cooling operation normal?
    Is the thermostat operation normal?
    Is the remote control’s LCD operation normal?
    Is the super alleru-buster filter is installed?
     1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap
    the insulated piping end to prevent water from going inside the piping.
     2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM
    with thickness 6 mm or above.
    46
    CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH 
    						
    							11 3-way Valve
    3-way Valve (Liquid Side)3-way Valve (Gas Side)
    WorksShaft PositionService PortShaft PositionService Port
    ShippingClosedClosedClosedClosed
    (With valve cap)(With cap)(With valve cap)(With cap)
    Air purgingClosedOpenClosedOpen
    (Installation and(Clockwise)(Connected manifo ld(Clockwise)(Push-pin)
    Re-installation)gauge w/charging cylinder)
    OperationOpenClosedOpenClosed
    (With valve cap)(With cap)(With valve cap)(With cap)
    Pumping downClosedClosedOpenOpen
    (Transferring)(Clockwise)(With cap)(Counter-clockwise)(Connected manifo ld
    gauge)
    EvacuationOpenOpenOpenOpen
    (Servicing)(Counter-clockwise)(Connected manifo ld
    gauge)(Counter-clockwise)(Connected manifo ld
    gauge)
    Gas chargingOpenOpenOpenOpen
    (Servicing)(Counter-clockwise)(Connected manifo ld
    gauge)(Counter-clockwise)(Connected manifo ld
    gauge)
    Pressure checkOpenOpenOpenOpen
    (Servicing)(Counter-clockwise)(With cap)(Counter-clockwise)(Connected manifo ld
    gauge)
    Gas releasingOpenOpenOpenOpen
    (Servicing)(Counter-clockwise)(Connected manifo ld
    gauge)(Counter-clockwise)(Connected manifo ld
    gauge)
    47
    CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH 
    						
    							11.1. Air purging
    Required tools: Hexagonal wrench, adjustable wrench,
    torque wrenches, wrench to hold the
    joints, gas leak detector, and charging
    set.
     1. Recheck the piping connections.
     2. Open thevalve of the lowpressure side of Manifold
    gauge counter-clockwise for 10 seconds, and then
    close it.
     3. Check for gas leakage.
     • Check the flare connections for gas leakage.
     4. Purge the air from the system.
     • Open the Low pressure side valve of the manifold
    gauge.
     • Press the valve core pin with the hexaganol wrench to
    purge the air for three seconds and then wait for one
    minute.
    Repeat this three times or more.
     5. Balance the refrigerant in the pipings and the indoor
    unit.
     • Close the Low pressure side valve of the manifold
    gauge.
     • Press the valve core pin with the hexaganol wrench to
    release the refrigerant until the gauge indicates.The air in the indoor unit and in the piping must be purged. If air
    remains in the refrigeration pipes, it will affect the compressor,
    reduce the cooling capacity, and could lead to a malfunction.
     6. Use torque wrench CWHAD-9211 to tighten the service port
    nut to a torque of 1.8 kg.cm.
     7. Set both the 3-wayvalves to theopen position.
     8. Mount thevalve stemnuts to the3-wayvalves.
     9. Check for gas leakage.
     • At this time, especially check for gas leakage from both
    the 3-wayvalve’s stem nuts, and from the service port
    caps.
    CautionIf gas leakage is discovered in step 3 above, take the
    following procedures:
     1. Re-tighten the connecting portion with torque
    wrenches.
    If the leakage ceases, continue the works from
    step 4.
     2. Locate and repair the leak. (Gas leak detector)
    Repeat the works from step 1.
    Service port cap
    Be sure, using a torque wrench to tighten the service port nut (after using the service port), so that it prevents the gas leakage from the
    refrigeration cycle.
    Procedure:
    48
    CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH 
    						
    							11.2. Pumping down
     1. Confirm that both the 3-wayvalves are setto the open
    position.
     • Remove the valve stem caps and confirm that the valve
    stems are in the raised position.
     • Be sure to use a hexagonal wrench to operate the valve
    stems.
     2. Operate the unit for 10 to 15 minutes.
     3. Stop operation and wait for 3 minutes, then connect the
    charge set to the serviceport of the3-wayvalves.
     • Connect the charge hose with the push pin to the gas
    side service port.
     4. Air purging of the charge hose.
     • Open the low-pressure valveon the charge set slightly
    to purge air from the charge hose.
     5. Set the Liquid side 3-wayvalve to theclosed position. 6. Operate the air conditioner at the cooling cycle and
    stop it when the gauge indicates 0 kg/cm2G.
     • If the unit cannot be operated at the cooling (weather is
    rather cool), press the Pump Down switch on the Indoor
    unit.
     • So that the unit can be operated.
     7. Immediately set the 3-way valve tothe closed position.
     • Do this quickly so that the gauge ends up indicating 1 to
    3 kg/cm
    2G.
     8. Disconnect the charge set, and mount both the 3-way
    valve’s stemnuts and the service port caps.
     • Use torque wrench CWHAD-9211 to tighten the service
    port nut to a torque of 1.8 N.m.
     • Be sure to check for gas leakage.
    Procedure:
    49
    CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH 
    						
    							(Re-installation)
     1. Remove the capnut from3-wayvalves.
     • Remove the cap nutfrom 3-wayvalves after carefully
    checked whether the piping connection was properly
    and certainly done.
     2. Confirm that thevalve inboth3-wayvalves are set to
    the CLOSED position.
     3. Connect the gas cylinder to the liquid-side (high-
    pressure) 3-wayvalve andthe charge set to the gas
    side (low-pressure) 3-wayvalve.
     • Remove the flare nut from the service port to connect
    the charge set and gas cylinder.
     • Close the valves on the gas cylinder and charge set.
     4. Air purging.
     • Open the valve on the gas cylinder.
     • Open the valve on the charge set, discharge for three
    seconds and wait for one minute. Repeat this three
    times. 5. Check for gas leakage.
     • Check the flare connections for gas leakage.
     6. Discharge the refrigerant.
     • Close the valve on the gas cylinder and discharge the
    refrigerant until the gauge indicates 3 to 5 kg/cm
    2G.
     7. Disconnect the charge set and the gas cylinder.
     8. Mount thevalve stemcap nuts and the flare nuts for
    service port ontothe 3-wayvalves.
     9. Mount the cap nut and service port nut onto the 3-way
    valves.
     • Be sure to use a torque wrench (CWHAD-9211) to
    tighten the service port nut.
     • Be sure to check for gas leakage.
    11.2.1. Re-air purging
    Procedure:
    50
    CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Cs C9dkzw Cu 2c18dkh Cu 3c20dkh Repair Manual