Home
>
Panasonic
>
Air Conditioner
>
Panasonic Air Conditioner Cz 64esmc1U Installation Instructions
Panasonic Air Conditioner Cz 64esmc1U Installation Instructions
Have a look at the manual Panasonic Air Conditioner Cz 64esmc1U Installation Instructions online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
11 5. Mode setting According to function of each system controller, set SW1 as Fig. 7. (1) Central control/Remote control mode z Central control mode System controller is used as central control equipment. Individual setting by remote controller can be inhibitted by system controller. z Remote control mode System controller is used as remote controller. Setting by system controller is inhibitted by other central control equipments. (2) ALL/ZONE mode z ALL mode All indoor units can be controlled by system controller. z ZONE mode Indoor units in one of ZONE 1, 2, 3 or 4 can be controlled by system controller. (3) Function of system controller is 10 types according to combination of central control/remote control mode and ALL/ZONE mode setting as the table 1. (4) Stick the system controller unit label in a conspicuous position. 2 ON OFF34562 ON OFF3456 2 ON OFF34562 ON OFF34561216 2 ON OFF34562 ON OFF3456171832 2 ON OFF34562 ON OFF3456333448 2 ON OFF34562 ON OFF3456495064 Central control modeRemote control mode ALL central controlALL remote control ZONE1 central controlZONE1 remote control ZONE2 central controlZONE2 remote control ZONE3 central controlZONE3 remote control ZONE4 central controlZONE4 remote controlInter-unit control wiring ZONE1 central control address 1-16 ZONE2 central control address 17-32 ZONE3 central control address 33-48 ZONE4 central control address 49-64 Fig. 7 Table 1 Central control Remote control ALL 1. ALL/Central 6. ALL/Remote ZONE1 2. ZONE1/Central 7. ZONE1/Remote ZONE2 3. ZONE2/Central 8. ZONE2/Remote ZONE3 4. ZONE3/Central 9. ZONE3/Remote ZONE4 5. ZONE4/Central 10. ZONE4/Remote $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE
12 6. How to perform zone registration To operate the system controller properly, zone registration is required after nishing the test run (and after setting all indoor unit addresses) using one of the following methods. (a) Zone registration using the remote controller Refer to page 14 (b) Zone registration using the system controller Refer to page 15 (c) Automatic zone registration using the system controller Refer to page 16 For methods (a) and (b), you should make a zone registration table manually before performing the registration as shown on the page 13. For method (c), zone registration is executed automatically, proceeding from small indoor unit address and small central addresses to larger numbers in numerical order. For example: Central address 1 2 3 4 5 6 ZONE-group 1-1 1-2 1-3 1-4 1-5 1-6 Indoor unit address 1-1 1-2 2-1 2-2 2-3 3-1 NOTE 1. An indoor unit address is assigned to each indoor unit during automatic address operation. Each indoor unit address combines an R.C. address and indoor unit number as follows: 1 1 : Indoor unit address (UNIT No.) Indoor unit No. Refrigerant circuit No. (R.C. address) This address is displayed on remote controller for UNIT No. when the UNIT button is pressed. 2. The central address represents the zone and group number. These addressed are assigned in ascending numerical order. $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE
14 (a) Zone registration using the remote controller (Determination of central address) z In this case, after con rming which indoor unit is connected to the remote controller and that the air conditioner in the OFF state, you set the central addresses one at a time. z If the system has no remote controller, connect a remote controller to the system temporarily. Then follow this procedure. NOTE The indoor unit address must already have been set before performing zone registration. If necessary, refer to the Installation Instructions supplied with the outdoor unit. (1) Press the and buttons at the same time of the remote controller for more than 4 seconds. (2) Do not press button. (3) Once in this mode, the UNIT No., CODE No., No. of SET DATA and indications will ash on the display as shown Fig. 8. NOTE In case of group control “ALL” instead of “UNIT No.” will ash on the display. Select the main indoor unit address by pressing the button once. (4) Set CODE No. to 03 using the and ( ) buttons. NOTE The CODE No. 03 must be selected to perform zone registration using the remote controller. (5) Set the Central address which you want to assign to the indoor unit address using the and ( ) buttons according to the zone registration table. (6) Press the button. The CODE No. and Central address changes from ashing to ON state. If you make mistake, then press the button and reset the central address. (7) Press the button to nish zone registration. Fig. 8 For example, in this case Indoor unit address: 1-8 Central address : 17 (ZONE 2, GROUP 1) Fig. 9 $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE
15 (b) Zone registration using the system controller z In this case, you set all Central addresses by system controller at once manually. (1) Press the and buttons at the same time for more than 4 seconds. and CODE No. C1 will ash. (2) After con rming that CODE No. C1 is displayed, press the button. Once in this mode, a change takes place as Fig. 10. (3) Select the zone and group No. which you want to set with and (GROUP) buttons. If already set, press the buttons. (4) Set the unit No. (Indoor unit address) with and buttons, according to the zone registration table. R.C. No. ..................... button Indoor unit No. ........... button (5) Press the button. GROUP No. turns ON and UNIT No. (Indoor unit address) changes from ashing to ON state. UNIT No. is registered to selected ZONE No. and GROUP No. If you make mistake, then press the button and reselect the ZONE, GROUP and UNIT No. (6) Register the other UNIT No. in the same way by following the steps (3) to (5). (7) Finally, complete the registration by pressing the button. ashes for a few minutes, then OFF. If no data is registered no number is displayed. Selected group No. if no data is registered. If data is registered the unit No. is displayed. For example, in the case at left Zone 3, group No. 7 Unit No. (indoor unit address) 2-8 Unit No. 2-8 is registered to zone 3-group 7.Fig. 10 Fig. 11 $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE
16 (c) Automatic zone registration using the system controller (1) Press the and buttons at the same time for more than 4 seconds. and CODE No. C1 will ash. (2) Select CODE. No. C2 by pressing and ( ) button and press the button. C2 changes from ashing to ON state and automatic zone registration will start. (3) Registered GROUP No. will be disappeared all. (4) Central address will be assigned from small indoor unit address to large one in numerical order automatically. Finishing automatic zone registration, changes from ashing to OFF. (5) If the error is happened, the “CHECK” starts ashing and zone registration nishes at this time. Press the button. (6) Finally, complete automatic zone registration mode by pressing the button. ashes for a few minutes, then OFF. Fig. 12 $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE
17 7. How to check overlapping of central address no. (1) Press the and buttons at the same time for more than 4 seconds. and CODE No. C1 will ash. (2) Select CODE. No. C3 by pressing , ( ) button and press the button. C3 changes from ashing to ON state and will ash. Then auto. overlap checking will start. (3) If C3 changes from ON to ashing and stops ashing and disappears, there is no overlapping. Then nally, complete the auto overlap checking mode by pressing the button. (4) If some of GROUP No., ZONE No. and UNIT No. ash, you should try again the zone registration. ① Select CODE No. C1 by pressing , ( ) button and press the button. ② Select the ashing GROUP No. with ZONE and GROUP button. Then press the button and reselect the ZONE, GROUP and UNIT No. ③ Then nally, complete the auto. overlap checking mode by pressing the button. Fig. 13 $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE
18 8. Memory back up switch Check the back up switch is ON for back side of system controller PCB. ON OFF 9. Test run (1) Power on for all indoor units. Next, power on for system controller. will ash, checking the indoor unit address automatically. (2) If group No. displayed on system controller is not same as indoor unit No.* which is connected, see Fig. 7 and setting again. *In case of group control, main unit No. only. Back up switch Back up battery $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE