    Have a look at the manual Panasonic Air Conditioner Cz 64esmc1U Installation Instructions online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							11
    5. Mode setting
    According to function of each system controller, set 
    SW1 as Fig. 7.
    (1) Central control/Remote control mode
    z Central control mode
      System controller is used as central control 
    equipment.
      Individual setting by remote controller can be 
    inhibitted by system controller.
    z Remote control mode
      System controller is used as remote controller. 
    Setting by system controller is inhibitted by other 
    central control equipments.
    (2) ALL/ZONE  mode
    z ALL mode
      All indoor units can be controlled by system 
    controller.
    z ZONE mode
      Indoor units in one of ZONE 1, 2, 3 or 4 can be 
    controlled by system controller.
    (3) Function of system controller is 10 types according 
    to combination of central control/remote control 
    mode and ALL/ZONE mode setting as the table 1.
    (4) Stick the system controller unit label in a 
    conspicuous position.
    2
    ON
    OFF34562
    ON
    OFF3456
    2
    ON
    OFF34562
    ON
    OFF34561216
    2
    ON
    OFF34562
    ON
    OFF3456171832
    2
    ON
    OFF34562
    ON
    OFF3456333448
    2
    ON
    OFF34562
    ON
    OFF3456495064
    Central control 
    modeRemote control 
    mode
    ALL
    central controlALL
    remote control
    ZONE1
    central controlZONE1
    remote control
    ZONE2
    central controlZONE2
    remote control
    ZONE3
    central controlZONE3
    remote control
    ZONE4
    central controlZONE4
    remote controlInter-unit control wiring
    ZONE1
    central control 
    address 1-16
    ZONE2
    central control 
    address 17-32
    ZONE3
    central control 
    address 33-48
    ZONE4
    central control 
    address 49-64
    Fig. 7
    Table 1
    Central control Remote control
    ALL 1. ALL/Central 6. ALL/Remote
    ZONE1 2. ZONE1/Central 7. ZONE1/Remote
    ZONE2 3. ZONE2/Central 8. ZONE2/Remote
    ZONE3 4. ZONE3/Central 9. ZONE3/Remote
    ZONE4 5. ZONE4/Central 10. ZONE4/Remote
    $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE 
    						
    							12
    6.  How to perform zone registration
    To operate the system controller properly, zone registration is required after 
     nishing the test run (and after setting all indoor unit addresses) using one of the 
    following methods.
    (a) Zone registration using the remote controller  
    Refer to page 14
    (b) Zone registration using the system controller 
    Refer to page 15
    (c) Automatic zone registration using the system controller  
    Refer to page 16
    For methods (a) and (b), you should make a zone registration table manually 
    before performing the registration as shown on the page 13.
    For method (c), zone registration is executed automatically, proceeding from 
    small indoor unit address and small central addresses to larger numbers in 
    numerical order. For example:
    Central address  1 2 3 4 5 6
    ZONE-group 1-1 1-2 1-3 1-4 1-5 1-6
    Indoor unit address 1-1 1-2 2-1 2-2 2-3 3-1
    NOTE
    1.  An indoor unit address is assigned to each indoor unit during automatic 
    address operation. Each indoor unit address combines an R.C. address and 
    indoor unit number as follows:
    1    1  : Indoor unit address (UNIT No.) 
      Indoor unit No.
      Refrigerant circuit No. (R.C. address)
      This address is displayed on remote controller for UNIT No. when the UNIT 
    button is pressed.
    2.  The central address represents the zone and group number. These 
    addressed are assigned in ascending numerical order.
    $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE 
    						
    							13
    
    						
    							14
    (a) Zone registration using the remote controller 
      (Determination of central address)
    z In this case, after con rming which indoor unit is connected to the 
    remote controller and that the air conditioner in the OFF state, you 
    set the central addresses one at a time.
    z If the system has no remote controller, connect a remote controller 
    to the system temporarily. Then follow this procedure.
    NOTE
    The indoor unit address must already have been set before performing 
    zone registration. If necessary, refer to the Installation Instructions 
    supplied with the outdoor unit.
    (1) Press  the 
     and  buttons at the same time of the remote 
    controller for more than 4 seconds.
    (2) Do not press 
     button.
    (3) Once in this mode, the UNIT No., CODE No., No. of SET DATA and 
     indications will  ash on the display as shown Fig. 8.
    NOTE
    In case of group control “ALL” instead of “UNIT No.” will  ash on the 
    display. Select the main indoor unit address by pressing the 
     
    button once.
    (4) Set CODE No. to 03 using the 
     and  (  ) buttons.
    NOTE
    The CODE No. 03 must be selected to perform zone registration using 
    the remote controller.
    (5) Set the Central address which you want to assign to the indoor unit 
    address using the 
     and  (  ) buttons according to the zone 
    registration table.
    (6) Press  the 
     button. The CODE No. and Central address changes 
    from  ashing to ON state. If you make mistake, then press the 
     
    button and reset the central address.
    (7) Press  the 
     button to  nish zone registration.
    Fig. 8
    For example, in this case 
    Indoor unit address:  1-8
    Central address :  17 (ZONE 2, GROUP 1)
    Fig. 9
    $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE 
    						
    							15
    (b) Zone registration using the system controller
    z In this case, you set all Central addresses by 
    system controller at once manually.
    (1) Press  the 
     and  buttons at the same time 
    for more than 4 seconds. 
     
     and CODE No. C1 will  ash.
    (2) After con rming that CODE No. C1 is displayed, 
    press the 
     button. Once in this mode, a change 
    takes place as Fig. 10.
    (3) Select the zone and group No. which you want to 
    set with 
     and  (GROUP) buttons.
      If already set, press the 
     buttons.
    (4) Set the unit No. (Indoor unit address) with 
     and 
     buttons, according to the zone registration table.
    R.C. No.  .....................
     button 
    Indoor unit No.  ...........
     button
    (5) Press  the 
     button.
      GROUP No. turns ON and UNIT No. (Indoor unit 
    address) changes from  ashing to ON state. UNIT 
    No. is registered to selected ZONE No. and GROUP 
    No.
      If you make mistake, then press the 
     button and 
    reselect the ZONE, GROUP and UNIT No.
    (6) Register the other UNIT No. in the same way by 
    following the steps (3) to (5).
    (7) Finally, complete the registration by pressing the 
     button.
     
      ashes for a few minutes, then OFF.
    If no data is 
    registered 
    no number 
    is displayed.
    Selected 
    group No. if 
    no data is 
    registered.
    If data is 
    registered 
    the unit No. 
    is displayed.
    For example, in the case at left
    Zone 3, group No. 7 
    Unit No. (indoor unit address) 2-8
    Unit No. 2-8 is registered to zone 3-group 7.Fig. 10
    Fig. 11
    $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE 
    						
    							16
    (c) Automatic zone registration using the system controller 
    (1) Press  the 
     and  buttons at the same time for more than 4 
    seconds. 
     
     and CODE No. C1 will  ash.
    (2) Select CODE. No. C2 by pressing 
     and  (  ) button and 
    press the 
     button.
      C2 changes from  ashing to ON state and automatic zone 
    registration will start.
    (3) Registered GROUP No. will be disappeared all.
    (4) Central address will be assigned from small indoor unit address to 
    large one in numerical order automatically.
      Finishing automatic zone registration, 
     changes from  ashing 
    to OFF.
    (5) If the error is happened, the “CHECK” starts  ashing and zone 
    registration  nishes at this time. Press the 
     button.
    (6) Finally, complete automatic zone registration mode by pressing the 
     button. 
     
      ashes for a few minutes, then OFF.
    Fig. 12
    $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE 
    						
    							17
    7.  How to check overlapping of central address no.
    (1) Press  the  and  buttons at the same time for more than 4 
    seconds. 
     
     and CODE No. C1 will  ash.
    (2) Select CODE. No. C3 by pressing 
     ,  (  ) button and 
    press the 
     button.
      C3 changes from  ashing to ON state and 
     will  ash. Then 
    auto. overlap checking will start.
    (3) If C3 changes from ON to  ashing and 
     stops  ashing and 
    disappears, there is no overlapping.
      Then  nally, complete the auto overlap checking mode by pressing 
    the 
     button.
    (4) If some of GROUP No., ZONE No. and UNIT No.  ash, you should 
    try again the zone registration.
    ①  Select CODE No. C1 by pressing  ,  (  ) button and 
    press the 
     button.
    ②  Select the  ashing GROUP No. with ZONE and GROUP button. 
    Then press the 
     button and reselect the ZONE, GROUP and 
    UNIT No.
    ③  Then  nally, complete the auto. overlap checking mode by 
    pressing the 
     button.
    Fig. 13
    $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE 
    						
    							18
    8.  Memory back up switch
    Check the back up switch is ON for back side of system controller PCB.
    ON OFF
    9. Test run
    (1) Power on for all indoor units. Next, power on for system controller. 
     
     will  ash, checking the indoor unit address automatically.
    (2) If group No. displayed on system controller is not same as indoor unit No.* 
    which is connected, see Fig. 7 and setting again.
      *In case of group control, main unit No. only.
    Back up switch
    Back up battery
    $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE 
    						
    							19
    $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE 
    						
    							Printed in Japan
    $;&4.$6@FOHJOEE$;&4.$6@FOHJOEE 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Air Conditioner Cz 64esmc1U Installation Instructions