Page 51
DEFINITY Enterprise Communications Server Release 8.2 System Description 555-233-200 Issue 1 April 2000 Site Requirements 41 Environmental Considerations Cross-Connect Field The cross-connect field equipment is located a specified distance from the DEFINITY cabinets and must meet specific requirements. An optional cross-connect field can be installed in the CMC right panel. For new installations, Lucent Technologies personnel may install the cross-connect field. For more details about the...
Page 52
Site Requirements 42 Environmental Considerations DEFINITY Enterprise Communications Server Release 8.2 System Description 555-233-200 Issue 1 April 2000 Altitude and Air Pressure At altitudes above 5,000 feet (1,525 meters), the maximum short-term temperature limit reduces by 1o Fahrenheit for each 1,000 feet (305 meters) of elevation above 5,000 feet (1,525 meters). For example: at sea level, the maximum short-term temperature limit is 120 o F (49o Celsius). At 10,000 feet (3,050 meters), the...
Page 53
DEFINITY Enterprise Communications Server Release 8.2 System Description 555-233-200 Issue 1 April 2000 Site Requirements 43 Environmental Considerations Ta b l e 6 . Te m p e r a t u r e a n d R e l a t i v e H u m i d i t y Room Temperature (Degrees Fahrenheit)Room Temperature (Degrees Celsius) Relative Humidity (%) 40 to 84 4.4 to 28.8 10 to 95 86 30.0 10 to 89 88 31.1 10 to 83 90 32.2 10 to 78 92 33.3 10 to 73 94 34.4 10 to 69 96 35.6 10 to 65 98 36.7 10 to 61 100 37.8 10 to 58 102 38.9...
Page 54
Site Requirements 44 Environmental Considerations DEFINITY Enterprise Communications Server Release 8.2 System Description 555-233-200 Issue 1 April 2000 Air Purity The Compact Modular Cabinet, Single-Carrier and Multi-Carrier Cabinets contain an air filter to reduce particulates flowing through the equipment. Do not install the cabinet where the air may be contaminated by excessive dust, lint, carbon particles, paper fiber contaminants, or metallic contaminants. For example, do not install the...
Page 55
DEFINITY Enterprise Communications Server Release 8.2 System Description 555-233-200 Issue 1 April 2000 Site Requirements 45 Environmental Considerations Small tools with universal motors are generally not a problem when they operate on separate power lines. Motors without commutators generally do not cause interference. Field strengths below 1.0 volt per meter are unlikely to cause interference. Measure weak fields with a tunable meter. Measure field strengths greater than 1.0 volt per meter...
Page 56
Site Requirements 46 Environmental Considerations DEFINITY Enterprise Communications Server Release 8.2 System Description 555-233-200 Issue 1 April 2000 Electromagnetic Compatibility Standards This product complies with and conforms to the following EMC standards (as applicable): nLimits and Methods of Measurements of Radio Interference Characteristics of Information Technology Equipment, EN55022 (CISPR22), 1993 nEN50082-1, European Generic Immunity Standard nFCC Part 15 nAustralia AS3548 NOTE: The...
Page 57
DEFINITY Enterprise Communications Server Release 8.2 System Description 555-233-200 Issue 1 April 2000 Site Requirements 47 Cabinet Power Requirements The “CE” mark is applied to the following products: nGlobal AC-powered Multicarrier Cabinet (MCC) with 25-Hz and 50-Hz ring generator nDC-powered Multicarrier Cabinet (MCC) with 25-Hz ring generator nAC-powered Enhanced Single-Carrier Cabinet (ESCC) with 25-Hz ring generator nAC-powered Compact Single-Carrier Cabinet (CSCC) with 25-Hz ring generator...
Page 58
Site Requirements 48 Cabinet Power Requirements DEFINITY Enterprise Communications Server Release 8.2 System Description 555-233-200 Issue 1 April 2000 Figure 17. Single-Phase, 120/240 VAC, 60 Hz Source Figure 18. Three-Phase, 120/208 VAC, 60 Hz Source 120 240 120 Phase A GroundNeutral Phase BTo equipment room AC load center widf1phs LJK 072298 120 208 208 120 120 Neutral Phase A Phase CGround Phase B To equipment room AC load center widf3phs LJK 071597
Page 59
DEFINITY Enterprise Communications Server Release 8.2 System Description 555-233-200 Issue 1 April 2000 Site Requirements 49 Cabinet Power Requirements 50 Hz Power Sources in R8 Systems Either of the following power sources can supply 50-Hz power to the AC- load in R7 and later systems: nInternational 5-wire, Y, 220/380 VAC. See Figure 19. nInternational Delta, 3-wire, 220 or 240 VAC. See Figure 20. NOTE: The type of power for a Multi-Carrier Cabinet is shown on the cabinet’s rear door, a...
Page 60
Site Requirements 50 Cabinet Power Requirements DEFINITY Enterprise Communications Server Release 8.2 System Description 555-233-200 Issue 1 April 2000 Figure 20. International Delta, 220 or 240 VAC, 50-Hz Source Ta b l e 9 lists the AC-power sources that can supply power to an AC- load in a cabinet. A NEMA receptacle (or equivalent) connects to the wires from the unit. The AC power cord from the power input of each unit plugs into a receptacle. Contact your Lucent Technologies representative for...