Page 51

DEFINITY Enterprise Communications Server Release 8.2
System Description  555-233-200  Issue 1
April 2000
Site Requirements 
41 Environmental Considerations 
Cross-Connect Field
The cross-connect field equipment is located a specified distance from the DEFINITY 
cabinets and must meet specific requirements. An optional cross-connect field can be 
installed in the CMC right panel.
For new installations, Lucent Technologies personnel may install the cross-connect field. 
For more details about the...

Page 52

Site Requirements 
42 Environmental Considerations 
DEFINITY Enterprise Communications Server Release 8.2
System Description  555-233-200  Issue 1
April 2000
Altitude and Air Pressure
At altitudes above 5,000 feet (1,525 meters), the maximum short-term temperature limit 
reduces by 1o Fahrenheit for each 1,000 feet (305 meters) of elevation above 5,000 feet 
(1,525 meters). For example: at sea level, the maximum short-term temperature limit is 
120
o F (49o Celsius). At 10,000 feet (3,050 meters), the...

Page 53

DEFINITY Enterprise Communications Server Release 8.2
System Description  555-233-200  Issue 1
April 2000
Site Requirements 
43 Environmental Considerations 
Ta b l e  6 . Te m p e r a t u r e  a n d  R e l a t i v e  H u m i d i t y  
Room Temperature 
(Degrees Fahrenheit)Room Temperature 
(Degrees Celsius)  Relative Humidity (%)
40 to 84 4.4 to 28.8 10 to 95
86 30.0 10 to 89
88 31.1 10 to 83
90 32.2 10 to 78
92 33.3 10 to 73
94 34.4 10 to 69
96 35.6 10 to 65
98 36.7 10 to 61
100 37.8 10 to 58
102 38.9...

Page 54

Site Requirements 
44 Environmental Considerations 
DEFINITY Enterprise Communications Server Release 8.2
System Description  555-233-200  Issue 1
April 2000
Air Purity
The Compact Modular Cabinet, Single-Carrier and Multi-Carrier Cabinets contain an air 
filter to reduce particulates flowing through the equipment. Do not install the cabinet 
where the air may be contaminated by excessive dust, lint, carbon particles, paper fiber 
contaminants, or metallic contaminants. For example, do not install the...

Page 55

DEFINITY Enterprise Communications Server Release 8.2
System Description  555-233-200  Issue 1
April 2000
Site Requirements 
45 Environmental Considerations 
Small tools with universal motors are generally not a problem when they operate on 
separate power lines. Motors without commutators generally do not cause interference. 
Field strengths below 1.0 volt per meter are unlikely to cause interference. 
Measure weak fields with a tunable meter. Measure field strengths greater than 1.0 volt 
per meter...

Page 56

Site Requirements 
46 Environmental Considerations 
DEFINITY Enterprise Communications Server Release 8.2
System Description  555-233-200  Issue 1
April 2000
Electromagnetic Compatibility Standards
This product complies with and conforms to the following EMC standards (as applicable):
nLimits and Methods of Measurements of Radio Interference Characteristics of 
Information Technology Equipment, EN55022 (CISPR22), 1993
nEN50082-1, European Generic Immunity Standard
nFCC Part 15
nAustralia AS3548
NOTE:
The...

Page 57

DEFINITY Enterprise Communications Server Release 8.2
System Description  555-233-200  Issue 1
April 2000
Site Requirements 
47 Cabinet Power Requirements 
The “CE” mark is applied to the following products:
nGlobal AC-powered Multicarrier Cabinet (MCC) with 25-Hz and 50-Hz ring 
generator
nDC-powered Multicarrier Cabinet (MCC) with 25-Hz ring generator
nAC-powered Enhanced Single-Carrier Cabinet (ESCC) with 25-Hz ring generator
nAC-powered Compact Single-Carrier Cabinet (CSCC) with 25-Hz ring generator...

Page 58

Site Requirements 
48 Cabinet Power Requirements 
DEFINITY Enterprise Communications Server Release 8.2
System Description  555-233-200  Issue 1
April 2000
Figure 17. Single-Phase, 120/240 VAC, 60 Hz Source
Figure 18. Three-Phase, 120/208 VAC, 60 Hz Source
120 240
120
Phase A
GroundNeutral
Phase BTo equipment room
AC load center
widf1phs LJK 072298
120
208
208
120
120
Neutral
Phase A
Phase CGround Phase B
To equipment room
AC load center
widf3phs LJK 071597 

Page 59

DEFINITY Enterprise Communications Server Release 8.2
System Description  555-233-200  Issue 1
April 2000
Site Requirements 
49 Cabinet Power Requirements 
50 Hz Power Sources in R8 Systems
Either of the following power sources can supply 50-Hz power to the AC- load in R7 and 
later systems:
nInternational 5-wire, Y, 220/380 VAC. See Figure 19. 
nInternational Delta, 3-wire, 220 or 240 VAC. See Figure 20.
NOTE:
The type of power for a Multi-Carrier Cabinet is shown on the cabinet’s rear door, 
a...

Page 60

Site Requirements 
50 Cabinet Power Requirements 
DEFINITY Enterprise Communications Server Release 8.2
System Description  555-233-200  Issue 1
April 2000
Figure 20. International Delta, 220 or 240 VAC, 50-Hz Source
Ta b l e  9 lists the AC-power sources that can supply power to an AC- load in a cabinet. A 
NEMA receptacle (or equivalent) connects to the wires from the unit. The AC power cord 
from the power input of each unit plugs into a receptacle.
Contact your Lucent Technologies representative for...