Home > Kenmore > Heater > Kenmore Power Miser 6 Manual

Kenmore Power Miser 6 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Kenmore Power Miser 6 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 23 Kenmore manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							31
    control valve/thermostat. Finally, start the thermocouple nut 
    and turn it all the way in by hand.  An additional quarter turn 
    with a 3/8” open-end wrench will then be sufficient to seat 
    the lockwasher. When you are finished, connect the two 
    wire leads that go to the thermal switch.
    7.  Reconnect the igniter wire.
    8.  Turn gas supply on and refer to the Lighting Instructions.
    9.  With the burner lit, check the gas control valve/thermostat 
    supply line, two piece wire connector, manifold tube, 
    and pilot tube connections for leaks. Check for leaks by 
    brushing on an approved noncorrosive leak detection 
    solution. Bubbles forming indicate a leak. Correct any leak 
    found. IMPORTANT: All leaks must be fixed immediately.
    10.  Replace the outer door.
    DOOR GASKETFLAME ARRESTORBRACKET
    TIP
    FIGURE 39.
    MANIFOLD TUBETIP
    BRACKETSLOT CLOSE-UP INSIDE VIEW OF
    THE COMBUSTION CHAMBER.
    FIGURE 40.
    Piezoelectric  Igniter  System                                   
    The piezoelectric igniter system consists of the igniter button, 
    electrode, and wire.  The pilot is ignited by an electric spark 
    generated when the igniter button is pressed. The spark gap 
    of 0.125 inch is set when the electrode is installed at the factory. 
    (Figure 41). Use only factory authorized piezoelectric igniter 
    parts for replacement.
    SNAP-ON CONNECTOR
    IGNITER
    BUTTON
    WIRE
    TO
    ELECTRODETHERMOCOUPLE
    PILOT
    PILOT
    BRACKET
    ELECTRODETIP
    .125” *
    * NOTE: SPARK GAP DISTANCE MEASURED FROM ELECTRODE TIP TO PILOT.
     
    FIGURE 41.
    Replacing  the  Manifold/Burner  Assembly                             
    Explosion Hazard
    •    Tighten both manifold door screws securely.
    •    Remove any fiberglass between gasket 
    and combustion chamber.
    •    Replace viewport if glass is missing or 
    damaged.
    •    Replace two piece wire connector if missing or 
    removed.
    •    Replace door gasket if damaged.
    •    Failure to follow these instructions can result 
    in death, explosion, or fire.
    WARNING
    1.  Check the door gasket for damage or imbedded debris 
    prior to installation.
    2.  Inspect the view port for damage and replace as required.
    3.  Insert the manifold/burner assembly into the burner 
    compartment, making sure that the tip of the manifold tube 
    engages in the slot of the bracket inside the combustion 
    chamber (Figures 39 & 40). 
    4.  Inspect the door gasket and make sure there is no 
    fiberglass insulation between the gasket and the 
    combustion chamber.
    5.  Replace the two screws, which secure the manifold/
    burner assembly door to the combustion chamber and 
    tighten securely. Once the manifold/burner assembly door 
    is tightened, visually inspect the door gasket between 
    the manifold/burner assembly door and the combustion 
    chamber for spaces or gaps that would prevent a seal. 
    IMPORTANT: Do not operate the water heater if the door 
    gasket does not create a seal between the manifold door 
    and the combustion chamber.
    6.  During the following procedure, do not cross-thread or 
    apply any thread sealant to any of the fittings listed below. 
    First, reconnect the manifold tubing to the gas control valve/
    thermostat. NOTE: L.P. gas systems use reverse (left-hand) 
    threads on the manifold tube.   
      NOTE: If a ferrule nut needs to be installed for the pilot 
    tube, locate the one provided with your parts kit.  Install it in 
    the gas control valve/thermostat at the pilot location, hand 
    tight only.  
      Next, insert the pilot tube into the ferrule nut until it bottoms 
    out. NOTE: Hold the tube in this position. Tighten the ferrule 
    nut with a wrench until the crimp connection seals to the 
    pilot tube. Continue to tighten until the nut is tight in the gas  
    						
    							32
    TEFLON® tape or pipe compound only on the threaded 
    section of the gas control valve/thermostat that screws into 
    the tank. 
    2.   Reconnect the gas piping to the gas control valve/
    thermostat. NOTE: Use an approved Teflon tape or pipe 
    compound on the gas piping connections.
    3.   Attach the igniter and bracket to the new gas control valve/
    thermostat, clipping it at the back edge of thermostat and 
    snapping it into place. NOTE: Do not use the (pilot) ferrule 
    nut supplied with the new gas control valve/thermostat, 
    unless the existing nut is not usable. Reconnect the pilot 
    tube, manifold tube, igniter wire, and thermal switch wires. 
    NOTE: L.P. gas systems use reverse (left-hand) threads on 
    the manifold tube.
    4.   Fill the tank completely with water. NOTE: To purge the 
    lines of any excess air, keep the hot water faucet open for 
    3 minutes after a constant flow of water is obtained.
    5.  Turn on the gas supply and test the gas supply connections 
    by brushing on an approved noncorrosive leak detection 
    solution. Bubbles forming indicate a leak. Correct any leak 
    found.
    6.   Check the operation of the burner by following the lighting 
    instructions on the front of the water heater. With the 
    burner lit, check the gas control valve/thermostat supply 
    line, manifold tube and pilot tube connections for leaks. 
    7.  Verify proper operation and then replace the outer door.
    8.  If additional information is required, contact Residential 
    Technical Assistance by referencing the number on the water 
    heater.
    TEFLON
    ® is a registered trademark of E.I. Du Pont De Nemours 
    and Company.
    FVIR  System  Operational  Checklist                                 
    1.  Manifold gasket properly sealed.
    2.  Viewport not damaged or cracked.
    3.  Flame-arrestor free of debris and undamaged.
    4.  Two piece wire connector properly installed.
    5.  No leaks at pilot and manifold connection.
    6.  Manifold door screws securely tightened. 
    7.  Depress the button on the thermal switch.
    Testing  the  Igniter  System                                      
    Turn off the gas to the water heater at the manual gas shut-off 
    valve. Watch the electrode tip while activating the igniter. A 
    visible spark should jump from the electrode. To avoid shock, 
    do not touch the burner or any metal part on the pilot or pilot 
    assembly. If no spark is visible, check the wire connections 
    and make sure the electrode is not broken. Replace the igniter 
    if defective. Dirt and rust on the pilot or electrode tip can 
    prevent the igniter spark. Wipe clean with a damp cloth and dry 
    completely. Rust can be removed from the electrode tip and 
    metal surfaces by lightly sanding with an emery cloth or fine 
    grit sandpaper.
    Removing and Replacing the Gas Control 
    Valve/Thermostat                                                             
    IMPORTANT: This water heater has a resettable thermal
    switch installed. Do not attempt to disable or modify this
    feature in any way. Use only factory authorized replacement 
    parts.
    Removing the Gas Valve:
    1.  Turn off the gas supply to the water heater at the manual gas 
    shut-off valve. This valve is typically located beside the water 
    heater. Note the position of the shut-off valve in the open/on 
    position then proceed to turn it off (Figure 11).
    2.  On the lower front of the water heater, locate the gas control 
    valve/thermostat (see Figure 32). Before performing any 
    maintenance, it is important to turn the temperature dial on 
    the gas control valve/thermostat to its lowest setting.
    3.  On top of the gas control valve/thermostat, turn the gas 
    control knob to the “OFF” position. See Lighting Instructions 
    on the water heater.
    4.  Drain the water heater. Refer to the section of “Draining 
    and Flushing” section and follow the procedure.
    5.  Disconnect the igniter wire from the igniter. NOTE:  There are 
    two types of igniters. If you have the square igniter, slide the 
    igniter bracket backwards away from the gas valve to remove 
    it.  If you have the round igniter, first remove the igniter from the 
    bracket by depressing front and rear holding tabs and lift. Next, 
    remove the igniter bracket from the gas valve. Disconnect the 
    thermocouple (right-hand threads), pilot tube, and manifold 
    tube at the gas control valve/thermostat (Figure 31). NOTE: 
    L.P. gas systems use reverse (left-hand) threads on the 
    manifold tube.
    6.  Refer to “Gas Piping” section (Figure 11) and disconnect 
    the ground joint union in the gas piping. Disconnect the 
    remaining pipe from the gas control valve/thermostat.
    7.  To remove the gas control valve/thermostat, thread a 
    correctly sized pipe into the inlet and use it to turn the gas 
    control valve/thermostat (counterclockwise.) Do not use a 
    pipe wrench or equivalent to grip body.  Damage may result, 
    causing leaks. 
      Do not insert any sharp objects into the inlet or outlet connections. 
    Damage to the gas control valve/thermostat may result.
    Replacing the Gas Valve:
    1.   To replace the gas control valve/thermostat, reassemble 
    in reverse order. When replacing the gas control valve/ 
    thermostat, thread a correctly sized pipe into the inlet and 
    use it to turn the gas valve (clockwise.) DO NOT OVER 
    TIGHTEN or damage may result. NOTE: Use an approved  
    						
    							33
    TROUBLESHOOTING GUIDE
    Start  Up  Conditions                                                                                                                                      
    Thermal Expansion
    As water is heated, it expands (thermal expansion). In a closed 
    system, the volume of water will grow. As the volume of water 
    grows, there will be a corresponding increase in water pressure 
    due to thermal expansion. Thermal expansion can cause 
    premature tank failure (leakage). This type of failure is not 
    covered under the limited warranty. Thermal expansion can also 
    cause intermittent temperature-pressure relief valve operation: 
    water discharged from the valve due to excessive pressure 
    build up. The temperature-pressure relief valve is not intended 
    for the constant relief of thermal expansion. This condition is not 
    covered under the limited warranty.
    A properly sized thermal expansion tank should be installed 
    on all closed systems to control the harmful effects of thermal 
    expansion. Thermal expansion tanks are available from Sears 
    stores and through the Sears Service Centers. Contact the local 
    plumbing inspector, water supplier and/or the Sears Service 
    Center for assistance in controlling these situations. See 
    Figure 42.
    Thermal Expansion Tank Specifi cations
     Tank                   Dimensions    Pipe
      Model   Capacity                 in Inches     Fitting
     Number  In Gallons  Diameter  Length  On Tank
      153.331020  2  8 (203 mm)  12-3/4 (323 mm)   3/4” Male
      153.331050  5  11 (279 mm)  14-3/4 (375 mm)   3/4” Male
    Expansion Tank Sizing Chart
    Inlet*        Water Heater Capacity (Gallons)
       Water
       Pressure 30 40 50 66 82
    Expansion 40psi  2  2 2 5 5
    Ta n k  50psi  2  2 2 5 5
    Capacity 60psi  2 2 5 5 5
    Needed 70psi 2 2 5 5 5
        80psi  2  5 5 5 5
    *Highest recorded inlet water pressure in a 24 hour period or regulated 
    water pressure.
    NOTE: Expansion tanks are pre-charged with a 40 psi air 
    charge.  If the inlet water pressure is higher than 40 psi, the 
    expansion tank’s air pressure must be adjusted to match 
    that pressure, but must not be higher than 80 psi.
          
          
    FIGURE 42.
    Strange Sounds
    Possible noises due to expansion and contraction of some 
    metal parts during periods of heat-up and cool-down do not 
    represent harmful or dangerous conditions.
    Condensation causes sizzling and popping within the burner 
    area during heating and cooling periods and should be 
    considered normal.  See “Condensation” section.
    Draft Hood Operation
    Check draft hood operation by performing a worst case 
    depressurization of the building. With all doors and windows 
    closed, and with all air handling equipment and exhaust fans 
    operating such as furnaces, clothes dryers, range hoods and 
    bathroom fans, a match flame should still be drawn into the draft 
    hood of the water heater with its burner firing. If the flame is not  
    						
    							34
    drawn toward the draft hood, shut off water heater and make 
    necessary air supply changes to correct.
    Condensation
    Whenever the water heater is filled with cold water, some 
    condensate will form while the burner is on. A water heater may 
    appear to be leaking when in fact the water is condensation. 
    This usually happens when: 
    •  A new water heater is filled with cold water for the first 
    time.
    •  Burning gas produces water vapor In water heaters, 
    particularly high efficiency models where flue temperatures 
    are lower.
    •  Large amounts of hot water are used in a short time and the 
    refill water in the tank is very cold.
    Moisture from the products of combustion condense on the 
    cooler tank surfaces and form drops of water which may fall 
    onto the burner or other hot surfaces to produce a “sizzling” or 
    “frying” noise.
    Excessive condensation can cause pilot outage due to water 
    running down the flue tube onto the main burner and putting 
    out the pilot.
    Because of the suddenness and amount of water, condensation 
    water may be diagnosed as a “tank leak”. After the water in 
    the tank warms up (about 1-2 hours), the condition should 
    disappear.
    Do not assume the water heater is leaking until there has been 
    enough time for the water in the tank to warm up. 
    An undersized water heater will cause more condensation. 
    The water heater must be sized properly to meet the family’s 
    demands for hot water including dishwashers, washing machines 
    and shower heads.
    Excessive condensation may be noticed during the winter and 
    early spring months when incoming water temperatures are at 
    their lowest.
    Good venting is essential for a gas fired water heater to operate 
    properly as well as to carry away products of combustion and 
    water vapor. 
    Smoke Odor
    It is not uncommon to experience a small amount of smoke and 
    odor during the initial start-up. This is due to burning off of oil 
    from metal parts, and will disappear in a short while.
    Operational  Conditions                                                                                                    
    Smelly Odor
    In each water heater there is installed at least one anode rod 
    (see parts section) for corrosion protection of the tank. Certain 
    water conditions will cause a reaction between this rod and the 
    water. The most common complaint associated with the anode 
    rod is one of a “rotten egg smell”. This odor is derived from 
    hydrogen sulfide gas dissolved in the water. The smell is the result of four factors which must all be present for the odor to 
    develop:
    •  a concentration of sulfate in the supply water.
    •  little or no dissolved oxygen in the water.
    •  a sulfate reducing bacteria within the water heater. (This 
    harmless bacteria is non-toxic to humans.)
    •  an excess of active hydrogen in the tank. This is caused by 
    the corrosion protective action of the anode.
    Smelly water may be eliminated or reduced in some water 
    heater models by replacing the anode(s) with one of less active 
    material, and then chlorinating the water heater tank and all 
    hot water lines. Contact Sears Service for further information 
    concerning this chlorination treatment and an anode replacement 
    kit #9001453. (For short heaters, use anode replacement 
    kit #9006299.)  Anode replacement and chlorination of the tank 
    are not covered by the water heater’s limited warranty.
    If the smelly water persists after the anode replacement and 
    chlorination treatment, it may be necessary to chlorinate or 
    aerate your water supply to eliminate the problem.
    Do not remove the anode, leaving the tank unprotected. By 
    doing so, all warranty on the water heater tank is voided.
    “AIR” In Hot Water Faucets
    HYDROGEN GAS: Hydrogen gas can be produced in a hot water 
    system that has not been used for a long period of time (generally 
    two weeks or more). Hydrogen gas is extremely fl ammable  and 
    explosive. To prevent the possibility of injury under these conditions, 
    we recommend the hot water faucet, located farthest away, be 
    opened for several minutes before any electrical appliances which are 
    connected to the hot water system are used (such as a dishwasher 
    or washing machine). If hydrogen gas is present, there will probably 
    be an unusual sound similar to air escaping through the pipe as the 
    hot water faucet is opened. There must be no smoking or open fl ame 
    near the faucet at the time it is open.
    Safety Shut-off and Thermal Switch
    This water heater is designed to automatically shut-off in the 
    event of the following:
    1.  The pilot flame is extinguished for any reason.
    2.  The water temperature exceeds 195°F (91°C).
    3.  Excessive build up of dust on the base ring filter or flame 
    arrestor. See Maintenance of your Water Heater Section.
    4.  The ignition of flammable vapors.
    A thermocouple is used to determine if a pilot flame is present, 
    and will shut off the gas supply to the main burner and the pilot  
    						
    							35
    Read this manual first. Then, before checking the water heater, 
    make sure the gas supply has been turned “OFF”, and never 
    turn the gas “ON” before the tank is completely full of water.
    Never use this water heater unless it is completely filled with 
    water.  To prevent damage to the tank, the tank must be filled 
    with water.  Water must flow from the hot water faucet before 
    turning “ON” gas to the water heater.  
    A.  Water at the draft hood is water vapor which has condensed 
    out of the combustion products.  This is caused by a 
    problem in the vent.  Contact a qualified technician.
    B.   *Condensation may be seen on pipes in humid weather or 
    pipe connections may be leaking.
    C.   *The anode rod fitting may be leaking.
    D.   Small amounts of water from temperature-pressure relief 
    valve may be due to thermal expansion or high water 
    pressure in your area.
    E.   *The temperature-pressure relief valve may be leaking at 
    the tank fitting.
    F.   Water from a drain valve may be due to the valve being 
    slightly opened.
    G.   *The drain valve may be leaking at the tank fitting.
    H.  Combustion products contain water vapor which can 
    condense on the cooler surfaces of the tank. Droplets form 
    and drip onto the burner or run on the floor. This is common 
    at the time of start-up after installation and when incoming 
    water is cold.
    I.   Water in the water heater bottom or on the floor may be 
    from condensation, loose connections, or the relief valve. 
    DO NOT replace the water heater until a full inspection 
    of all possible water sources is made and necessary 
    corrective steps taken.
    Leakage from other appliances, water lines, or ground seepage 
    should also be checked.
    *  To check where threaded portion enters tank, insert cotton 
    swab between jacket opening and fitting. If cotton is wet, follow 
    draining instructions in the “Draining and Flushing” section and 
    then remove fitting. Put pipe dope or teflon tape on the threads 
    and replace. When you are finished, follow the steps in “Filling 
    the Water Heater” in the Installation Instructions earlier in this 
    manual. if the flame is absent. This unit is also equipped with a thermal 
    switch, designed to shut off the gas supply in the event the 
    water heater has been exposed to flammable vapors (e.g., 
    spilled gasoline), poor combustion caused by a blocked vent or 
    insufficient combustion air. If the thermal switch opens:
    1. Check the fl ame-arrestor for signs of high temperature (blue 
    or black discoloration). See Figure 38. 
    2. If there are signs of high temperature or that the thermal switch 
    has opened, inspect your installation for problems with venting, 
    combustion air supply, or a possible fl ammable vapor event. 
    (See “Pilot Light Troubleshooting Flowchart” section.) Correct 
    any issues prior to resetting the thermal switch. If you suspect 
    a fl ammable vapor incident has occurred, do not use this 
    appliance. Immediately call a qualifi ed technician to inspect 
    the appliance. Water heaters subjected to a fl ammable vapors 
    ignition will require replacement of the entire water heater.
    3. Reset the thermal switch by depressing the small button in the 
    center of the thermal switch. Follow the Lighting Instructions 
    found on the front of your water heater. A high temperature 
    limit switch or ECO (Energy Cut Off) in the tank is used to 
    shut off the unit if the water temperature exceeds 195°F 
    (91°C). The ECO is a single-use switch, which, if activated, 
    requires complete replacement of the entire gas control valve/
    thermostat. If the ECO should activate, the water heater cannot 
    be used until the gas control valve/thermostat is replaced by 
    a qualifi ed technician. Contact Sears at 1-800-4-MY-HOME 
    (1-800-469-4663) to request service.
    Leakage Checkpoints
                 
    6” MAXIMUM
    AIR GAP
    AC
    B
    D
    E
    F
    G
    H
    I
    FIGURE 43. 
    						
    							36
    TROUBLESHOOTING CHART
    PROBLEM POSSIBLE CAUSE(S) CORRECTIVE ACTION
    BURNER WILL NOT IGNITE 1.  Pilot not lit
    2.  Thermostat set too low
    3. No gas
    4.  Dirt in the gas lines
    5.  Pilot line clogged
    6.  Main burner line clogged
    7. Non-functioning thermocouple
    8. Non-functioning thermostat
    9.  Heater installed in a confined area1. Light pilot
    2.  Turn temp. dial to desired temperature
    3.  Check with gas utility company
    4.  Notify utility-install trap in gas line
    5.  Clean, locate source and correct
    6.  Clean, locate source and correct
    7.  R e p l a c e  t h e r m o c o u p l e
    8. Replace thermostat
    9.  Provide fresh air ventilation
    SMELLY WATER 1.  Sulfides in the water 1.  Replace the anode with a special anode
    BURNER FLAME YELLOW-
    LAZY1.  Insufficient secondary air
    2.  Low gas pressure
    3.  Water heater flue or vent system 
    blocked
    4.  Main burner line clogged
    5.  Heater installed in a confined area
    6.  Obstruction in main burner orifice1.  Provide ventilation to water heater
    2.  Check with gas utility company
    3.  Clean, locate source and correct
    4.  Clean, locate source and correct
    5.  Proper fresh air ventilation
    6.  Clean or replace orifice
    PILOT WILL NOT LIGHT OR 
    REMAIN LIT1. Non-functioning igniter
    2.  The thermal switch tripped
    3.  Wire lead connection at thermal switch 
    loose
    4.  Thermocouple connection loose
    5.  Air in gas line
    6.  Low gas pressure
    7.  N o  g a s
    8.  Dirt in gas lines
    9. Cold drafts
    10.  Thermostat ECO switch open
    11.  Pilot line or orifice clogged
    12. Non-functioning thermocouple
    13.  Air for combustion obstructed
    14. Flammable vapors incident, FVIR 
    function actuated
    15.  Base-ring filter obstructed1.  Replace igniter pilot assembly
    2.  See Pilot Light Troubleshooting Flowchart section
    3.  Remove and reconnect the wire leads at 
    thermal switch, confirm connections are tight 
    and not loose
    4.  Finger tighten; then 1/4 turn with wrench
    5.  Bleed the air from the gas line
    6.  Check with gas utility company
    7.  Check with gas utility company
    8.  Notify utility-install dirt trap in gas line
    9.  Locate source and correct
    10. Replace thermostat
    11.  Clean, locate source and correct
    12. Replace thermocouple
    13.  See maintenance section for inspection and   
    cleaning of flame arrester 
    14. Replace water heater, eliminate flammable 
    vapors source. Contact Sears Service.
    15.  Inspect and clean base-ring filter. See “External 
    Cleaning & Inspection of the Base-Ring Filter.”
    HIGH OPERATION COSTS 1.  Thermostat set too high
    2.  Sediment or lime in tank
    3.  Water heater too small for job
    4.  Wrong piping connections
    5. Leaking faucets
    6. Gas leaks
    7.  Wasted hot water
    8.  Long runs of exposed piping
    9.  Hot water piping in exposed wall1.  Set temperature dial to lower setting
    2.  Drain/flush-provide water treatment if needed
    3.  Install adequate heater
    4.  Correct piping-dip tube must be in cold inlet
    5. Repair faucets
    6.  Check with utility-repair at once
    7.  A d v i s e  c u s t o m e r
    8. Insulate piping
    9. Insulate piping
    INSUFFICIENT HOT WATER 1.  Thermostat set too low
    2.  Sediment or lime in tank
    3.  Water heater too small
    4.  Wrong piping connections
    5. Leaking faucets
    6.  Wasted hot water
    7.  Long runs of exposed piping
    8.  Hot water piping in outside wall
    9.  Low gas pressure1.  Turn temperature dial to desired setting
    2.  Drain/flush-provide water treatment if needed
    3.  Install adequate heater
    4.  Correct piping-dip tube must be in cold inlet
    5 Repair faucets
    6. Advise customer
    7. Insulate piping
    8. Insulate piping
    9.  Check with gas utility company
    SLOW HOT WATER 
    RECOVERY1.  Insufficient secondary air
    2.  Water heater flue or vent system 
    blocked
    3.  Low gas pressure
    4. Improper calibration
    5.  Thermostat set too low
    6.  Water heater too small
    7.  Wrong piping connections
    8.  Wasted hot water1.  Provide ventilation to water heater. Check flue 
    way, flue baffle, and burner
    2.  Clean flue, locate source and correct
    3.  Check with gas utility company
    4. Replace thermostat
    5.  Turn temperature dial to desired setting
    6.  Install adequate heater
    7.  Correct piping-dip tube must be in cold inlet
    8. Advise customer
    DRIP FROM RELIEF VALVE 1.  Excessive water pressure
    2. Heater stacking
    3.  Closed water system1.  Use a pressure reducing valve and relief 
    valve
    2.  Lower the thermostat setting
    3.  See “Closed System/Thermal Expansion” 
    						
    							37
    PROBLEM POSSIBLE CAUSE(S) CORRECTIVE ACTION
    THERMOSTAT FAILS TO 
    SHUT-OFF1.  Thermostat not functioning properly
    2. Improper calibration1. Replace thermostat
    2. Replace thermostat
    COMBUSTION ODORS 1.  Insufficient secondary air
    2.  Water heater flue or vent system 
    blocked
    3.  Heater installed in a confined area1.  Provide ventilation to water heater. Check flue
      way, flue baffle, and burner
    2.  Clean, locate source and correct
    3.  Provide fresh air ventilation
    SMOKING AND  CARBON 
    FORMATION (SOOTING)1.  Insufficient secondary air
    2.  Low gas pressure
    3.  Water heater flue or vent system 
    blocked
    4.  Thermostat not functioning properly
    5.  Heater installed in a confined area
    6.  Burner flame yellow-lazy1.  Provide ventilation to water heater. Check flue 
    way, flue baffle, burner
    2.  Check with gas utility company
    3.  Clean, locate source and correct
    4. Replace thermostat
    5.  Provide fresh air ventilation
    6.  See “Burner Flame Yellow-Lazy”
    CONDENSATION 1.  Temperature setting too low 1.  Increase the temperature setting.  Refer to the 
    “Condensation” sub-section of this manual’s 
    Troubleshooting Guide.
    BURNER FLAME FLOATS 
    AND LIFTS  OFF PORTS1.  Orifice too large
    2.  High gas pressure
    3.  Water heater flue or vent system 
    blocked
    4. Cold drafts1.  Replace with correct orifice
    2.  Check with gas utility company
    3.  Clean flue and burner-locate source and correct
    4.  Locate source and correct
    BURNER FLAME TOO HIGH 1.  Orifice too large 1.  Replace with correct orifice
    FLAME BURNS AT ORIFICE 1.  Thermostat not functioning properly
    2.  Low gas pressure1. Replace thermostat
    2.  Check with gas utility company
    PILOT FLAME
    TOO SMALL1.  Pilot line or orifice clogged
    2.  Low gas pressure1.  Clean, locate source and correct
    2.  Check with gas utility company
    TROUBLESHOOTING CHART (CONTINUED) 
    						
    							38
    Has the thermal switch 
    tripped?
    NO
    Check for insufficient 
    combustion air.
    Are there openings 
    for make-up air to 
    enter the room?
    Are the openings of sufficient size? 
    See “Combustion Air Supply and Ventilation” 
    section in this manual for requirements.
    Is there a furnace/air 
    handler in the same room as 
    the water heater?
    Does the return air duct for the furnace/air handler draw 
    its air from a separate location than the water heater? 
    See the “Location Requirements” and “Combustion Air 
    Supply and Ventilation” sections in this manual.
    Is there proper drafting at the 
    draft hood? See “Checking the 
    Draft” section in this manual.
    Is the flame-arrestor free from 
    debris due to excessive lint, dirt, 
    dust or oil?
    Check the water heater for a Flammable Vapor (FV) event. Note: it may be 
    necessary to remove the manifold door assembly to visually inspect the water 
    heater. Reference the “Maintenance of your Water Heater” section of this 
    manual for removal instructions.
    Is the igniter wire insulation burnt or 
    show signs of discoloration?
    Install correct size make-up air openings per 
    the “Combustion Air Supply and Ventilation” 
    section in this manual.
    NO
    NO
    Correct size of openings to 
    allow sufficient air.
    Refer to the “Maintenance of Your Water Heater” section of this 
    manual for information on cleaning the flame-arrestor. 
    NO
    NO
    Check the vent system for restrictions/obstructions and check the vent 
    termination height. Refer to the “Installation Instructions” section of this 
    manual for specific requirements.
    NOIs the pilot tube 
    damaged?NODoes the flame 
    arrestor show signs 
    of discoloration and/
    or debris?
    Shut-off the gas supply to the water 
    heater at the manual gas shut-off 
    valve, then contact Sears Service at 
    1-800-4-MY-HOME (1-800-469-4663).
    YES
    YES
    YES
    YES
    YES
    YES
    YES
    YESYES
    NO
    Contact a local Heating, Ventilation, Air 
    Conditioning & Refrigeration authorized 
    service provider.
    Does pilot light go out when 
    button is released?
    YES
    NOCheck Draft. (See “Checking the 
    Draft” section of this manual.)
    NO
    YES
    Is the thermocouple 
    connection loose?
    Tighten the connection
    NO
    Test the thermocouple using the following 
    procedure: Disconnect the thermocouple from the 
    gas control valve/thermostat. Using a multimeter 
    with alligator clip leads, attach the red lead to 
    the body (copper part) of the thermocouple. 
    Attach the black lead to the end (silver part) of 
    the thermocouple that connects to the gas control 
    valve/thermostat. Follow the instruction to light 
    the pilot and watch the voltage readings on the 
    multimeter. After 45 seconds the meter should 
    read 12 millivolts DC or more.
    NODoes the thermocouple pass the test?
    YESYES
    YES
    Are the wires from the gas 
    control valve/thermostat firmly 
    connected to the switch?
    NOAre the wires damaged 
    and/or frayed?
    YES
    NOSecure connections 
    and attempt a relight.
    Replace the gas control 
    valve/thermostat.YES
    PILOT LIGHT TROUBLESHOOTING FLOWCHART
    THERMAL
    SWITCH
    Replace the thermocouple.
    Is the base-ring filter clean (i.e., free 
    of lint, dust, or debris)?
    YES
    NOInspect and clean the base-ring filter. Refer to the “External 
    Inspection & Cleaning of the Base-Ring Filter” section of this manual.  
    						
    							39
    NOTES 
    						
    							40
    Model Numbers
    Key No. Part Description 153.336433 153.336472 153.336572
    1 Anode Rod9003944 9003944 9003944
    2 Base-Ring Filter9006660 9006616 9006660
    3 Burner Head9006136 9006136 9006136
    4 Burner Orifi ce9006699 9006699 9006699
    5 Draft Hood9006647 9006647 9006647
    6 Drain Valve9002402 9002402 9002402
    7 Gas Control ValveF145-1555 F145-1555 F145-1555
    8 Inlet Tube w/ Gasket9006692 9003473 9006653
    9 Inner Door Gasket9006141 9006141 9006141
    10 Instruction Manual *186496-000 186496-000 186496-000
    11 Mag-Erad *23600 23600 23600
    12 Manifold Door Assembly - Contains: 
    Manifold Tube, Gasket, Door, Pilot Tube, 
    Thermocouple, Two-Piece Wire Connector 
    w/ Clip, Thermal Switch and Pilot Assembly.9006697 9006617 9006695
    13 Nipple w/Heat Trap9003719 9003719 9003719
    14 Outer Door9006648 9006648 9006648
    15 Piezo Igniter w/ Clip9006143 9006143 9006143
    16 Pilot Assembly w/ Tubing and 
    Fittings9006666 9006666 9006666
    17 T & P Relief Valve9000071 9000071 9000071
    18 Temperature Adjustment KnobF145-1280 F145-1280 F145-1280
    19 Thermocouple9000056 9000056 9000056
    20 Two-Piece Wire Connector w/ Clip9006449 9006449 9006449
     * Not Shown.      
    Now that you have purchased your gas water heater, should 
    a need ever exist for repair parts or service, simply contact 
    any Sears Service Center or call 1-800-4-MY-HOME
    ® 
    (1-800-469-4663). Be sure to provide all pertinent facts when 
    you call or visit.
    WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE 
    FOLLOWING INFORMATION:
    • MODEL NUMBER 
    •    SERIAL NUMBER   
    •    TYPE GAS - NATURAL OR PROPANE (L.P.) 
    •    PART DESCRIPTION
    THIS IS A REPAIR PARTS LIST, NOT A PACKING LIST.
    POWER MISER™ 6 GAS WATER HEATER
    PARTS ORDER LIST
    3
    4
    16
    9
    1220
    19
    13
    18
    17
    7
    6
    14
    2
    15
    18
    13
    5
    153.336433 40 Gallon Short (Natural)
    153.336472 40 Gallon Tall (Natural)
    153.336572 50 Gallon Tall (Natural)
    MODEL NUMBERS 
    						
    All Kenmore manuals Comments (0)