Home > Kenmore > Heater > Kenmore Power Miser 6 Manual

Kenmore Power Miser 6 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Kenmore Power Miser 6 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 23 Kenmore manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							11
    Installation  Checklist                                                  
    Water Heater Location
    Water heater location is important and can affect system 
    performance. Please check the following:
    □  Installation area free of corrosive elements and flammable 
    materials.
    □  Centrally located with the water piping system (For new 
    installations). Located as close to the gas piping and vent 
    pipe system as possible.
    □  Located indoors and in a vertical position. Protected from 
    freezing temperatures.
    □ Proper clearances from combustible surfaces 
    maintained and not installed directly on a carpeted floor.
    □  Provisions made to protect the area from water damage. 
    Metal drain pan installed and piped to an adequate drain.
    □  Sufficient room to service the water heater. See Clearances 
    and Accessibility section of this manual.
    □  Water heater not located near an air moving device.
    □  Is the installed environment dirty (excessive amounts of 
    lint, dirt, dust, etc.)?  If so, the base-ring filter located on 
    the bottom of the water heater will need to be cleaned 
    periodically.  Refer to the “Maintenance of your Water 
    Heater” section of this manual for information on cleaning 
    the base-ring filter. 
    Combustion Air Supply and Ventilation
    Check for sufficient combustion air supply.  Insufficient air for 
    the combustion of gas will result in the flame becoming “lazy”, 
    thereby allowing heat to build up in the combustion chamber.  
    This excessive heat will cause a thermal switch on the door 
    assembly to trip. Is the water heater installed in a closet or other 
    small, enclosed space? If so:
    □  Are there openings for make-up air to enter and exit the 
    room/area? 
    □ Are the openings of sufficient size?  Remember, if there 
    are other gas-fired or air-consuming appliances in the 
    same room, you need more make-up air.  Refer to the 
    “Installation Instructions” and “Combustion Air Supply and 
    Ventilation” sections for specific requirements.
    □ Make sure that fresh air is not taken from areas that contain 
    negative pressure producing devices such as exhaust fans, 
    dryers, fireplaces, etc.
    □   Is there a furnace/air handler in the same room space as 
    the water heater?  If so, has a return air duct system been 
    attached that exits the room? If so, check for leaks on the 
    air duct system. If no air duct system is present, correct 
    immediately by contacting a local Heating, Ventilation, Air-
    Conditioning & Refrigeration (HVAC-R) authorized service 
    provider. 
    □  Use a fresh air supply that is free of corrosive elements and 
    flammable vapors.
    IMPORTANT INFORMATION ABOUT THIS WATER HEATER
    This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor ignition incident. 
    The new technology used in meeting these standards makes this product more sensitive to installation errors. Please review the 
    following checklist and make any required installation upgrades or changes.  
    Questions?  Contact Sears at 1-800-4-MY-HOME (1-800-469-4663).
    □  Fresh air openings must be sized correctly with consideration 
    given to the blocking effect of louvers and grilles.
    □  Ductwork must be the same cross-sectional area as the 
    openings.
    Vent Pipe System
    Check for proper drafting at the water heater draft hood. Refer 
    to the “Checking the Draft” section of this manual for the test 
    procedure. If the procedure shows insufficient draft is present, 
    please check the following:
    □  Draft hood properly installed.
    □  Vent connectors securely fastened with screws and 
    supported properly to maintain six inch clearance.
    □  Vent connector made of approved material and sized 
    correctly.
    □  Vent pipe system installed according to all local and state 
    codes or, in the absence of local and state codes, the 
    “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current 
    edition.
    □  Flue baffle properly positioned in the flue tube.
    □  Check the vent system for restrictions/obstructions and 
    check the vent termination height.  Refer to the “Combustion 
    Air Supply and Ventilation” section of this water heater 
    manual for specific requirements.
    □ Recheck for sufficient combustion air supply.
    Water System Piping
    □  Temperature and pressure relief valve properly installed with 
    a discharge line run to an open drain and protected from 
    freezing.
    □  All piping properly installed and free of leaks.
    □  Heater completely filled with water.
    □  Closed system pressure build-up devices installed.
    □ Tempering valve (when applicable) installed per 
    manufacturer’s instructions (See “Water Temperature 
    Regulation” section).
    Gas Supply and Piping
    □  Gas type is the same as that listed on the water heater rating 
    plate.
    □  Gas line equipped with shut-off valve, union, and  drip leg.
    □  Use pipe joint compound or teflon tape marked as being 
    resistant to the action of petroleum [Propane (L.P.)] gases.
    □  Adequate pipe size and approved pipe material.
    □  An approved noncorrosive leak detection solution used 
    to check all connections and fittings for possible gas leaks. 
    Correct any leak found. 
    						
    							12
    INSTALLATION INSTRUCTIONS
    Removing  the  Old  Water  Heater                                                         
    FIGURE 2.
    1.      Turn “OFF” the gas supply to the 
    water heater.
        If the main gas line shutoff valve 
    serving all gas appliances is used,  
    also shut “OFF” the gas at each 
    appliance.  Leave all gas appliances  
    shut “OFF” until the water heater 
    installation is completed. See 
    Figures 2 and 3.
                                                
    2.    Turn “OFF” the water supply to 
    the water heater at the water 
    shut off valve or water meter.  
    Some installations require that 
    the water be turned off to the 
    entire house. See Figures 2 
    and 4.
                               
    3.      Check again to make sure the gas supply is “OFF” to the water 
    heater. Then disconnect the gas supply connection from the 
    gas control valve.
    4.    Attach a hose to the water heater 
    drain valve and put the other end 
    in a fl oor drain or outdoors.  (See 
    Figures 2 and 5.) Open the water 
    heater drain valve.  Open a nearby 
    hot water faucet which will relieve 
    pressure in the water heater and 
    speed draining. The water passing out  
    of the drain valve may be extremely 
    hot.  To avoid being scalded, make 
    sure all connections are tight and that 
    the water fl ow is directed away from 
    any person. 
    5.      Disconnect the vent pipe from the draft hood where it connects 
    to the water heater.  In most installations the  vent pipe can 
    be lifted off after any screw or other attached devices are 
    removed.  Dispose of the draft hood.  The new water heater 
    has a draft hood which must be used for proper operation.
    6.  If you have copper piping to the water heater, the two copper 
    water pipes can be cut with a hacksaw approximately four 
    inches away from where they connect to the water heater. 
    See Figure 6. This will avoid cutting off pipes too short. 
    Additional cuts can be made later if necessary. Disconnect the 
    temperature-pressure relief valve drain line. When the water 
    heater is drained, disconnect the hose from the drain valve. 
    Close the drain valve. The water heater is now completely 
    disconnected and ready to be removed.
    FIGURE 6.
     
    If you have galvanized pipes to the water heater, loosen 
    the two galvanized pipes with a pipe wrench at the union in 
    each line.  Also disconnect the piping remaining to the water 
    heater. See Figure 7.  These pieces should be saved since 
    they may be needed when reconnecting the new water heater.  
    Disconnect the temperature-pressure relief valve drain line.  
    When the water heater is drained, disconnect the hose from 
    the drain valve.  Close the drain valve.  The water heater 
    is now completely disconnected and ready to be removed. 
    Mineral buildup or sediment may have accumulated in the 
    old water heater.  This causes the water heater to be much 
    heavier than normal and this residue, if spilled out, could 
    cause staining.                          
    FIGURE 7.
    FIGURE 3.
    FIGURE 4.
    FIGURE 5.CHECK WITH
    LOCAL UTILITY
    FOR MINIMUM HEIGHT
    3” MINIMUM
    DRIP LEG
    GROUND 
    JOINT
    UNION
    SUITABLE
    DRAIN
    MANUAL GAS 
    SHUT-OFF VALVE
    6” MAXIMUM
    AIR GAP DISCHARGE PIPE
    (DO NOT CAP 
    OR PLUG) 1
    2
    3
    4
    56      
    						
    							13
    Location  Requirements                                              
    Carbon Monoxide Poisoning Hazard
    WARNING
    Do not install in a mobile home.  
    Doing so can result in carbon monoxide poisoning and death.  
    The FVIR System is designed to reduce the risk of flammable 
    vapor-related fires. The patented system protects your family by 
    trapping the burning vapors within the water heater combustion 
    chamber through the special flame-arrestor. The burning vapors 
    literally “burn themselves out” without escaping back into the 
    room. In the event of a flammable vapor incident, the FVIR 
    System disables the water heater by shutting off the gas supply 
    to the water heater’s burner and pilot, preventing re-ignition 
    of any remaining flammable vapors in the area. This will not 
    prevent a possible fire/explosion if the igniter is depressed 
    and flammable vapors have accumulated in the combustion 
    chamber with the pilot light off. If you suspect a flammable 
    vapor incident has occurred, do not use this appliance. Do not 
    attempt to light this appliance, or depress the igniter button 
    if you suspect flammable vapors have accumulated inside or 
    outside the appliance. Immediately call a qualified technician to 
    inspect the appliance. Water heaters subjected to a flammable 
    vapors incident will show a discoloration on the flame-arrestor 
    and require replacement of the entire water heater.
    FIRE AND EXPLOSION HAZARD
    Can result in serious injury or death
            Do not store or use gasoline or other flammable 
    vapors and liquids in the vicinity of this or any other 
    appliance. Storage of or use of gasoline or other 
    flammable vapors or liquids in the vicinity of this or any 
    other appliance can result in serious injury or death.
    Fl ammable VaporsFLAMMABLES
    Read and follow water heater warnings and instructions.
    WARNING
    Do not use or store flammable products such as gasoline, 
    solvents, or adhesives in the same room or area near the 
    water heater. If such flammables must be used, all gas burning 
    appliances in the vicinity must be shut off and their pilot lights 
    extinguished. Open the doors and windows for ventilation while 
    flammable substances are in use. 
    If flammable liquids or vapors have spilled or leaked in the 
    area of the water heater, leave the area immediately and call 
    the fire department from a neighbor’s home. Do not attempt to 
    clean the spill until all ignition sources have been extinguished.
    Fire or Explosion Hazard
    WARNING
    •  Read instruction manual before installing, using or 
      servicing water heater.
    •  Improper use may result in fire or explosion.
    •  Maintain required clearances to combustibles.
    Keep combustibles such as boxes, magazines, clothes, etc. 
    away from the water heater area. 
    Site  Location                                                          
    •  Select a location near the center of the water piping system. 
    The water heater must be installed indoors and in a vertical 
    position on a level surface. DO NOT install in bathrooms, 
    bedrooms, or any occupied room normally kept closed.
    •  Locate the water heater as close to the chimney or gas 
    vent as practical. Consider the vent system piping and 
    combustion air supply requirements when selecting the 
    water heater location. The venting system must be able 
    to run from the water heater to termination with minimal 
    length and elbows. 
    •  Locate the water heater near the existing gas piping. If 
    installing a new gas line, locate the water heater to minimize 
    the pipe length and elbows. 
    •  The water heater should be located in an area not subject 
    to freezing temperatures. Water heaters located in 
    unconditioned spaces (i.e., attics, basements, etc.) may 
    require insulation of the water piping and drain piping 
    to protect against freezing. The drain and controls must 
    be easily accessible for operation and service. Maintain 
    proper clearances as specified on the rating plate.
    •  Do not locate the water heater near an air-moving device. 
    The operation of air-moving devices such as exhaust fans, 
    ventilation systems, clothes dryers, fireplaces, etc., can 
    affect the proper operation of the water heater. Special 
    attention must be given to conditions these devices may 
    create. Flow reversal of flue gases may cause an increase 
    of carbon monoxide inside of the dwelling (Figure 8).
    •  If the water heater is located in an area that is subjected to 
    lint and dirt, it may be necessary to periodically clean the 
    base-ring filter and flame-arresto r (s e e E x te r n a l I ns p e c t i o n 
    & Cleaning of the Flame-arrestor). 
    •  This water heater is not for use in manufactured (mobile) 
    homes or outdoor installation.  
    NOTE:  This water heater must be installed according to all local 
    and state codes or, in the absence of local and state codes, the 
    “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition.
    REVERSE FLOW
    OF GASES  
    EXHAUST FAN
    FIGURE 8 
    						
    							14
    IMPORTANT: The water heater should be located in an area 
    where leakage of the tank or connections will not result in damage 
    to the area adjacent to the water heater or to lower floors of the 
    structure. Due to the normal corrosive action of water, the tank will 
    eventually leak after an extended period of time. Also any external 
    plumbing leak, including those from improper installation, may 
    cause early failure of the tank due to corrosion if not repaired.  If 
    the homeowner is uncomfortable with making the repair a qualified 
    technician should be contacted.  A suitable metal drain pan should 
    be installed under the water heater as shown below, to help protect 
    the property from damage which may occur from condensate 
    formation or leaks in the piping connections or tank. The pan must 
    limit the water level to a maximum depth of 1-3/4” and be two inches 
    wider than the heater and piped to an adequate drain. NOTE: The 
    pan must not restrict combustion air flow. Locate the water heater 
    near a suitable indoor drain. Outside drains are subject to freezing 
    temperatures which can obstruct the drain line. The piping should 
    be at least 3/4” ID and pitched for proper drainage. 
      METAL
    DRAIN
    PAN
    AT LEAST 2” GREATER  THAN THE 
    DIAMETER OF THE WATER HEATER.PIPED TO AN 
    ADEQUATE DRAIN
    FIGURE 9.
    Water heater life depends upon water quality, water usage, 
    water temperature and the environment in which the water 
    heater is installed. Water heaters are sometimes installed 
    in locations where leakage may result in property damage, 
    even with the use of a drain pan piped to a drain. However, 
    unanticipated damage can be reduced or prevented by a leak 
    detector or water shut-off device used in conjunction with 
    a piped drain pan. These devices are available from some 
    plumbing supply wholesalers and retailers, and detect and react 
    to leakage in various ways:
    •   Sensors mounted in the drain pan that trigger an alarm or 
    turn off the incoming water to the water heater when water 
    is detected.
    •   Sensors mounted in the drain pan that turn off the water 
    supply to the entire home when water is detected in the 
    drain pan.
    •   Water supply shut-off devices that activate based on the 
    water pressure differential between the cold water and hot 
    water pipes connected to the water heater.
    •   Devices that will turn off the gas supply to a gas water 
    heater while at the same time shutting off its water supply.
    Insulation Blankets                                            
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
    Insulation blankets available to the general public for external 
    use on gas water heaters are not necessary with Kenmore 
    products. The purpose of an insulation blanket is to reduce the 
    standby heat loss encountered with storage tank heaters. Your 
    Kenmore water heater meets or exceeds the National Appliance 
    Energy Conservation Act standards with respect to insulation 
    and standby loss requirements, making an insulation blanket 
    unnecessary.
     WARNING
    Should you choose to apply an insulation blanket to this 
    heater, you should follow these instructions (See Figure 1 
    for identification of components mentioned below). Failure to 
    follow these instructions can restrict the air flow required for 
    proper combustion, potentially resulting in fire, asphyxiation, 
    serious personal injury or death.
    • Do not apply insulation to the top of the water heater, as    
    this will interfere with safe operation of the draft hood.
    • Do not cover the outer door, thermostat or temperature & 
    pressure relief valve.
    • Do not allow insulation to come within 2” (50.8 mm) of 
    the floor to prevent blockage of combustion air flow to the 
    burner.
    • Do not cover the instruction manual. Keep it on the side of 
    the water heater or nearby for future reference.
    • Do obtain new warning and instruction labels from Sears 
    for placement on the blanket directly over the existing 
    labels.
    • Do inspect the insulation blanket frequently to make 
    certain it does not sag, thereby obstructing combustion air 
    flow.
    Clearances  and  Accessibility                                    
    NOTE: Minimum clearances from combustible materials are 
    stated on the label adjacent to the gas control valve/thermostat 
    of the water heater.  The water heater is certified for installation 
    on a combustible floor.
    • IMPORTANT: If installing over carpeting, the carpeting 
    must be protected by a metal or wood panel beneath the 
    water heater. The protective panel must extend beyond the 
    full width and depth of the water heater by at least three 
    inches (76.2mm) in any direction; o r i f i n a n a l c ove o r c l o s et 
    installation, the entire floor must be covered by the panel. 
    • Figure 10 may be used as a reference guide to locate the 
    specific clearance locations. A minimum of 24 inches of 
    front clearance should be provided for inspection and 
    service.   
    						
    							15
     
    BACK
    SIDES
    TOP
    VIEWSIDESVENT
    FRONT
    24” MINIMUM
    FOR SERVICETOP
    TO 
    CEILING
    FIGURE 10.
    Filling  the  Water  Heater                                                                                                                                          
    Never use this water heater unless it is completely full of water.  
    To prevent damage to the tank, the tank must be fi lled with water.  
    Water must fl ow from the hot water faucet before turning “ON” gas 
    to the water heater. To fi ll the water heater with water:
    •   Close the water heater drain valve by turning the handle to 
    the right (clockwise). The drain valve is on the lower front of 
    the water heater.
    Explosion Hazard
    •  Use a new CSA approved gas supply line.
    •  Install a shut-off valve.
    •  Do not connect a natural gas water heater to an 
    L.P. gas supply.
    •  Do not connect an L.P. gas water heater to a 
    natural gas supply.
    •  Failure to follow these instructions can result in 
    death, explosion, or carbon monoxide poisoning.
    WARNING
    Gas  Requirements                                                       
    IMPORTANT: Read the rating plate to be sure the water heater 
    is made for the type of gas you will be using in your home. This 
    information will be found on the rating plate located near the 
    gas control valve/thermostat. If the information does not agree 
    with the type of gas available, do not install or light. Call your 
    dealer.
    NOTE: An odorant is added by the gas supplier to the gas used 
    by this water heater. This odorant may fade over an extended 
    period of time. Do not depend upon this odorant as an indication 
    of leaking gas.
    Gas  Piping                                                                    
    The gas piping must be installed according to all local and state 
    GAS SUPPLY
    codes or, in the absence of local and state codes, the “National 
    Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition.
    Tables 1 and 2 on the following page provide a sizing reference 
    for commonly used gas pipe materials. Consult the “National 
    Fuel Gas Code” for the recommended gas pipe size of other 
    materials.
    NOTE: Use pipe joint compound or teflon tape marked as being 
    resistant to the action of petroleum [Propane (L.P.)] gases. 
    (See Figure 11.)
    1.  Install a readily accessible manual shut-off valve in the gas 
    supply line as recommended by the local utility. Know the 
    location of this valve and how to turn off the gas to this unit.
    2.  Install a drip leg (if not already incorporated as part of 
    the water heater) as shown. The drip leg must be no less 
    than three inches long for the accumulation of dirt, foreign 
    material, and water droplets.
    3.  Install a ground joint union between the gas control valve/
    thermostat and the manual shut-off valve. This is to allow 
    easy removal of the gas control valve/ thermostat.
    4.  Turn the gas supply on and check for leaks. Test all 
    connections by brushing on an approved noncorrosive 
    leak-detection solution. Bubbles will show a leak. Correct 
    any leak found.
    CHECK WITH
    LOCAL UTILITY
    FOR MINIMUM HEIGHT
    3” MINIMUM
    DRIP LEG
    GROUND 
    JOINT
    UNION
    SUITABLE
    DRAIN
    MANUAL GAS 
    SHUT-OFF VALVE
    FIGURE 11. •   Open the cold water supply valve to the water heater.  
    NOTE: The cold water supply valve must be left open 
    when the water heater is in use.
    •   To ensure complete fi lling of the tank, allow air to exit by 
    opening the nearest hot water faucet.  Allow water to run until 
    a constant fl ow is obtained.  This will let air out of the water 
    heater and the piping.
    •   Check all water piping and connections for leaks.  Repair as 
    needed. 
    						
    							16
    Gas  Pressure                                                         
    WARNING
    Explosion Hazard
    •  Gas leaks can not always be detected by smell.
    •  Gas suppliers recommend that you use a gas 
    detector approved by UL or CSA.
    •  For more information, contact your gas supplier.
    •  If a gas leak is detected, follow the “What to do if you 
    smell gas” instructions on the cover of this manual.
    IMPORTANT: The gas supply pressure must not exceed the maximum 
    supply pressure as stated on the water heater’s rating plate. The 
    minimum supply pressure is for the purpose of input adjustment.
    Gas  Pressure  Testing                                           
    IMPORTANT: This water heater and its gas connection must be 
    leak tested before placing the appliance in operation.
    •  If the code requires the gas lines to be tested at a pressure 
    exceeding 14” W.C., the water heater and its manual shut-off 
    valve must be disconnected from the gas supply piping system 
    and the line capped.
    •  If the gas lines are to be tested at a pressure less than 14” W.C., 
    the water heater must be isolated from the gas supply piping 
    system by closing its manual shut-off valve.
    NOTE: Air may be present in the gas lines and could prevent the 
    pilot from lighting on initial start-up. The gas lines should be purged 
    of air by a qualified technician after installation of the gas piping 
    system. While purging the gas piping system of air, ensure that 
    the fuel is not spilled in the area of the water heater installation, 
    or any source of ignition.  If the fuel is spilled while purging the 
    piping system of air follow the “WHAT TO DO IF YOU SMELL 
    GAS” instructions on the cover of this manual.
    LP  Gas  Only                                                                    
    WARNING
    Explosion Hazard
    Have a qualified person make sure L.P. gas pressure 
    does not exceed 13” water column.
    Examples of a qualified person include: licensed 
    plumbers, authorized gas company personnel, and 
    authorized service personnel.
    Failure to do so can result in death, explosion, or 
    fire.
       
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
    Liquefied petroleum gas is over 50% heavier than air and in 
    the occurrence of a leak in the system, the gas will settle at 
    floor level. Basements, crawl spaces, closets and areas below 
    ground level will serve as pockets for the accumulation of gas. 
    Before lighting an L.P. gas water heater, smell all around the 
    appliance at floor level. If you smell gas, follow the instructions 
    as given in the warning on the front page.
    When your L.P. tank runs out of fuel, turn off the gas at all 
    gas appliances including pilot lights. After the tank is refi lled, 
    all appliances must be re-lit according to their manufacturer’s 
    instructions. 
    						
    							17
    Carbon Monoxide Warning
    Follow all the local and state codes or, in the absence of 
    local and state codes, the “National Fuel Gas Code”, 
    ANSI Z223.1 (NFPA 54)- current edition to properly 
    install vent system.
    Failure to do so can result in death, explosion, or 
    carbon monoxide poisoning.
    WARNING
    IMPORTANT:  Air for combustion and ventilation must not 
    come from a corrosive atmosphere. Any failure due to corrosive 
    elements in the atmosphere is excluded from warranty 
    coverage.
    The following types of installation (not limited to the following) 
    will require outdoor air for combustion due to chemical exposure 
    and may reduce but not eliminate the presence of corrosive 
    chemicals in the air:
    • beauty shops
    •  photo processing labs
    •  buildings with indoor pools 
    •  water heaters installed in laundry, hobby, or craft rooms
    •  water heaters installed near chemical storage areas
    Combustion air must be free of acid-forming chemicals such as sulfur, 
    fluorine, and chlorine. These elements are found in aerosol sprays, 
    detergents, bleaches, cleaning solvents, air fresheners, paint, and 
    varnish removers, refrigerants, and many other commercial and 
    household products. When burned, vapors from these products 
    form highly corrosive acid compounds. These products should not 
    be stored or used near the water heater or air inlet.
    Combustion and ventilation air requirements are determined by 
    the location of the water heater. The water heater may be located 
    in either an open (unconfined) area or in a confined area or small 
    enclosure such as a closet or small room. Confined spaces are 
    areas with less than 50 cubic feet for each 1,000 BTUH of the total 
    input for all gas-using appliances.
    Unconfined  Space                                                   
    A water heater in an unconfined space uses indoor air for 
    combustion and requires at least 50 cubic feet for each 1,000 
    BTUH of the total input for all gas appliances. The table below 
    shows a few examples of the minimum square footage (area) 
    required for various BTUH inputs.
    TABLE 3
    BTUH InputMinimum Square
    Feet with
    8’ CeilingTypical Room
    with 8’ Ceiling
    30,000 188 9 x 21
    45,000 281 14 x 20
    60,000 375 15 x 25
    75,000 469 15 x 31
    90,000 563 20 x 28
    105,000 657 20 x 33
    COMBUSTION AIR SUPPLY & VENTILATION
    TABLE 3
    120,000 750 25 x 30
    135,000 844 28 x 30
    IMPORTANT:
    •  The area must be open and be able to provide the proper 
    air requirements to the water heater. Areas that are being 
    used for storage or contain large objects may not be 
    suitable for water heater installation. 
    •  Water heaters installed in open spaces in buildings with 
    unusually tight construction may still require outdoor air 
    to function properly. In this situation, outside air openings 
    should be sized the same as for a confined space. 
    •  Modern home construction usually requires supplying 
    outside air into the water heater area. 
    Confined Space                                                     
    For the correct and proper operation of this water heater, 
    ample air must be supplied for the combustion, ventilation, and 
    dilution of flue gases. Small enclosures and confined areas 
    must have two permanent openings so that sufficient fresh air 
    can be drawn from outside of the enclosure. One opening shall 
    be within 12 inches of the top and one within 12 inches of the 
    bottom of the enclosure as shown in Figure 12.
    The size of each opening (free area) is determined by the total 
    BTUH input of all gas utilization equipment (i.e., water heaters, 
    furnaces, clothes dryers, etc.) and the method by which the air 
    is provided. The BTUH input can be found on the water heater 
    rating plate. Additional air can be provided by two methods:
    1.   All air from inside the building.
    2.   All air from outdoors.
    12” MAXIMUM
    PERMANENT
    OPENINGS TO
    THE OUTSIDE OR 
    ADDITIONAL 
    ROOMS WITHIN
    THE BUILDINGCLOSET
    OR 
    OTHER 
    CONFINED 
    SPACE
    12” MAXIMUM
    FIGURE 12.
    All  Air  from  Inside  the  Building                              
    When additional air is to be provided to the confined area 
    from additional room(s) within the building, the total volume of 
    the room(s) must be of sufficient size to properly provide the 
    necessary amount of fresh air to the water heater and other  
    						
    							18
    TABLE 4
    Minimum Free Area of Permanent Openings for Ventilation 
    and Combustion Air Supply - All Air from Outdoors Only.
    Based on total BTUH input rating for all utilizing equipment 
    within the confi ned  space.
    Opening SourceMinimum Free Area 
    Per Opening (sq. in.)Reference 
    Drawing
    * D i r e c t  t o  o u t d o o r s 1 sq. in, per 4000 BTUH F i g u r e  14
    Ve r t i c a l  D u c t s 1 sq. in, per 4000 BTUH F i g u r e  15
    H o r i z o n t a l  D u c t s 1 sq. in, per 2000 BTUH F i g u r e  16
    S i n g l e O p e n i n g 1 sq. in, per 3000 BTUH F i g u r e 17
    Example: A water heater with an input rating of 50,000 BTUH using 
    horizontal ducts would require each opening to have a minimum free 
    area of 25 square inches.
    Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25 sq. 
    in.
    *  These openings connect directly with the outdoors through a 
    ventilated attic, a ventilated crawl space, or through an outside 
    wall.
    Consult the local codes of your area for specific ventilation and 
    combustion air requirements.
    GABLE VENT
    TO OUTDOORS
    INSTALL ABOVE
    INSULATION
    CONFINED
    SPACE
    ALTERNATE
    AIR INLETOUTLET 
    AIR TO 
    ATTIC 1 SQ.
    INCH PER 
    4000 BTUH
    INLET AIR FROM 
    THE CRAWL SPACE
    OPEN 
    FOUNDATION 
    VENT 1 SQ. INCH PER 
    4000 BTUH
    ALL AIR FROM OUTDOORS: INLET AIR FROM VENTILATED
    CRAWL SPACE/OUTLET AIR TO VENTILATED ATTIC 
    FIGURE 14.
    GABLE VENT
    TO OUTDOORS
    INSTALL ABOVE
    INSULATION
    CONFINED
    SPACEOUTLET AIR
    TO ATTIC
    1 SQ. INCH
    PER 4000 
    BTUH
    INLET AIR DUCT
    1 SQ. INCH PER
    4000 BTUH
    12” MAXIMUM
    ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC
    FIGURE 15.
    gas utilization equipment in the area. If you are unsure that the 
    structure meets this requirement, contact your local gas utility 
    company or other qualified agency for a safety inspection. 
    Each of the two openings shall have a minimum free area of 1 
    square inch per 1,000 BTUH of the total input rating of all gas 
    utilization equipment in the confined area, but not less than 100 
    square inches (Figure 13).
    CONFINED
    SPACE
    PERMANENT
    OPENINGS
    1 SQUARE
    INCH/1000
    BTUH 
    (MINIMUM
    100 SQ. IN.)
    FIGURE 13.
    All Air  from  Outdoors                                           
    Outdoor fresh air can be provided to a confined area either 
    directly or by the use of vertical and horizontal ducts. The 
    fresh air can be taken from the outdoors or from crawl or attic 
    spaces that freely communicate with the outdoors. Attic or crawl 
    spaces cannot be closed and must be properly ventilated to the 
    outside. 
    Ductwork must be of the same cross-sectional area as the 
    free area of the opening to which they connect. The minimum 
    dimension of rectangular air ducts cannot be less than three 
    inches. 
    The size of each of the two openings is determined by the 
    method in which the air is to be provided. Refer to Table 4 to 
    calculate the minimum free area for each opening. Figures 14, 
    15, 16 and 17 are typical examples of each method. 
    Louvers  and  Grilles                                                     
    In calculating free area for ventilation and combustion air supply 
    openings, consideration must be given to the blocking effect 
    of protection louvers, grilles, and screens. These devices can 
    reduce airflow, which in turn may require larger openings to 
    achieve the required minimum free area. Screens must not be 
    smaller than 1/4” mesh. If the free area through a particular 
    design of louver or grille is known, it should be used in 
    calculating the specified free area of the opening. If the design 
    and free area are not known, it can be assumed that most wood 
    louvers will allow 20 - 25% of free area while metal louvers and 
    grilles will allow 60 - 75% of free area. 
    Louvers and grilles must be locked open or interconnected with 
    the equipment so that they are opened automatically during 
    equipment operation. 
    Keep louvers and grilles clean and free of debris or other 
    obstructions. 
    						
    							19
    1 SQ. INCH PER
    2000 BTUH
    CONFINED
    SPACE
    1 SQ. INCH PER
    2000 BTUHINLETOUTLET
    OUTDOOR
    AIR DUCTS
    ALL AIR FROM OUTDOORS USING HORIZONTAL DUCTS
    FIGURE 16.
    ALTERNATIVE
    OPENING
    LOCATION
    1 SQ. INCH 
    PER 3000 BTUH CONFINED
    SPACE
    ALL AIR FROM OUTDOORS - USING A SINGLE PERMANENT OPENING
    FIGURE 17.
    Vent  Pipe  System                                                   
    This water heater uses a non-direct, single-pipe vent system 
    to remove exhaust gases created by the burning of fossil fuels. 
    Air for combustion is taken from the immediate water heater 
    location or is ducted in from the outside (see “Combustion Air 
    Supply and Ventilation”).
    This water heater must be properly vented for the removal of 
    exhaust gases to the outside atmosphere. Correct installation 
    of the vent pipe system is mandatory for the proper and efficient 
    operation of this water heater and is an important factor in the 
    life of the unit.
    The vent pipe must be installed according to all local and state 
    codes or, in the absence of local and state codes, the “National 
    Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition. The 
    vent pipe installation must not be obstructed so as to prevent 
    the removal of exhaust gases to the outside atmosphere.
    IMPORTANT: The use of vent dampers is not recommended 
    by the manufacturer of this water heater. Although some vent 
    dampers are certified by CSA International, this certification 
    applies to the vent damper device only and does not mean they 
    are certified for use on this water heater.
    U.L. recognized fuel gas and carbon monoxide (CO) detectors 
    are recommended in all applications and should be installed 
    using the manufacturer’s instructions and local codes, rules, or 
    regulations.
    IMPORTANT:  If you lack the necessary skills required to 
    properly install this venting system, you should not proceed, but 
    get help from a qualified technician.
    Draft  Hood  Installation                                             
    SHEET METAL SCREWS (FOUR PROVIDED)
    DRAFT HOOD
    LEGS LEGS
    SLOT SLOT
    JACKET TOP
    INSTALL THE DRAFT HOOD WITH
    THE FOUR SCREWS PROVIDED.
    FIGURE 18.
    Align the legs of the draft hood with the slots provided. Insert 
    the legs and secure the draft hood to the water heater’s top 
    with the four screws provided as shown in Figure 18. Do not 
    alter the draft hood in any way. If you are replacing an existing 
    water heater, be sure to use the draft hood supplied with this 
    water heater.
    Vent  Pipe  Size                                                               
    It is important that you follow the guidelines in these instructions 
    for sizing a vent pipe system. If a transition to a larger vent size 
    is required, the vent transition connection must be made at the 
    draft hood outlet.
    Vent  Connectors                                                          
    1.  Type B, Double wall, U.L. Listed Vent Pipe.
    2.  Single wall Vent Pipe.
    Maintain the manufacturer’s specified minimum clearance from 
    combustible materials when using type B double wall vent 
    pipe.
    Vent connectors made of type B, double wall vent pipe material 
    may pass through walls or partitions constructed of combustible 
    material if the minimum listed clearance is maintained.
    Maintain a six inch minimum clearance from all combustible 
    materials when using single wall vent pipe.
    IMPORTANT: Single wall vent pipe cannot be used for water 
    heaters located in attics and may not pass through attic spaces, 
    crawl spaces or any confined or inaccessible location. A single 
    wall metal vent connector cannot pass through any interior 
    wall.
    When installing a vent connector, please note the following 
    (See Figures 19-21):
    •  Install the vent connector avoiding unnecessary bends, 
    which create resistance to the flow of vent gases.
    •  Install without dips or sags with an upward slope of at least 
    1/4-inch per foot.
    •  Joints must be fastened by sheet metal screws or other 
    approved means. It must be supported to maintain 
    clearances and prevent separation of joints and damage.
    •  The length of the vent connector cannot exceed 75% of the 
    ver tical vent height. 
    						
    							20
    separation, and maintain clearances to combustible materials 
    (Figures 20 and 21).
    IMPORTANT: This gas vent must be terminated in a vertical 
    position to facilitate the removal of the burnt gases.
    An unused chimney flue or masonry enclosure may be used as a 
    passageway for the installation of a gas vent (Figure 21).
    Common (combined) venting is allowable with vertical type B 
    vent systems and lined masonry chimneys as long as proper 
    draft for the water heater is established under all conditions of 
    operation. CAUTION: DO NOT common vent this water heater 
    with any power vented appliance.
    Figures 19-21 are examples of vent pipe system installations 
    and may or may not be typical for your specific application. 
    Consult the “National Fuel Gas Code”, NFPA 54, ANSI Z223.1-
    current edition and the guidelines set forth by prevailing local 
    codes.
    VERTICAL GAS VENT SYSTEM WITH 
    TYPE B DOUBLE WALL VENT PIPE.
    3 FT. MINIMUM
    LISTED VENT CAP
    2 FT. MINIMUM ABOVE ANY OBJECT 
    WITHIN 10 FT. HORIZONTALLY
    TYPE B DOUBLE
    WALL VENT PIPE
    **MAINTAIN
    SPECIFIED
    CLEARANCE
    VENT
    CONNECTOR
    SLOPE UP
    1/4 IN. PER FT.
    MINIMUM *MAINTAIN
    CLEARANCE
    SUPPORT
    STRAP
    FIGURE 20.
    VENTING THROUGH A CHIMNEY WITH
    TYPE B DOUBLE WALL VENT PIPE.5 FT. MINIMUMLISTED VENT CAP
    VENT  CONNECTOR
    UNUSED CHIMNEY
    FLUE OR MASONRY
    ENCLOSURE SEAL *MAINTAIN
    CLEARANCE
    VENT
    CONNECTOR
    SLOPE UP 
    1/4 IN. PER FT.
    MINIMUM**MAINTAIN
    SPECIFIED
    CLEARANCE
    SUPPORT
    STRAP
    FIGURE 21.
    * Maintain vent pipe clearance requirements to local, state and/or the 
    “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition.
    ** NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid 
    Fuel-Burning Appliances states that these chimneys are intended to 
    be installed in accordance with the installation instructions provided 
    with each chimney support assembly. Minimum air space clearance to 
    combustible materials should be maintained as marked on the chimney 
    sections.
    •  The vent connector must be accessible for cleaning, 
    inspection, and replacement.
    •  Vent connectors cannot pass through any ceiling, floor, 
    firewall, or fire partition.
    •  It is recommended (but not mandatory) that a minimum 12 
    inches of vertical vent pipe be installed on the draft hood 
    prior to any elbow in the vent system.
    IMPORTANT: Existing vent systems must be inspected for 
    obstructions, corrosion, and proper installation.
    Chimney  Connection                                                  
    IMPORTANT: Before connecting a vent to a chimney, make sure 
    the chimney passageway is clear and free of obstructions. The 
    chimney must be cleaned if previously used for venting solid 
    fuel appliances or fireplaces. Also consult local and state codes 
    for proper chimney sizing and application or, in the absence 
    of local and state codes, the “National Fuel Gas Code”, ANSI 
    Z223.1(NFPA 54)-current edition.
    •  The connector must be installed above the extreme bottom 
    of the chimney to prevent potentially blocking the flue 
    gases.
    •  The connector must be firmly attached and sealed to 
    prevent it from falling out.
    •  To aid in removing the connector, a thimble or slip joint may 
    be used.
    •  The connector must not extend beyond the inner edge of 
    the chimney as it may restrict the space between it and the 
    opposite wall of the chimney (Figure 19).
    LISTED LINED
    CHIMNEY
    2 FT. MINIMUM ABOVE ANY OBJECT 
    WITHIN 10FT. HORIZONTALLY
    DO NOT EXTEND 
    VENT BEYOND EDGE
    OF CHIMNEY
    VENT
    CONNECTOR  3 FT. MINIMUM 
    MAINTAIN
    CLEARANCE*
    SEAL 
    SLOPE
    UP 1/4 IN.
    PER FT.
    MINIMUM
    CHIMNEY TERMINATION VENT SYSTEM
    SUPPORT
    STRAP
    FIGURE 19.
    Do not terminate the vent connector in a chimney that has not 
    been certified for this purpose. Some local codes may prohibit 
    the termination of vent connectors in a masonry chimney.
    Vertical  Exhaust  Gas  Vent                                          
    Vertical exhaust gas vents must be installed with U.L. listed type B 
    vent pipe according to the vent manufacturer’s instructions and the 
    terms of its listing. 
    It must be connected to the water heater’s draft hood by a 
    listed vent connector or by directly originating at the draft hood 
    opening.
    Vertical gas vents must terminate with a listed cap or other roof 
    assembly and be installed according to their manufacturer’s 
    instructions.
    Gas vents must be supported to prevent damage, joint  
    						
    All Kenmore manuals Comments (0)