Kenmore Power Miser 6 Manual
Have a look at the manual Kenmore Power Miser 6 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 23 Kenmore manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
11 Installation Checklist Water Heater Location Water heater location is important and can affect system performance. Please check the following: □ Installation area free of corrosive elements and flammable materials. □ Centrally located with the water piping system (For new installations). Located as close to the gas piping and vent pipe system as possible. □ Located indoors and in a vertical position. Protected from freezing temperatures. □ Proper clearances from combustible surfaces maintained and not installed directly on a carpeted floor. □ Provisions made to protect the area from water damage. Metal drain pan installed and piped to an adequate drain. □ Sufficient room to service the water heater. See Clearances and Accessibility section of this manual. □ Water heater not located near an air moving device. □ Is the installed environment dirty (excessive amounts of lint, dirt, dust, etc.)? If so, the base-ring filter located on the bottom of the water heater will need to be cleaned periodically. Refer to the “Maintenance of your Water Heater” section of this manual for information on cleaning the base-ring filter. Combustion Air Supply and Ventilation Check for sufficient combustion air supply. Insufficient air for the combustion of gas will result in the flame becoming “lazy”, thereby allowing heat to build up in the combustion chamber. This excessive heat will cause a thermal switch on the door assembly to trip. Is the water heater installed in a closet or other small, enclosed space? If so: □ Are there openings for make-up air to enter and exit the room/area? □ Are the openings of sufficient size? Remember, if there are other gas-fired or air-consuming appliances in the same room, you need more make-up air. Refer to the “Installation Instructions” and “Combustion Air Supply and Ventilation” sections for specific requirements. □ Make sure that fresh air is not taken from areas that contain negative pressure producing devices such as exhaust fans, dryers, fireplaces, etc. □ Is there a furnace/air handler in the same room space as the water heater? If so, has a return air duct system been attached that exits the room? If so, check for leaks on the air duct system. If no air duct system is present, correct immediately by contacting a local Heating, Ventilation, Air- Conditioning & Refrigeration (HVAC-R) authorized service provider. □ Use a fresh air supply that is free of corrosive elements and flammable vapors. IMPORTANT INFORMATION ABOUT THIS WATER HEATER This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor ignition incident. The new technology used in meeting these standards makes this product more sensitive to installation errors. Please review the following checklist and make any required installation upgrades or changes. Questions? Contact Sears at 1-800-4-MY-HOME (1-800-469-4663). □ Fresh air openings must be sized correctly with consideration given to the blocking effect of louvers and grilles. □ Ductwork must be the same cross-sectional area as the openings. Vent Pipe System Check for proper drafting at the water heater draft hood. Refer to the “Checking the Draft” section of this manual for the test procedure. If the procedure shows insufficient draft is present, please check the following: □ Draft hood properly installed. □ Vent connectors securely fastened with screws and supported properly to maintain six inch clearance. □ Vent connector made of approved material and sized correctly. □ Vent pipe system installed according to all local and state codes or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition. □ Flue baffle properly positioned in the flue tube. □ Check the vent system for restrictions/obstructions and check the vent termination height. Refer to the “Combustion Air Supply and Ventilation” section of this water heater manual for specific requirements. □ Recheck for sufficient combustion air supply. Water System Piping □ Temperature and pressure relief valve properly installed with a discharge line run to an open drain and protected from freezing. □ All piping properly installed and free of leaks. □ Heater completely filled with water. □ Closed system pressure build-up devices installed. □ Tempering valve (when applicable) installed per manufacturer’s instructions (See “Water Temperature Regulation” section). Gas Supply and Piping □ Gas type is the same as that listed on the water heater rating plate. □ Gas line equipped with shut-off valve, union, and drip leg. □ Use pipe joint compound or teflon tape marked as being resistant to the action of petroleum [Propane (L.P.)] gases. □ Adequate pipe size and approved pipe material. □ An approved noncorrosive leak detection solution used to check all connections and fittings for possible gas leaks. Correct any leak found.
12 INSTALLATION INSTRUCTIONS Removing the Old Water Heater FIGURE 2. 1. Turn “OFF” the gas supply to the water heater. If the main gas line shutoff valve serving all gas appliances is used, also shut “OFF” the gas at each appliance. Leave all gas appliances shut “OFF” until the water heater installation is completed. See Figures 2 and 3. 2. Turn “OFF” the water supply to the water heater at the water shut off valve or water meter. Some installations require that the water be turned off to the entire house. See Figures 2 and 4. 3. Check again to make sure the gas supply is “OFF” to the water heater. Then disconnect the gas supply connection from the gas control valve. 4. Attach a hose to the water heater drain valve and put the other end in a fl oor drain or outdoors. (See Figures 2 and 5.) Open the water heater drain valve. Open a nearby hot water faucet which will relieve pressure in the water heater and speed draining. The water passing out of the drain valve may be extremely hot. To avoid being scalded, make sure all connections are tight and that the water fl ow is directed away from any person. 5. Disconnect the vent pipe from the draft hood where it connects to the water heater. In most installations the vent pipe can be lifted off after any screw or other attached devices are removed. Dispose of the draft hood. The new water heater has a draft hood which must be used for proper operation. 6. If you have copper piping to the water heater, the two copper water pipes can be cut with a hacksaw approximately four inches away from where they connect to the water heater. See Figure 6. This will avoid cutting off pipes too short. Additional cuts can be made later if necessary. Disconnect the temperature-pressure relief valve drain line. When the water heater is drained, disconnect the hose from the drain valve. Close the drain valve. The water heater is now completely disconnected and ready to be removed. FIGURE 6. If you have galvanized pipes to the water heater, loosen the two galvanized pipes with a pipe wrench at the union in each line. Also disconnect the piping remaining to the water heater. See Figure 7. These pieces should be saved since they may be needed when reconnecting the new water heater. Disconnect the temperature-pressure relief valve drain line. When the water heater is drained, disconnect the hose from the drain valve. Close the drain valve. The water heater is now completely disconnected and ready to be removed. Mineral buildup or sediment may have accumulated in the old water heater. This causes the water heater to be much heavier than normal and this residue, if spilled out, could cause staining. FIGURE 7. FIGURE 3. FIGURE 4. FIGURE 5.CHECK WITH LOCAL UTILITY FOR MINIMUM HEIGHT 3” MINIMUM DRIP LEG GROUND JOINT UNION SUITABLE DRAIN MANUAL GAS SHUT-OFF VALVE 6” MAXIMUM AIR GAP DISCHARGE PIPE (DO NOT CAP OR PLUG) 1 2 3 4 56
13 Location Requirements Carbon Monoxide Poisoning Hazard WARNING Do not install in a mobile home. Doing so can result in carbon monoxide poisoning and death. The FVIR System is designed to reduce the risk of flammable vapor-related fires. The patented system protects your family by trapping the burning vapors within the water heater combustion chamber through the special flame-arrestor. The burning vapors literally “burn themselves out” without escaping back into the room. In the event of a flammable vapor incident, the FVIR System disables the water heater by shutting off the gas supply to the water heater’s burner and pilot, preventing re-ignition of any remaining flammable vapors in the area. This will not prevent a possible fire/explosion if the igniter is depressed and flammable vapors have accumulated in the combustion chamber with the pilot light off. If you suspect a flammable vapor incident has occurred, do not use this appliance. Do not attempt to light this appliance, or depress the igniter button if you suspect flammable vapors have accumulated inside or outside the appliance. Immediately call a qualified technician to inspect the appliance. Water heaters subjected to a flammable vapors incident will show a discoloration on the flame-arrestor and require replacement of the entire water heater. FIRE AND EXPLOSION HAZARD Can result in serious injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Storage of or use of gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance can result in serious injury or death. Fl ammable VaporsFLAMMABLES Read and follow water heater warnings and instructions. WARNING Do not use or store flammable products such as gasoline, solvents, or adhesives in the same room or area near the water heater. If such flammables must be used, all gas burning appliances in the vicinity must be shut off and their pilot lights extinguished. Open the doors and windows for ventilation while flammable substances are in use. If flammable liquids or vapors have spilled or leaked in the area of the water heater, leave the area immediately and call the fire department from a neighbor’s home. Do not attempt to clean the spill until all ignition sources have been extinguished. Fire or Explosion Hazard WARNING • Read instruction manual before installing, using or servicing water heater. • Improper use may result in fire or explosion. • Maintain required clearances to combustibles. Keep combustibles such as boxes, magazines, clothes, etc. away from the water heater area. Site Location • Select a location near the center of the water piping system. The water heater must be installed indoors and in a vertical position on a level surface. DO NOT install in bathrooms, bedrooms, or any occupied room normally kept closed. • Locate the water heater as close to the chimney or gas vent as practical. Consider the vent system piping and combustion air supply requirements when selecting the water heater location. The venting system must be able to run from the water heater to termination with minimal length and elbows. • Locate the water heater near the existing gas piping. If installing a new gas line, locate the water heater to minimize the pipe length and elbows. • The water heater should be located in an area not subject to freezing temperatures. Water heaters located in unconditioned spaces (i.e., attics, basements, etc.) may require insulation of the water piping and drain piping to protect against freezing. The drain and controls must be easily accessible for operation and service. Maintain proper clearances as specified on the rating plate. • Do not locate the water heater near an air-moving device. The operation of air-moving devices such as exhaust fans, ventilation systems, clothes dryers, fireplaces, etc., can affect the proper operation of the water heater. Special attention must be given to conditions these devices may create. Flow reversal of flue gases may cause an increase of carbon monoxide inside of the dwelling (Figure 8). • If the water heater is located in an area that is subjected to lint and dirt, it may be necessary to periodically clean the base-ring filter and flame-arresto r (s e e E x te r n a l I ns p e c t i o n & Cleaning of the Flame-arrestor). • This water heater is not for use in manufactured (mobile) homes or outdoor installation. NOTE: This water heater must be installed according to all local and state codes or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition. REVERSE FLOW OF GASES EXHAUST FAN FIGURE 8
14 IMPORTANT: The water heater should be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the water heater or to lower floors of the structure. Due to the normal corrosive action of water, the tank will eventually leak after an extended period of time. Also any external plumbing leak, including those from improper installation, may cause early failure of the tank due to corrosion if not repaired. If the homeowner is uncomfortable with making the repair a qualified technician should be contacted. A suitable metal drain pan should be installed under the water heater as shown below, to help protect the property from damage which may occur from condensate formation or leaks in the piping connections or tank. The pan must limit the water level to a maximum depth of 1-3/4” and be two inches wider than the heater and piped to an adequate drain. NOTE: The pan must not restrict combustion air flow. Locate the water heater near a suitable indoor drain. Outside drains are subject to freezing temperatures which can obstruct the drain line. The piping should be at least 3/4” ID and pitched for proper drainage. METAL DRAIN PAN AT LEAST 2” GREATER THAN THE DIAMETER OF THE WATER HEATER.PIPED TO AN ADEQUATE DRAIN FIGURE 9. Water heater life depends upon water quality, water usage, water temperature and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a drain pan piped to a drain. However, unanticipated damage can be reduced or prevented by a leak detector or water shut-off device used in conjunction with a piped drain pan. These devices are available from some plumbing supply wholesalers and retailers, and detect and react to leakage in various ways: • Sensors mounted in the drain pan that trigger an alarm or turn off the incoming water to the water heater when water is detected. • Sensors mounted in the drain pan that turn off the water supply to the entire home when water is detected in the drain pan. • Water supply shut-off devices that activate based on the water pressure differential between the cold water and hot water pipes connected to the water heater. • Devices that will turn off the gas supply to a gas water heater while at the same time shutting off its water supply. Insulation Blankets Insulation blankets available to the general public for external use on gas water heaters are not necessary with Kenmore products. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. Your Kenmore water heater meets or exceeds the National Appliance Energy Conservation Act standards with respect to insulation and standby loss requirements, making an insulation blanket unnecessary. WARNING Should you choose to apply an insulation blanket to this heater, you should follow these instructions (See Figure 1 for identification of components mentioned below). Failure to follow these instructions can restrict the air flow required for proper combustion, potentially resulting in fire, asphyxiation, serious personal injury or death. • Do not apply insulation to the top of the water heater, as this will interfere with safe operation of the draft hood. • Do not cover the outer door, thermostat or temperature & pressure relief valve. • Do not allow insulation to come within 2” (50.8 mm) of the floor to prevent blockage of combustion air flow to the burner. • Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference. • Do obtain new warning and instruction labels from Sears for placement on the blanket directly over the existing labels. • Do inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air flow. Clearances and Accessibility NOTE: Minimum clearances from combustible materials are stated on the label adjacent to the gas control valve/thermostat of the water heater. The water heater is certified for installation on a combustible floor. • IMPORTANT: If installing over carpeting, the carpeting must be protected by a metal or wood panel beneath the water heater. The protective panel must extend beyond the full width and depth of the water heater by at least three inches (76.2mm) in any direction; o r i f i n a n a l c ove o r c l o s et installation, the entire floor must be covered by the panel. • Figure 10 may be used as a reference guide to locate the specific clearance locations. A minimum of 24 inches of front clearance should be provided for inspection and service.
15 BACK SIDES TOP VIEWSIDESVENT FRONT 24” MINIMUM FOR SERVICETOP TO CEILING FIGURE 10. Filling the Water Heater Never use this water heater unless it is completely full of water. To prevent damage to the tank, the tank must be fi lled with water. Water must fl ow from the hot water faucet before turning “ON” gas to the water heater. To fi ll the water heater with water: • Close the water heater drain valve by turning the handle to the right (clockwise). The drain valve is on the lower front of the water heater. Explosion Hazard • Use a new CSA approved gas supply line. • Install a shut-off valve. • Do not connect a natural gas water heater to an L.P. gas supply. • Do not connect an L.P. gas water heater to a natural gas supply. • Failure to follow these instructions can result in death, explosion, or carbon monoxide poisoning. WARNING Gas Requirements IMPORTANT: Read the rating plate to be sure the water heater is made for the type of gas you will be using in your home. This information will be found on the rating plate located near the gas control valve/thermostat. If the information does not agree with the type of gas available, do not install or light. Call your dealer. NOTE: An odorant is added by the gas supplier to the gas used by this water heater. This odorant may fade over an extended period of time. Do not depend upon this odorant as an indication of leaking gas. Gas Piping The gas piping must be installed according to all local and state GAS SUPPLY codes or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition. Tables 1 and 2 on the following page provide a sizing reference for commonly used gas pipe materials. Consult the “National Fuel Gas Code” for the recommended gas pipe size of other materials. NOTE: Use pipe joint compound or teflon tape marked as being resistant to the action of petroleum [Propane (L.P.)] gases. (See Figure 11.) 1. Install a readily accessible manual shut-off valve in the gas supply line as recommended by the local utility. Know the location of this valve and how to turn off the gas to this unit. 2. Install a drip leg (if not already incorporated as part of the water heater) as shown. The drip leg must be no less than three inches long for the accumulation of dirt, foreign material, and water droplets. 3. Install a ground joint union between the gas control valve/ thermostat and the manual shut-off valve. This is to allow easy removal of the gas control valve/ thermostat. 4. Turn the gas supply on and check for leaks. Test all connections by brushing on an approved noncorrosive leak-detection solution. Bubbles will show a leak. Correct any leak found. CHECK WITH LOCAL UTILITY FOR MINIMUM HEIGHT 3” MINIMUM DRIP LEG GROUND JOINT UNION SUITABLE DRAIN MANUAL GAS SHUT-OFF VALVE FIGURE 11. • Open the cold water supply valve to the water heater. NOTE: The cold water supply valve must be left open when the water heater is in use. • To ensure complete fi lling of the tank, allow air to exit by opening the nearest hot water faucet. Allow water to run until a constant fl ow is obtained. This will let air out of the water heater and the piping. • Check all water piping and connections for leaks. Repair as needed.
16 Gas Pressure WARNING Explosion Hazard • Gas leaks can not always be detected by smell. • Gas suppliers recommend that you use a gas detector approved by UL or CSA. • For more information, contact your gas supplier. • If a gas leak is detected, follow the “What to do if you smell gas” instructions on the cover of this manual. IMPORTANT: The gas supply pressure must not exceed the maximum supply pressure as stated on the water heater’s rating plate. The minimum supply pressure is for the purpose of input adjustment. Gas Pressure Testing IMPORTANT: This water heater and its gas connection must be leak tested before placing the appliance in operation. • If the code requires the gas lines to be tested at a pressure exceeding 14” W.C., the water heater and its manual shut-off valve must be disconnected from the gas supply piping system and the line capped. • If the gas lines are to be tested at a pressure less than 14” W.C., the water heater must be isolated from the gas supply piping system by closing its manual shut-off valve. NOTE: Air may be present in the gas lines and could prevent the pilot from lighting on initial start-up. The gas lines should be purged of air by a qualified technician after installation of the gas piping system. While purging the gas piping system of air, ensure that the fuel is not spilled in the area of the water heater installation, or any source of ignition. If the fuel is spilled while purging the piping system of air follow the “WHAT TO DO IF YOU SMELL GAS” instructions on the cover of this manual. LP Gas Only WARNING Explosion Hazard Have a qualified person make sure L.P. gas pressure does not exceed 13” water column. Examples of a qualified person include: licensed plumbers, authorized gas company personnel, and authorized service personnel. Failure to do so can result in death, explosion, or fire. Liquefied petroleum gas is over 50% heavier than air and in the occurrence of a leak in the system, the gas will settle at floor level. Basements, crawl spaces, closets and areas below ground level will serve as pockets for the accumulation of gas. Before lighting an L.P. gas water heater, smell all around the appliance at floor level. If you smell gas, follow the instructions as given in the warning on the front page. When your L.P. tank runs out of fuel, turn off the gas at all gas appliances including pilot lights. After the tank is refi lled, all appliances must be re-lit according to their manufacturer’s instructions.
17 Carbon Monoxide Warning Follow all the local and state codes or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1 (NFPA 54)- current edition to properly install vent system. Failure to do so can result in death, explosion, or carbon monoxide poisoning. WARNING IMPORTANT: Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to corrosive elements in the atmosphere is excluded from warranty coverage. The following types of installation (not limited to the following) will require outdoor air for combustion due to chemical exposure and may reduce but not eliminate the presence of corrosive chemicals in the air: • beauty shops • photo processing labs • buildings with indoor pools • water heaters installed in laundry, hobby, or craft rooms • water heaters installed near chemical storage areas Combustion air must be free of acid-forming chemicals such as sulfur, fluorine, and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint, and varnish removers, refrigerants, and many other commercial and household products. When burned, vapors from these products form highly corrosive acid compounds. These products should not be stored or used near the water heater or air inlet. Combustion and ventilation air requirements are determined by the location of the water heater. The water heater may be located in either an open (unconfined) area or in a confined area or small enclosure such as a closet or small room. Confined spaces are areas with less than 50 cubic feet for each 1,000 BTUH of the total input for all gas-using appliances. Unconfined Space A water heater in an unconfined space uses indoor air for combustion and requires at least 50 cubic feet for each 1,000 BTUH of the total input for all gas appliances. The table below shows a few examples of the minimum square footage (area) required for various BTUH inputs. TABLE 3 BTUH InputMinimum Square Feet with 8’ CeilingTypical Room with 8’ Ceiling 30,000 188 9 x 21 45,000 281 14 x 20 60,000 375 15 x 25 75,000 469 15 x 31 90,000 563 20 x 28 105,000 657 20 x 33 COMBUSTION AIR SUPPLY & VENTILATION TABLE 3 120,000 750 25 x 30 135,000 844 28 x 30 IMPORTANT: • The area must be open and be able to provide the proper air requirements to the water heater. Areas that are being used for storage or contain large objects may not be suitable for water heater installation. • Water heaters installed in open spaces in buildings with unusually tight construction may still require outdoor air to function properly. In this situation, outside air openings should be sized the same as for a confined space. • Modern home construction usually requires supplying outside air into the water heater area. Confined Space For the correct and proper operation of this water heater, ample air must be supplied for the combustion, ventilation, and dilution of flue gases. Small enclosures and confined areas must have two permanent openings so that sufficient fresh air can be drawn from outside of the enclosure. One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure as shown in Figure 12. The size of each opening (free area) is determined by the total BTUH input of all gas utilization equipment (i.e., water heaters, furnaces, clothes dryers, etc.) and the method by which the air is provided. The BTUH input can be found on the water heater rating plate. Additional air can be provided by two methods: 1. All air from inside the building. 2. All air from outdoors. 12” MAXIMUM PERMANENT OPENINGS TO THE OUTSIDE OR ADDITIONAL ROOMS WITHIN THE BUILDINGCLOSET OR OTHER CONFINED SPACE 12” MAXIMUM FIGURE 12. All Air from Inside the Building When additional air is to be provided to the confined area from additional room(s) within the building, the total volume of the room(s) must be of sufficient size to properly provide the necessary amount of fresh air to the water heater and other
18 TABLE 4 Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply - All Air from Outdoors Only. Based on total BTUH input rating for all utilizing equipment within the confi ned space. Opening SourceMinimum Free Area Per Opening (sq. in.)Reference Drawing * D i r e c t t o o u t d o o r s 1 sq. in, per 4000 BTUH F i g u r e 14 Ve r t i c a l D u c t s 1 sq. in, per 4000 BTUH F i g u r e 15 H o r i z o n t a l D u c t s 1 sq. in, per 2000 BTUH F i g u r e 16 S i n g l e O p e n i n g 1 sq. in, per 3000 BTUH F i g u r e 17 Example: A water heater with an input rating of 50,000 BTUH using horizontal ducts would require each opening to have a minimum free area of 25 square inches. Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25 sq. in. * These openings connect directly with the outdoors through a ventilated attic, a ventilated crawl space, or through an outside wall. Consult the local codes of your area for specific ventilation and combustion air requirements. GABLE VENT TO OUTDOORS INSTALL ABOVE INSULATION CONFINED SPACE ALTERNATE AIR INLETOUTLET AIR TO ATTIC 1 SQ. INCH PER 4000 BTUH INLET AIR FROM THE CRAWL SPACE OPEN FOUNDATION VENT 1 SQ. INCH PER 4000 BTUH ALL AIR FROM OUTDOORS: INLET AIR FROM VENTILATED CRAWL SPACE/OUTLET AIR TO VENTILATED ATTIC FIGURE 14. GABLE VENT TO OUTDOORS INSTALL ABOVE INSULATION CONFINED SPACEOUTLET AIR TO ATTIC 1 SQ. INCH PER 4000 BTUH INLET AIR DUCT 1 SQ. INCH PER 4000 BTUH 12” MAXIMUM ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC FIGURE 15. gas utilization equipment in the area. If you are unsure that the structure meets this requirement, contact your local gas utility company or other qualified agency for a safety inspection. Each of the two openings shall have a minimum free area of 1 square inch per 1,000 BTUH of the total input rating of all gas utilization equipment in the confined area, but not less than 100 square inches (Figure 13). CONFINED SPACE PERMANENT OPENINGS 1 SQUARE INCH/1000 BTUH (MINIMUM 100 SQ. IN.) FIGURE 13. All Air from Outdoors Outdoor fresh air can be provided to a confined area either directly or by the use of vertical and horizontal ducts. The fresh air can be taken from the outdoors or from crawl or attic spaces that freely communicate with the outdoors. Attic or crawl spaces cannot be closed and must be properly ventilated to the outside. Ductwork must be of the same cross-sectional area as the free area of the opening to which they connect. The minimum dimension of rectangular air ducts cannot be less than three inches. The size of each of the two openings is determined by the method in which the air is to be provided. Refer to Table 4 to calculate the minimum free area for each opening. Figures 14, 15, 16 and 17 are typical examples of each method. Louvers and Grilles In calculating free area for ventilation and combustion air supply openings, consideration must be given to the blocking effect of protection louvers, grilles, and screens. These devices can reduce airflow, which in turn may require larger openings to achieve the required minimum free area. Screens must not be smaller than 1/4” mesh. If the free area through a particular design of louver or grille is known, it should be used in calculating the specified free area of the opening. If the design and free area are not known, it can be assumed that most wood louvers will allow 20 - 25% of free area while metal louvers and grilles will allow 60 - 75% of free area. Louvers and grilles must be locked open or interconnected with the equipment so that they are opened automatically during equipment operation. Keep louvers and grilles clean and free of debris or other obstructions.
19 1 SQ. INCH PER 2000 BTUH CONFINED SPACE 1 SQ. INCH PER 2000 BTUHINLETOUTLET OUTDOOR AIR DUCTS ALL AIR FROM OUTDOORS USING HORIZONTAL DUCTS FIGURE 16. ALTERNATIVE OPENING LOCATION 1 SQ. INCH PER 3000 BTUH CONFINED SPACE ALL AIR FROM OUTDOORS - USING A SINGLE PERMANENT OPENING FIGURE 17. Vent Pipe System This water heater uses a non-direct, single-pipe vent system to remove exhaust gases created by the burning of fossil fuels. Air for combustion is taken from the immediate water heater location or is ducted in from the outside (see “Combustion Air Supply and Ventilation”). This water heater must be properly vented for the removal of exhaust gases to the outside atmosphere. Correct installation of the vent pipe system is mandatory for the proper and efficient operation of this water heater and is an important factor in the life of the unit. The vent pipe must be installed according to all local and state codes or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition. The vent pipe installation must not be obstructed so as to prevent the removal of exhaust gases to the outside atmosphere. IMPORTANT: The use of vent dampers is not recommended by the manufacturer of this water heater. Although some vent dampers are certified by CSA International, this certification applies to the vent damper device only and does not mean they are certified for use on this water heater. U.L. recognized fuel gas and carbon monoxide (CO) detectors are recommended in all applications and should be installed using the manufacturer’s instructions and local codes, rules, or regulations. IMPORTANT: If you lack the necessary skills required to properly install this venting system, you should not proceed, but get help from a qualified technician. Draft Hood Installation SHEET METAL SCREWS (FOUR PROVIDED) DRAFT HOOD LEGS LEGS SLOT SLOT JACKET TOP INSTALL THE DRAFT HOOD WITH THE FOUR SCREWS PROVIDED. FIGURE 18. Align the legs of the draft hood with the slots provided. Insert the legs and secure the draft hood to the water heater’s top with the four screws provided as shown in Figure 18. Do not alter the draft hood in any way. If you are replacing an existing water heater, be sure to use the draft hood supplied with this water heater. Vent Pipe Size It is important that you follow the guidelines in these instructions for sizing a vent pipe system. If a transition to a larger vent size is required, the vent transition connection must be made at the draft hood outlet. Vent Connectors 1. Type B, Double wall, U.L. Listed Vent Pipe. 2. Single wall Vent Pipe. Maintain the manufacturer’s specified minimum clearance from combustible materials when using type B double wall vent pipe. Vent connectors made of type B, double wall vent pipe material may pass through walls or partitions constructed of combustible material if the minimum listed clearance is maintained. Maintain a six inch minimum clearance from all combustible materials when using single wall vent pipe. IMPORTANT: Single wall vent pipe cannot be used for water heaters located in attics and may not pass through attic spaces, crawl spaces or any confined or inaccessible location. A single wall metal vent connector cannot pass through any interior wall. When installing a vent connector, please note the following (See Figures 19-21): • Install the vent connector avoiding unnecessary bends, which create resistance to the flow of vent gases. • Install without dips or sags with an upward slope of at least 1/4-inch per foot. • Joints must be fastened by sheet metal screws or other approved means. It must be supported to maintain clearances and prevent separation of joints and damage. • The length of the vent connector cannot exceed 75% of the ver tical vent height.
20 separation, and maintain clearances to combustible materials (Figures 20 and 21). IMPORTANT: This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases. An unused chimney flue or masonry enclosure may be used as a passageway for the installation of a gas vent (Figure 21). Common (combined) venting is allowable with vertical type B vent systems and lined masonry chimneys as long as proper draft for the water heater is established under all conditions of operation. CAUTION: DO NOT common vent this water heater with any power vented appliance. Figures 19-21 are examples of vent pipe system installations and may or may not be typical for your specific application. Consult the “National Fuel Gas Code”, NFPA 54, ANSI Z223.1- current edition and the guidelines set forth by prevailing local codes. VERTICAL GAS VENT SYSTEM WITH TYPE B DOUBLE WALL VENT PIPE. 3 FT. MINIMUM LISTED VENT CAP 2 FT. MINIMUM ABOVE ANY OBJECT WITHIN 10 FT. HORIZONTALLY TYPE B DOUBLE WALL VENT PIPE **MAINTAIN SPECIFIED CLEARANCE VENT CONNECTOR SLOPE UP 1/4 IN. PER FT. MINIMUM *MAINTAIN CLEARANCE SUPPORT STRAP FIGURE 20. VENTING THROUGH A CHIMNEY WITH TYPE B DOUBLE WALL VENT PIPE.5 FT. MINIMUMLISTED VENT CAP VENT CONNECTOR UNUSED CHIMNEY FLUE OR MASONRY ENCLOSURE SEAL *MAINTAIN CLEARANCE VENT CONNECTOR SLOPE UP 1/4 IN. PER FT. MINIMUM**MAINTAIN SPECIFIED CLEARANCE SUPPORT STRAP FIGURE 21. * Maintain vent pipe clearance requirements to local, state and/or the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition. ** NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances states that these chimneys are intended to be installed in accordance with the installation instructions provided with each chimney support assembly. Minimum air space clearance to combustible materials should be maintained as marked on the chimney sections. • The vent connector must be accessible for cleaning, inspection, and replacement. • Vent connectors cannot pass through any ceiling, floor, firewall, or fire partition. • It is recommended (but not mandatory) that a minimum 12 inches of vertical vent pipe be installed on the draft hood prior to any elbow in the vent system. IMPORTANT: Existing vent systems must be inspected for obstructions, corrosion, and proper installation. Chimney Connection IMPORTANT: Before connecting a vent to a chimney, make sure the chimney passageway is clear and free of obstructions. The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces. Also consult local and state codes for proper chimney sizing and application or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition. • The connector must be installed above the extreme bottom of the chimney to prevent potentially blocking the flue gases. • The connector must be firmly attached and sealed to prevent it from falling out. • To aid in removing the connector, a thimble or slip joint may be used. • The connector must not extend beyond the inner edge of the chimney as it may restrict the space between it and the opposite wall of the chimney (Figure 19). LISTED LINED CHIMNEY 2 FT. MINIMUM ABOVE ANY OBJECT WITHIN 10FT. HORIZONTALLY DO NOT EXTEND VENT BEYOND EDGE OF CHIMNEY VENT CONNECTOR 3 FT. MINIMUM MAINTAIN CLEARANCE* SEAL SLOPE UP 1/4 IN. PER FT. MINIMUM CHIMNEY TERMINATION VENT SYSTEM SUPPORT STRAP FIGURE 19. Do not terminate the vent connector in a chimney that has not been certified for this purpose. Some local codes may prohibit the termination of vent connectors in a masonry chimney. Vertical Exhaust Gas Vent Vertical exhaust gas vents must be installed with U.L. listed type B vent pipe according to the vent manufacturer’s instructions and the terms of its listing. It must be connected to the water heater’s draft hood by a listed vent connector or by directly originating at the draft hood opening. Vertical gas vents must terminate with a listed cap or other roof assembly and be installed according to their manufacturer’s instructions. Gas vents must be supported to prevent damage, joint