Home > Honeywell > Thermostat > Honeywell Sundial RF Pack 1 Wireless Enabled Timer and Thermostat User Manual

Honeywell Sundial RF Pack 1 Wireless Enabled Timer and Thermostat User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Sundial RF Pack 1 Wireless Enabled Timer and Thermostat User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							21
    DT92E OPERATING INDICATORS
    Low Battery Indicator / Battery Replacement
    The battery symbol will start 
    to flash if the battery power is 
    running low. From this point, 
    there will be a minimum of 4 
    weeks before the product will 
    cease to function.
    Batteries are accessed by 
    unclipping the front cover at the 
    bottom. Note battery polarity. 
    Reverse process to refit front 
    cover.
    Use 2xLR6 (AA) alkaline 
    batteries only. 
    Immediately on power up, DT92E will try to communicate and synchronise with 
    ST9120C. This process may take up to 4 minutes, and will be indicated by the word 
    ‘Sync’ on the DT92E display.
    RF Communications Indicator
    A brief flash of the RF symbol  indicates the DT92E 
    has been communicating with the other system 
    controls.
    Lockout
    Your DT92E works in conjunction with the ST9120C 
    time control. If the timer is set to OFF or CONT it may 
    not be possible to override it from the thermostat 
    and this is indicated by the lockout symbol 
    . To 
    switch the heating on you must go to the timer and 
    set the Mode to AUTO, ONCE, or CONT. 
    2 x LR6 AA Alkaline
    1
    2 
    						
    							22
    DT92E ENERGY SAVING ECO FEATURE
    The ECO button allows you to change to a lower, energy saving set temperature for 
    a period of your choice, from 1 to 24 hours. This temperature is pre-set in the DT92E 
    Installer Mode, but you can adjust this to any temperature you want when ECO mode 
    has been activated. The default ECO temperature is 18°C.
    At the end of the time period, the thermostat will return to its original set 
    temperature.
    Entering ECO Mode and Setting 
    the Energy Saving Time Period
    Press the green ECO button to enter ECO 
    mode. The word ECO will appear on the 
    display and the thermostat will allow you to 
    set the number of hours you want to be at 
    the new set temperature.
    Use the 
     and  buttons to set the hours, 
    up to a maximum of 24 hours.
    Please note – ECO mode is not accessible 
    in Holiday mode or if Service shutdown 
    has occurred.
    What Happens in ECO Mode?
    In ECO mode, the display will show a 
    countdown of the remaining time (hours 
    and minutes) in ECO mode, identified by 
    the hourglass symbol. The display will 
    alternate every 5 seconds to show the 
    current room temperature.
    When in ECO mode, pressing the 
     or  
    buttons will adjust the set temperature for 
    the remainder of the ECO time period. 
    5 s 5 s
    5 s
    1,2,3,4....,24hr 
    						
    							23
    DT92E ENERGY SAVING ECO FEATURE
    FINE TUNING YOUR  DT92E
    Changing the DT92E Installer Parameters
    The DT92E has a special Installer Mode where some features can be adjusted to suit 
    your lifestyle or preferences – these are called Installer Parameters, and are listed in 
    the table below, along with a description of the options that are possible.
    Your installer should set this up for you to suit your application (see \
    CONFIGURATION 
    & SERVICE DATA section). However, you may wish to alter some of the settings 
    yourself, and this section shows you how to do this.
    INSTALLER 
    PARAMETERParameter
    Default 
    Value Options
    Description
    Temperature 
    measurement offset t0
    0-3 to 3 K Offset to measured 
    temperature
    Upper setpoint limit uL3521 to 
    35°C Upper set temperature 
    limit in °C
    Lower setpoint limit LL55 to 21°C Lower set temperature 
    limit in °C
    Energy saving ECO 
    setpoint ES
    185 to 35°C Energy saving ECO set 
    temperature in °C
    Reset parameters 
    to factory settings FS
    10, 1Parameter will be set to 0 
    if any of the other param-
    eter values have been 
    changed. Set to 1 to get 
    back to factory settings.
    How to Exit ECO Mode
    To exit ECO mode, simply press the green 
    ECO button again. ECO will disappear 
    from the display and the thermostat will 
    control to its previous set temperature. 
    						
    							24
    To Enter Installer Mode:
    a. Hold the 
     button for 2 seconds until DT92E is in standby mode.
    b. Hold 
     and  buttons for 3 seconds until the word ‘Inst’ appears on the 
    display.
    c.  Press the 
     button.
    The first parameter is now ready to be changed.
    To Select a Parameter:
    Use the 
     and  buttons to move from one parameter 
    to the next. Stop at the Parameter you wish to change.
    To Change a Parameter:
    Use the standby button to select the parameter value, then the 
     and  buttons to 
    change the value. Confirm the change by pressing the  button again to take you 
    back to the parameter.
    To Exit Installer Mode:
    Hold the 
     button for 3 
    seconds to exit Installer 
    Mode.
    Note: The Installer Mode will 
    exit automatically after 10 
    minutes if  no adjustments 
    have been made in this 
    time.
    FINE TUNING YOUR  DT92E
    3 s
    3 s
    2 s 
    						
    							25
    Automatic Operation
    The BDR91T relay box simply switches the boiler on 
    and off according to a wireless signal it receives from 
    the ST9120C timer. It is mainly used when the boiler 
    is installed  in a remote location where it may be 
    difficult to run wires direct from the timer. The green 
    light indicates the status of the relay output:
    Green light on = relay on
    Green light off = relay off
    Temporary Manual Override
    In normal operation it should not be necessary to 
    interact with the BDR91T. However it is possible to 
    press the button and temporarily override the current 
    relay position. This will be cancelled as soon as the 
    Relay Box receives another signal from the ST9120C 
    timer, because automatic operation has a higher 
    priority than manual operation.
    Loss of Wireless Communications
    If the RF communication is lost for a period of 1 hour the red light will illuminate.
    The Relay Box will then enter the failsafe mode as selected by your Installer (see 
    page 30).
    When RF communication is restored, the Relay Box will automatically return to 
    normal operation.
    OPERATING YOUR BDR91T RELAY BOX (IF INSTALLED)
    Green LED
    Red LED
    Push button 
    						
    							26
    FAQ  AND TROUBLESHOOTING
    How do I set the time only, if the ST9120C clock is not correct?
    Your ST9120C contains an accurate digital clock that is factory set. Should you ever 
    need to change the time, just follow this procedure:
    a. Move the slider to the DAY/TIME position.
    b.  Keep pressing the green 
     button until the message ‘SET THE TIME’ is 
    displayed. To change the time, press the   or  buttons until the correct 
    time is shown. The message ‘IS TIME OK?’ will be displayed. Press the green  
    button to confirm the time is correct.  If you have made a change, the message 
    ‘TIME SAVED’ will show, followed quickly by ‘DATE + TIME COMPLETE’.
    c.  Move the slider to the RUN  position, to complete changing the time.
    What do I do when the clocks go back in October and forward 
    in March?
    Your ST9120C is factory set to change the clock automatically at the correct dates, 
    so you should never need to adjust the clock forward or backwards yourself. It is 
    possible to disable this particular feature, as described in the section ‘Changing the 
    Installer Parameters’ (page 15). You may also check the section ‘Configuration & 
    Service Data’ (page 30) to see how your Installer has configured your product.
    What should I do if I get ‘lost’ while programming the ST9120C?
    The LoT™ Display on ST9120C will provide you with help and tips to work through 
    the programming. Should you ever get ‘lost’, the simplest thing to do is\
     to move the 
    slider to the RUN  position, and then move it back to the appropriate programming 
    position where you got lost. At this point just follow the instructions again.
    What happens if there is a power failure?
    In the event of a mains power failure, the ST9120C display will go blank, the 
    indicator lamps will go out, and the control outputs will switch off. The real time 
    will be constantly maintained by means of the built-in battery backup, ready to 
    power back up as if nothing had happened when the mains power is restored. In 
    addition, all programmes and settings are stored in a special memory (called Non 
    Volatile  memory) which requires no power to maintain information so will be retained 
    indefinitely.
    Should the correct time and date ever be lost, for whatever reason, the message ‘SET 
    DATE + TIME’ will be displayed whilst the slider is in the RUN  position. In this case, 
    simply follow the procedure described under ‘Step 1: Setting the Date & Time’ 
    (page 6). It should not be necessary to make any changes to your programmes. 
    						
    							27
    FAQ  AND TROUBLESHOOTING
    How reliable is 2-way RF communication?
    The 2-way RF communication (also known as wireless communication) used by 
    Honeywell is extremely robust and reliable. When installed correctly the Signal 
    Strength test feature allows the Installer to locate the system components where 
    mutual signal reception is strong. During communication, signals are sent several 
    times to ensure receipt, and if any message is garbled, the error detection software 
    recognises this and ensures the message is repeated again.
    What do I do if RF communication is lost?
    Follow the steps in the Troubleshooting Guide on the next page. The most likely 
    cause for loss of communications is the DT92E batteries running low on p\
    ower. This 
    will be indicated on the DT92E display by a flashing battery symbol, or the display 
    may even be blank. Simply replace the batteries (as shown on page 21) and wait a 
    few minutes for communications to become re-established.
    If this does not resolve the problem it may be that the RF signal path between 
    the ST9120C and the DT92E is blocked by a metal object. Check the direct path 
    between the two devices and reposition any object that may be blocking the signal, 
    or move the thermostat.
    How do I know when to change the batteries in the DT92E 
    room thermostat?
    If the DT92E batteries need changing, the battery symbol will flash on the DT92E 
    display. DT92E will continue to operate for at least 4 weeks after the indicato\
    r begins 
    to flash. The ST9120C will also show the message ‘SENSOR LOW BATT’ and the 
    radiator symbol 
     will flash. It is important to change the DT92E batteries as soon 
    as the low battery condition is indicated, as reduced battery power may affect the 
    RF signal strength and impair RF communications.
    Can I override the Timer from the DT92E thermostat?
    As well as changing the set temperature from the DT92E, it is also possible to 
    override the heating system on or off from the DT92E.  This is only possible if the 
    ST9120C is in AUTO or ONCE Modes. If ST9120C is in CONT mode it will not\
     be 
    possible to switch the heating off from the DT92E. Similarly, if ST9120C is in OFF 
    mode, it will not be possible to switch the heating on from the DT92E. If these latter 
    overrides are required it is first necessary to change the ST9120C mode setting to 
    AUTO or ONCE. 
    						
    							28
    FAQ  AND TROUBLESHOOTING
    Troubleshooting Guide
    This is a quick guide to help you diagnose and cope with possible problems with 
    your wireless control system. For further assistance, please contact your Installer.
    SymptomPossible CauseRemedy
    ST9120C has a blank 
    LCD display No power to the 
    heating systemCheck that there is power to the 
    heating system
    Fault in ST9120C
    Call Installer
    ST9120C indicates 
    the system is ON, but 
    radiators are cold and/
    or taps are running with 
    cold water.
    Temperature controls 
    are switched off or 
    set too lowCheck that the temperature controls in 
    the system are set to appropriate levels
    Boiler or other 
    system controls 
    have malfunctioned Call Installer
    ST9120C shows the 
    message: 
    ‘INTERNAL FAULT’ Fault in ST9120C
    Call Installer
    Every few seconds, the 
    ST9120C screen shows 
    the message:  ST9120C is counting 
    down the number of 
    days until your next 
    boiler service is due.Arrange a boiler service before the 
    counter reaches zero.
    After servicing your boiler, the Service 
    Engineer / Installer will reset the 
    ST9120C to remind you when the next 
    boiler service is due. Each service is 
    normally a maximum of 1 year apart.
    Although the heating 
    is still operating, the 
    ST9120C screen keeps 
    flashing the message:Your boiler service is 
    overdue.
    Arrange an immediate boiler service.
    After servicing your boiler, the Service 
    Engineer / Installer will reset the 
    ST9120C to remind you when the next 
    boiler service is due. Each service is 
    normally a maximum of 1 year apart.
    The ST9120C screen 
    shows the message: Your boiler service 
    is overdue and 
    the boiler has 
    been automatically 
    switched off to 
    ensure your safety.Arrange an immediate boiler service.
    If set to do so, it may be possible to 
    obtain limited use of the boiler by 
    pressing the EXTRA HOUR button. 
    Each button press will allow operation 
    of the boiler for 1 hour at a time, and 
    the screen will display the message 
    ‘On 1h’.
    After servicing your boiler, the Service 
    Engineer / Installer will reset the 
    ST9120C to remind you when the next 
    boiler service is due. Each service is 
    normally a maximum of 1 year apart. 
    						
    							29
    SymptomPossible CauseRemedy
    ST9120C shows the 
    message ‘SENSOR LOW 
    BATT’ and a flashing 
    radiator symbol DT92E batteries 
    are running low on 
    power Change the DT92E batteries (see page 
    21 for how to do this)
    DT92E shows a flashing 
    battery symbol 
    DT92E display is blank
    ST9120C shows the 
    message ‘NO SIGNAL’ 
    and a flashing radiator 
    symbol 
     and DT92E 
    shows a flashing RF 
    symbol 
    DT92E batteries are 
    running low on powerChange the DT92E batteries (see page 
    21 for how to do this)
    RF communication 
    path between 
    ST9120C and 
    DT92E is blocked, 
    possibly by a 
    metal object Check direct path between both 
    products and re-position any objects 
    that may be blocking the signal
    Relocate the DT92E, if possible
    ST9120C shows the 
    message ‘NO SIGNAL’ 
    and a flashing flame 
    symbol 
    Red light on BDR91T 
    (if installed) is lit 
    continuously RF communication 
    path between 
    ST9120C and 
    BDR91T is 
    blocked, possibly 
    by a metal object
    Check direct path between both 
    products and re-position any objects 
    that may be blocking the signal
    ST9120C shows the 
    message ‘SENSOR 
    FAULT’ and a flashing 
    radiator symbol 
    DT92E display shows 
    ‘’ and a flashing 
    spanner symbol   Fault with DT92E
    Call Installer
    Troubleshooting Guide (cont.)
    FAQ  AND TROUBLESHOOTING 
    						
    							3050047645-005 A
    CONFIGURATION & SERVICE DATA
    Configuration Data (to be completed by Installer)
    The tables below are for the Installer to complete to indicate how your ST9120C and 
    DT92E have been configured.
    Application
    Insert application number as per Installation wiring diagrams:
    Configurable FeaturesOptionsFactory 
    settingInstaller configured 
    (tick box or note value)
    ST9120C Configuration - standard
    24hr or am/pm clock 
    display. am/pm display
    24hr display
    Display backlight operation. Off
    on if button pressed
    on continuously
    Automatic time change.disabled,
    enabled
    1-day or 5/2-day or 7-day 
    operation.1-day operation
    5/2-day operation
    7-day operation
    Number of ON/OFFs per 
    day.2 on/offs per day,
    3 on/offs per day
    Default time programme.
    A = standardb = at home
    C = economy
    Hot water set temperature From 40 to 85°C60°C
    Optimum start no optimum start
    delayed start
    optimum start on
    Optimum start limit 1 hour
    2 hours
    3 hours
    Optimum stop disabled
    enabled
    Frost protection temperature From 5 to 16°C5°C
    Minimum ON/OFF time 1, 2, 3, 4, 5 minutes1 minute
    Cycle rate 3, 6, 9, 12 cycles 
    per hour6 cycles
    Proportional band width From 1.5 to 3.0°C1.5°C
    Failsafe mode (loss of RF 
    communications) Off
    On 20% 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell Sundial RF Pack 1 Wireless Enabled Timer and Thermostat User Manual