Home > Honeywell > Alarm system > Honeywell Notifier Nfs28 Manual

Honeywell Notifier Nfs28 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Notifier Nfs28 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							997-492-000-6, Issue 6
    July 20114
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    WARNING High Voltage!
    Take suitable precau-
    tions to avoid electric shock.
    EN 54-2 (and ISO
    7240-2): Section Ref.
    Brief explanation of non-compliance here.
    !
    EN54
    ISO 7240!
    EN54
    ISO
    7240
    1.7 Ancillary Functions
    The following is a list of ancillary functions that are
    provided by the control panel in addition to those required
    by EN 54-2/4. These functions are described in the
    section of this manual as referenced.
    Ancillary Functions Manual
    Section Refs.
    Site specific Setup options 7
    Extend delay timer 7.8
    Sounder Volt-free contact options 7.6
    Relay drive output option 7.6
    1.8 Related Documents
    This manual only describes the installation, commissioning
    and configuration of the control panel. All user functions
    are covered by the EN 54 2-8 Zone Conventional Fire
    Control Panel User Manual (ref. 997-493 -00X).
    1.9 Warnings and Cautions
    Where appropriate, this guide and the remainder of the
    manual include advisory warnings and cautions to remind
    you to consider safety at all times, especially when
    following the procedures described in this manual.
    You are alerted to any areas where hazardous voltages
    are present, or where there may be a risk of damage to
    static-sensitive devices if the recommended procedures
    described in this manual are not followed. An example
    of a high voltage warning and anti-static caution is
    provided to the left of this paragraph.
    The caution at left indicates that it is possible to configure
    a panel in a way that would make it non-compliant with
    the requirements of EN 54 or ISO 7240. This should only
    be done under exceptional circumstances and with the
    authority of the local fire officer.
    The following features are provided by the Power Supply
    Unit (PSU) of the NFS 2-8 and FLS 2-8 fire control panels
    to comply with EN 54-4 and ISO 7240-4.
    Features of the NFS 2-8 & FLS 2-8 Clause
    Power Supply Unit (PSU)
    Derive power from the mains supply 5.1
    Derive power from a standby battery source 5.2
    Charge and monitor the standby
    battery/batteries 5.3
    Detect and signal various PSU faults 5.4 
    						
    							997-492-000-6, Issue 6July 2011
    5
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    2 Installation Guide
    2.1 How to Use this Guide
    This Installation Guide provides you with simple
    guidelines to install a fire control panel system, quickly
    and safely. The guide does not describe panel
    configuration procedures as it is covered by the relevant
    section of this manual.
    For each stage in the panel installation and
    commissioning procedures a brief description is given
    of its purpose, complete with detail drawings, flow
    diagrams and/or other graphics, wherever possible, to
    make the instructions easy to follow.
    2.2 Pre-installation Check List
    Before installing your control panel or fitting detectors,
    you must first ensure that the following criteria have been
    met. Failure to do this may not only result in damage to
    the equipment, but may also cause problems when
    commissioning the equipment or adversely affect its
    performance.
    2.2.1 Some Panel DO’s and DON’T’s
    Before selecting a location for the panel and detectors,
    DO make sure that:
    a) The ambient temperature is in the range:
    +5
    °C to 35°C and
    b) The relative humidity is between: 5% and 95% (non-condensing)
    c. The panel is wall mounted in a position which allows clear visibility of displays and easy access to
    operating controls. The height above floor level should
    be chosen such that the middle of the panel is just
    above normal eye level (approximately 1.5  metres).
    d) DO NOT locate the panel where it is exposed to high levels of moisture 
    						
    							997-492-000-6, Issue 6
    July 20116
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    e) DO NOT locate the panel where there are high levelsof vibration or shock
    f) DO NOT site the panel where there would be restricted access to the internal equipment and
    cabling/wiring connections.
    2.3 Transient Protection
    This equipment contains transient-protection devices.
    Although no system is completely immune from lightning
    transients and interference, for these devices to function
    correctly, and to reduce susceptibility, this equipment
    must be earthed correctly.
    As with all solid state devices, this system may operate
    erratically or can be damaged if subjected to lightning-
    induced transients.
    The use of outside aerial wiring is not recommended
    due to the increased susceptibility to nearby lightning
    strikes. 
    						
    							997-492-000-6, Issue 6July 2011
    7
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    2.4 Product Inspection
    The 2-8 Zone Fire control panel is simple to install and
    commission if the recommended procedures described
    in this Installation Guide, and the Installation and
    Commissioning sections of this manual, are followed.
    Follow all installation instructions described in this
    manual. These instructions must be understood and
    followed to avoid damage to the control panel and
    associated equipment.
    2.4.1 Checking Your Panel for Damage
    Before attempting to install your panel you should do the
    following:
    1
    After removing the control panel from its packaging,
    and before you proceed with installing in its chosen
    location, check for any damage that may have been
    caused during transit.
    Note: In the unlikely event that the panel has been
    damaged in transit, you MUST NOT install it but
    contact your supplier for their returns procedure.
    2.4.2 What to do if Yo u Suspect Your Panel is Damaged
    The procedure described below tells you what to do in
    the unlikely event that the supplied equipment has been
    damaged after leaving the factory. However, if you have
    problems regarding the quality of any supplied order
    items including the control panel, its ancillaries or this
    manual, or items are missing, follow the procedure below.
    1If, after removing the panel from its packaging, a visual
    inspection reveals that it has been damaged, you
    MUST NOT continue with the installation but contact
    your supplier for advice on what to do next.
    Similarly, if the product is found to be faulty during
    installation contact your supplier immediately.
    2 To aid your supplier you are requested to note all the
    details relevant to your complaint, clearly stating
    details of any technical problems, date of receipt,
    packaging condition, etc. and forward this to your
    supplier.
    3 Where the product needs to be returned to your
    supplier, you are requested to use the original
    packaging wherever possible.
    Check for damage
    before proceeding with the installation!
    1
    2 
    						
    							997-492-000-6, Issue 6
    July 20118
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    2.5 Installation Preparation
    This section describes making the panel ready for
    installation.
    2.5.1 Removing the Cover
    Remove the front cover as follows:
    Use the supplied 4mm hexagonal socket wrench to release
    the two recessed, socket-headed screws located in position
    ‘A’ - the screws are captive and do not need to be removed
    from the cover moulding. Once the screws have disengaged
    the back box, remove the cover as follows:
    i Gently pull the bottom edge of the cover clear of the
    back box.
    ii Carefully lift the top edge of the cover up and away from the back box to disengage the locating lugs.
    iii Store the cover safely until required for re-fitting.
    2.5.2 Back Box Fixing
    The back box must be fixed to the wall with screws at three
    fixing locations (see drawing) following the procedure
    described below.
    Wall Flatness
    To prevent distortion, the back box must be installed on the
    wall as flat as possible, i.e. with a maximum flatness
    deviation between any two points of 3mm. Where the wall
    is out of tolerance, use appropriate packing pieces when
    installing the back box to meet the above requirements.
    Failure to comply with this requirement may result in
    the misalignment and consequent difficulty in fitting
    the front cover or malfunction of control pushbuttons.
    When a suitable location has been found for installing the
    control panel, proceed as described below:
    1 Prepare apertures (20mm knockouts) required for
    cable access as follows:
    With the cover removed position the back box so the
    interior is towards you. Using a No. 5, slot-ended
    screwdriver, position its end in the recess (A) of the
    20mm knockout and incline the screwdriver towards you
    at about 15° from the vertical (see illustration at left).
    Support the screwdriver as illustrated to minimize
    penetration of the back box. While in this position  use
    something suitable, such as a mallet, to strike the top of
    the screwdriver to achieve a clean break of the knockout.
    2 Hold the back box assembly in the required position
    against the wall and mark the position of the keyhole (A).
    3 Drill and plug the wall to take size 4 to 5mm screws.
    4 With the panel supported by the top screw, and
    ensuring that it is level, mark the other two screw
    positions (B). Drill holes and plug.
    5 Screw the panel back box to the wall using all three
    fixing holes and 4 to 5mm steel, flat-underside-headed
    screws.  DO NOT use countersunk-headed screws .
    Use washers with 4mm-sized screws.
    A
    A
    Overall Dimensions of panel in
    millimetres:
    318(h) x 355.5(w) x 96(d).
    (Distance between fixing holes marked
    on rear face of back box).
    A
    BB 
    						
    							997-492-000-6, Issue 6July 2011
    9
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    2.6 Optional Equipment
    2.6.1 2-Way Relay PCB
    An optional 
    PCB supporting Fire and Fault condition, volt-
    free, status outputs may be fitted.  When fitted, the PCB
    is connected to the Main PCB via connector, PL1.
    Note:  These relays are only intended to switch SELV.
    See  Section 8 Specifications .
    The PCB is fitted immediately to the left of the Main PCB.
    Full instructions for installation are provided with the 2-
    way Relay PCB kit (PN: 020-713).
    The artwork provided above the wiring termination blocks
    shows the Fire and Fault relay contacts with the relays
    in a non-energised state. With the panel in its normal
    quiescent state, i.e. with no fire or fault conditions present,
    the Fire relay is not energised and the Fault relay is
    energised. Terminate external wiring as appropriate.
    2.6.2 8-Way Relay PCB
    The panel has provision for fitting up to two optional 8-
    way Relay PCBs. A 16-way ribbon cable connects SK2
    on the 8-way Relay PCB to the PSU PCB. When two 8-
    way Relay PCBs are fitted, a short 16-way ribbon cable
    is used to link the two PCBs together: connector SK2 on
    the second PCB to SK1 on the first PCB.
    The Main PCB must be removed to allow the PCB(s) to
    be fitted and for the correct termination of the ribbon
    cable at the PSU and 8-way Relay PCB and between
    the 8-way Relay PCBs, when two PCBs are fitted.
    Full installation instructions (PN: 997-512-000-1) are
    provided with the 8-way Relay PCB kit (PN: 020-747).
    2.6.3 4-Way Sounder PCB
    The panel has provision for fitting up to two optional 4-
    way Sounder PCBs. A 16-way ribbon cable connects SK2
    on the 4-way Sounder PCB to the PSU PCB. When two
    4-way Sounder PCBs are fitted, a short 16-way ribbon
    cable is used to link the two PCBs together: connector
    SK2 on the second PCB to SK1 on the first PCB.
    The Main PCB must be removed to allow the PCB(s) to
    be fitted and for the correct termination of the ribbon
    cable at the PSU and 4-way Sounder PCB and between
    the 4-way Sounder PCBs, when two PCBs are fitted.
    Full installation instructions (PN: 997-536-000-1) are
    provided with the 4-way Sounder PCB kit (PN: 020-772).
    PL1
    FIRE FAULT
    SK2
    SK1
    SK2
    SK1 
    						
    							997-492-000-6, Issue 6
    July 201110
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    3 Cabling
    3.1 Cabling Instructions
    All wiring should comply with current IEE wiring
    regulations (BS7671) or the applicable local wiring
    regulations. Note also the requirements of EN 54-14 for
    cabling and interconnection of a fire detection and alarm
    system.
    EMC Requirements:
     To meet the EMC requirements
    of the European Directives, it is necessary to ensure
    that a screened or metal sheathed cable is used.
    Cable conductor size should be a minimum of 0.5mm
    2.
    Terminals accept one 0.5 to 2.5mm2 stranded or solid
    conductor.
    Cables should be brought into the back box through the
    20mm knockouts provided on the top face. Refer to
    Section 2.5.2  for details on preparing the knockouts.
    Ensure that all openings in the back box are closed off
    before connecting power to the panel.
    Mains Supply
    The supply to the panel must be provided with a suitable
    and readily-accessible, double-pole,  mains-disconnect
    device . The mains supply must be suitably fused and
    rated according to the specifications.
    Always ensure that the mains cables are brought into
    the back box separately to the low-voltage wiring (refer
    to  Section 6.4  Powering the Panel ). All  low-voltage
    cables should have a minimum 300VAC rating.
    The termination of earth mains wiring must be done
    before the termination of any external cable screens.
    Cable Screen Wires
    Cables should be screened. Screen wires should be
    terminated inside the back box as follows:
    a. Screen tails should be of sufficient length to connect to the earth post (A) at the commissioning stage.
    Once all screen wires have been terminated at the
    earth post (A), use the M4 nut (B), spring washer (C)
    and two plain washers (D) either side of the screen
    wires to make sure a good earthing bond is created.
    b. Use insulation sleeving on the tails between the cable entry position and the earth post. Run the tails close
    to the rear wall of the back box.
    Note:  In cases where all 8 zones are to be configured
    and there is a need to reduce the number of cable
    screen tails being routed through the panel, an
    alternative method is to fit a suitable earth block
    (not provided). The fixing points (E) may be used
    to mount the block. Provide a suitable cable
    between this block and the earth post. Using
    insulation sleeving, terminate all cable screen tails
    at the earth block.
    WARNING Risk of electric
    shock. Before working on
    mains connections, ensure mains power supply to the panel is disconnected.
    E
    Ensure incoming earthis connected to the
    post provided and NOT at the PSU PCB. 
    						
    							997-492-000-6, Issue 6July 2011
    11
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    3.1.1 Cable Terminations
    This section provides guidance on where to bring cables
    into the back box for ease of termination.
    a. The mains supply should be brought into the control
    panel such that the live (L) and neutral (N) cable path
    to the mains termination block (MTB) is kept as short
    as possible. Refer to  Section 6.4 Powering the
    Panel  for the recommended method of terminating
    the mains wiring and safety earth. This must be done
    before terminating all other panel wiring.
    b. All zone and ancillary cable terminations should be brought into the panel at suitable positions and routed
    tidily between entry and termination points.
    The drawing below shows recommended points of entry
    so that the following cabling can meet these requirements.
    a. Mains supply cable
    b. Zone circuits: 1- 2, 1- 4 or 1- 8
    c. Sounder circuits
    d. Digital input circuits
    e. Auxiliary output circuit (to  meet the requirements of EMC
    compatibility, cable length 
    must not exceed 30m)
    f. 2-way relay PCB outputs (optional)
    g. 8-way relay PCB(s) outputs* (optional)
    h. 4-way sounder PCB(s) outputs (optional)
    * With 8 Zone panels it may be necessary to use multi- core cables for these relay outputs.
    3.2 Quality of Cable and of Cable Installation
    It is important that good quality cable is used, and that
    correct installation techniques are followed. In general,
    the following cable installation requirements must be met:
    a. All cable sections must be circular to allow effectivecable clamping using the cable glands.
    b. The cable must be screened (sheathed) to provide protection against Radio Frequency Interference
    (RFI) and the screen must be connected to the
    earthing point in the back box (refer to  Section 3.1).
    c. The screen must be continuous.
    d. Cable recommended for use is MICC with a LSF PVC overcovering, a fire resilient cable to BS7629 or PVC/
    SWA/PVC to BS6387.
    Recommended Cables:
    Cables should not exceed 40R resistance per core and
    300nF core-to-core capacitance. This will correspond
    to approximately 1km cable length. The following is a
    list of recommended cables:
    Manufacturer Product  Name Part Number Type1
    AEIMICC 2L1.5Enhanced
    AEI Firetec 298-052Standard
    Draka FiretufPlus FTPLUS2E1.5RD Enhanced
    Draka Firetuf FTZ 2E1.5Standard
    Pirelli FP Plus FP Plus 2x1.5 Red Enhanced
    Pirelli FP200 Gold FP200 Gold  2x1.5 RedStandard
    1For a definition of ‘Standard’ and ‘Enhanced’
    cable requirements and their different
    applications, refer to BS  5839-1, Section 26.
    Enhanced cable is typically required for spur
    sounder outputs while standard cables may
    be adequate for other fire-related I/O,
    provided there is diverse cable routing. 
    						
    							997-492-000-6, Issue 6
    July 201112
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    3.3 EMC Considerations
    Following the above instructions and by using suitable
    screened cables EMC problems will be avoided.
    In particularly difficult EMC environments, or where non-
    preferred cabling is used, it is possible to fit ferrite sleeves
    to cables entering the panel, in particular the power supply
    input, sounder and auxiliary output cables.
    The ferrite sleeves (A) should be fitted over all the
    conductor(s) and as close as possible to the entry point
    of the cable. If required, use a cable tie (B)  - not supplied
    - to hold the ferrite in position.
    If additional ferrites are required these can be purchased
    from your supplier (quote part no. 538-143).
    3.4 Cables for Sounder Circuits
    When designing the sounder circuits, check that you are
    using an adequate cable diameter, considering the cable
    length, to ensure sounders operate within specification.
    Example:
    Sounder circuit output: 20.0V (min); 0.5A (max)
    Sounder device spec.: 15Vdc (min); 20mA (depends
    on tone used)
    Cable type spec.: Pirelli FP200 Gold, 1.5mm
    2
    core resistance:12.1R/km (per
    core at 20°C).
    Maximum number of sounders per sounder output circuit: = 0.5A / 0.020A = 25
    Assuming worst case loading with all sounders at the
    end of the cable:
    Maximum cable resistance to ensure 15V: = (20-15) / 0.5 = 10R
    Maximum cable length that will ensure 15V minimum: = 10 / (12.1+ 12.1) = 0.413km
    If the sounders are more evenly distributed along the
    length of the cable, then calculations will show that longer
    cable lengths are permissable. After installation, the
    following tests will confirm that your installation is
    functional:
    a. Activate the sounders and measure the voltage drop along the cable:
    V
    drop = Panel Terminal Voltage - End-of-line Voltage
    b. Subtract this from the mimimum terminal voltage when on battery back up to give the minimum end-
    of-line voltage (V
    eolmin):
    V
    eolmin = 20 - Vdrop
    The voltage must exceed the minimum specification of
    the sounders, i.e. 15V for the Notifier NS14.
    A
    B 
    						
    							997-492-000-6, Issue 6July 2011
    13
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    4 Field Devices
    The Fire Control Panel is capable of working with various
    manucturer’s field devices (for compatible field devices
    refer to 
    Section 1 Introduction ).
    Each of these devices is supplied with an instruction leaflet
    showing the correct interconnections for various applications.
    Before connecting the panel or devices, the wiring should
    be tested for insulation and continuity. Once any
    components are connected, do not use a high-voltage
    tester, such as a Megger, on the circuitry. Low-voltage
    multimeters may be used.
    CAUTION  - DO NOT use a Megger on zone wiring with
    detector heads removed (or fitted) as this will damage
    the Schottky diodes fitted to the bases and/or detectors.
    Some manufacturers fit a spring in the detector base
    which can be used to manually short-circuit the diode
    for wiring testing prior to fitting detectors. Where a spring
    is not provided, use a link
    1 to short out the diode. Refer
    to the manuafacturer’s instructions provided.
    1DO NOT forget to remove these links at the
    completion of wiring testing .
    4.1 End-of-Line Devices
    The panel is designed to work with the following zone
    circuit end-of-line (EOL) devices:
    •A 0.47μF capacitor, or
    •A 4k7 resistor*
    * This EOL device is not recommended for new
    installations where the latest field devices are to be used.
    The 4k7 resistor should only be used where the control
    panel is being installed as a fire control panel replacement
    and the existing field devices are to be retained.
    Using the 0.47 μF capacitor will reduce the size of the
    standby batteries. Refer to  Section 6.4.1 Batteries for
    more information on recommended battery sizes. Where
    zones are to use a mix of detectors and MCPs a 0.47 μF
    capacitor EOL device must be used.
    Retrofit Installations
    The 4k7 resistor EOL devices may be retained on existing
    installations. However, existing Active End-of-Line (AEOL)
    devices must be replaced with a 0.47 μF capacitor  or the
    additional kit  (PN: 020-417) must be fitted (refer to
    Section 6.3 External Wiring for EOL device compatibility
    issues).
    Caution:  To avoid inadvertant activation of the sounders
    the panel must be re-configured to work with resistor
    EOL devices - Refer to Section 7.5.6 EOL Device Type.
    CAUTION
    DO NOT use a Megger on zone wiring with diodes in circuit.
    CAUTION
    Replace AEOLs on existing
    installations with
     a 0.47μ F
    capacitor or use Additional kit (PN: 020-417).
    CAUTION
    AEOL must be configuredor the panel may reportan alarm at power up. 
    						
    All Honeywell manuals Comments (3)

    Related Manuals for Honeywell Notifier Nfs28 Manual