Honeywell Notifier Nfs28 Manual
Have a look at the manual Honeywell Notifier Nfs28 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
997-492-000-6, Issue 6 July 20114 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual WARNING High Voltage! Take suitable precau- tions to avoid electric shock. EN 54-2 (and ISO 7240-2): Section Ref. Brief explanation of non-compliance here. ! EN54 ISO 7240! EN54 ISO 7240 1.7 Ancillary Functions The following is a list of ancillary functions that are provided by the control panel in addition to those required by EN 54-2/4. These functions are described in the section of this manual as referenced. Ancillary Functions Manual Section Refs. Site specific Setup options 7 Extend delay timer 7.8 Sounder Volt-free contact options 7.6 Relay drive output option 7.6 1.8 Related Documents This manual only describes the installation, commissioning and configuration of the control panel. All user functions are covered by the EN 54 2-8 Zone Conventional Fire Control Panel User Manual (ref. 997-493 -00X). 1.9 Warnings and Cautions Where appropriate, this guide and the remainder of the manual include advisory warnings and cautions to remind you to consider safety at all times, especially when following the procedures described in this manual. You are alerted to any areas where hazardous voltages are present, or where there may be a risk of damage to static-sensitive devices if the recommended procedures described in this manual are not followed. An example of a high voltage warning and anti-static caution is provided to the left of this paragraph. The caution at left indicates that it is possible to configure a panel in a way that would make it non-compliant with the requirements of EN 54 or ISO 7240. This should only be done under exceptional circumstances and with the authority of the local fire officer. The following features are provided by the Power Supply Unit (PSU) of the NFS 2-8 and FLS 2-8 fire control panels to comply with EN 54-4 and ISO 7240-4. Features of the NFS 2-8 & FLS 2-8 Clause Power Supply Unit (PSU) Derive power from the mains supply 5.1 Derive power from a standby battery source 5.2 Charge and monitor the standby battery/batteries 5.3 Detect and signal various PSU faults 5.4
997-492-000-6, Issue 6July 2011 5 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 2 Installation Guide 2.1 How to Use this Guide This Installation Guide provides you with simple guidelines to install a fire control panel system, quickly and safely. The guide does not describe panel configuration procedures as it is covered by the relevant section of this manual. For each stage in the panel installation and commissioning procedures a brief description is given of its purpose, complete with detail drawings, flow diagrams and/or other graphics, wherever possible, to make the instructions easy to follow. 2.2 Pre-installation Check List Before installing your control panel or fitting detectors, you must first ensure that the following criteria have been met. Failure to do this may not only result in damage to the equipment, but may also cause problems when commissioning the equipment or adversely affect its performance. 2.2.1 Some Panel DO’s and DON’T’s Before selecting a location for the panel and detectors, DO make sure that: a) The ambient temperature is in the range: +5 °C to 35°C and b) The relative humidity is between: 5% and 95% (non-condensing) c. The panel is wall mounted in a position which allows clear visibility of displays and easy access to operating controls. The height above floor level should be chosen such that the middle of the panel is just above normal eye level (approximately 1.5 metres). d) DO NOT locate the panel where it is exposed to high levels of moisture
997-492-000-6, Issue 6 July 20116 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual e) DO NOT locate the panel where there are high levelsof vibration or shock f) DO NOT site the panel where there would be restricted access to the internal equipment and cabling/wiring connections. 2.3 Transient Protection This equipment contains transient-protection devices. Although no system is completely immune from lightning transients and interference, for these devices to function correctly, and to reduce susceptibility, this equipment must be earthed correctly. As with all solid state devices, this system may operate erratically or can be damaged if subjected to lightning- induced transients. The use of outside aerial wiring is not recommended due to the increased susceptibility to nearby lightning strikes.
997-492-000-6, Issue 6July 2011 7 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 2.4 Product Inspection The 2-8 Zone Fire control panel is simple to install and commission if the recommended procedures described in this Installation Guide, and the Installation and Commissioning sections of this manual, are followed. Follow all installation instructions described in this manual. These instructions must be understood and followed to avoid damage to the control panel and associated equipment. 2.4.1 Checking Your Panel for Damage Before attempting to install your panel you should do the following: 1 After removing the control panel from its packaging, and before you proceed with installing in its chosen location, check for any damage that may have been caused during transit. Note: In the unlikely event that the panel has been damaged in transit, you MUST NOT install it but contact your supplier for their returns procedure. 2.4.2 What to do if Yo u Suspect Your Panel is Damaged The procedure described below tells you what to do in the unlikely event that the supplied equipment has been damaged after leaving the factory. However, if you have problems regarding the quality of any supplied order items including the control panel, its ancillaries or this manual, or items are missing, follow the procedure below. 1If, after removing the panel from its packaging, a visual inspection reveals that it has been damaged, you MUST NOT continue with the installation but contact your supplier for advice on what to do next. Similarly, if the product is found to be faulty during installation contact your supplier immediately. 2 To aid your supplier you are requested to note all the details relevant to your complaint, clearly stating details of any technical problems, date of receipt, packaging condition, etc. and forward this to your supplier. 3 Where the product needs to be returned to your supplier, you are requested to use the original packaging wherever possible. Check for damage before proceeding with the installation! 1 2
997-492-000-6, Issue 6 July 20118 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 2.5 Installation Preparation This section describes making the panel ready for installation. 2.5.1 Removing the Cover Remove the front cover as follows: Use the supplied 4mm hexagonal socket wrench to release the two recessed, socket-headed screws located in position ‘A’ - the screws are captive and do not need to be removed from the cover moulding. Once the screws have disengaged the back box, remove the cover as follows: i Gently pull the bottom edge of the cover clear of the back box. ii Carefully lift the top edge of the cover up and away from the back box to disengage the locating lugs. iii Store the cover safely until required for re-fitting. 2.5.2 Back Box Fixing The back box must be fixed to the wall with screws at three fixing locations (see drawing) following the procedure described below. Wall Flatness To prevent distortion, the back box must be installed on the wall as flat as possible, i.e. with a maximum flatness deviation between any two points of 3mm. Where the wall is out of tolerance, use appropriate packing pieces when installing the back box to meet the above requirements. Failure to comply with this requirement may result in the misalignment and consequent difficulty in fitting the front cover or malfunction of control pushbuttons. When a suitable location has been found for installing the control panel, proceed as described below: 1 Prepare apertures (20mm knockouts) required for cable access as follows: With the cover removed position the back box so the interior is towards you. Using a No. 5, slot-ended screwdriver, position its end in the recess (A) of the 20mm knockout and incline the screwdriver towards you at about 15° from the vertical (see illustration at left). Support the screwdriver as illustrated to minimize penetration of the back box. While in this position use something suitable, such as a mallet, to strike the top of the screwdriver to achieve a clean break of the knockout. 2 Hold the back box assembly in the required position against the wall and mark the position of the keyhole (A). 3 Drill and plug the wall to take size 4 to 5mm screws. 4 With the panel supported by the top screw, and ensuring that it is level, mark the other two screw positions (B). Drill holes and plug. 5 Screw the panel back box to the wall using all three fixing holes and 4 to 5mm steel, flat-underside-headed screws. DO NOT use countersunk-headed screws . Use washers with 4mm-sized screws. A A Overall Dimensions of panel in millimetres: 318(h) x 355.5(w) x 96(d). (Distance between fixing holes marked on rear face of back box). A BB
997-492-000-6, Issue 6July 2011 9 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 2.6 Optional Equipment 2.6.1 2-Way Relay PCB An optional PCB supporting Fire and Fault condition, volt- free, status outputs may be fitted. When fitted, the PCB is connected to the Main PCB via connector, PL1. Note: These relays are only intended to switch SELV. See Section 8 Specifications . The PCB is fitted immediately to the left of the Main PCB. Full instructions for installation are provided with the 2- way Relay PCB kit (PN: 020-713). The artwork provided above the wiring termination blocks shows the Fire and Fault relay contacts with the relays in a non-energised state. With the panel in its normal quiescent state, i.e. with no fire or fault conditions present, the Fire relay is not energised and the Fault relay is energised. Terminate external wiring as appropriate. 2.6.2 8-Way Relay PCB The panel has provision for fitting up to two optional 8- way Relay PCBs. A 16-way ribbon cable connects SK2 on the 8-way Relay PCB to the PSU PCB. When two 8- way Relay PCBs are fitted, a short 16-way ribbon cable is used to link the two PCBs together: connector SK2 on the second PCB to SK1 on the first PCB. The Main PCB must be removed to allow the PCB(s) to be fitted and for the correct termination of the ribbon cable at the PSU and 8-way Relay PCB and between the 8-way Relay PCBs, when two PCBs are fitted. Full installation instructions (PN: 997-512-000-1) are provided with the 8-way Relay PCB kit (PN: 020-747). 2.6.3 4-Way Sounder PCB The panel has provision for fitting up to two optional 4- way Sounder PCBs. A 16-way ribbon cable connects SK2 on the 4-way Sounder PCB to the PSU PCB. When two 4-way Sounder PCBs are fitted, a short 16-way ribbon cable is used to link the two PCBs together: connector SK2 on the second PCB to SK1 on the first PCB. The Main PCB must be removed to allow the PCB(s) to be fitted and for the correct termination of the ribbon cable at the PSU and 4-way Sounder PCB and between the 4-way Sounder PCBs, when two PCBs are fitted. Full installation instructions (PN: 997-536-000-1) are provided with the 4-way Sounder PCB kit (PN: 020-772). PL1 FIRE FAULT SK2 SK1 SK2 SK1
997-492-000-6, Issue 6 July 201110 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 3 Cabling 3.1 Cabling Instructions All wiring should comply with current IEE wiring regulations (BS7671) or the applicable local wiring regulations. Note also the requirements of EN 54-14 for cabling and interconnection of a fire detection and alarm system. EMC Requirements: To meet the EMC requirements of the European Directives, it is necessary to ensure that a screened or metal sheathed cable is used. Cable conductor size should be a minimum of 0.5mm 2. Terminals accept one 0.5 to 2.5mm2 stranded or solid conductor. Cables should be brought into the back box through the 20mm knockouts provided on the top face. Refer to Section 2.5.2 for details on preparing the knockouts. Ensure that all openings in the back box are closed off before connecting power to the panel. Mains Supply The supply to the panel must be provided with a suitable and readily-accessible, double-pole, mains-disconnect device . The mains supply must be suitably fused and rated according to the specifications. Always ensure that the mains cables are brought into the back box separately to the low-voltage wiring (refer to Section 6.4 Powering the Panel ). All low-voltage cables should have a minimum 300VAC rating. The termination of earth mains wiring must be done before the termination of any external cable screens. Cable Screen Wires Cables should be screened. Screen wires should be terminated inside the back box as follows: a. Screen tails should be of sufficient length to connect to the earth post (A) at the commissioning stage. Once all screen wires have been terminated at the earth post (A), use the M4 nut (B), spring washer (C) and two plain washers (D) either side of the screen wires to make sure a good earthing bond is created. b. Use insulation sleeving on the tails between the cable entry position and the earth post. Run the tails close to the rear wall of the back box. Note: In cases where all 8 zones are to be configured and there is a need to reduce the number of cable screen tails being routed through the panel, an alternative method is to fit a suitable earth block (not provided). The fixing points (E) may be used to mount the block. Provide a suitable cable between this block and the earth post. Using insulation sleeving, terminate all cable screen tails at the earth block. WARNING Risk of electric shock. Before working on mains connections, ensure mains power supply to the panel is disconnected. E Ensure incoming earthis connected to the post provided and NOT at the PSU PCB.
997-492-000-6, Issue 6July 2011 11 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 3.1.1 Cable Terminations This section provides guidance on where to bring cables into the back box for ease of termination. a. The mains supply should be brought into the control panel such that the live (L) and neutral (N) cable path to the mains termination block (MTB) is kept as short as possible. Refer to Section 6.4 Powering the Panel for the recommended method of terminating the mains wiring and safety earth. This must be done before terminating all other panel wiring. b. All zone and ancillary cable terminations should be brought into the panel at suitable positions and routed tidily between entry and termination points. The drawing below shows recommended points of entry so that the following cabling can meet these requirements. a. Mains supply cable b. Zone circuits: 1- 2, 1- 4 or 1- 8 c. Sounder circuits d. Digital input circuits e. Auxiliary output circuit (to meet the requirements of EMC compatibility, cable length must not exceed 30m) f. 2-way relay PCB outputs (optional) g. 8-way relay PCB(s) outputs* (optional) h. 4-way sounder PCB(s) outputs (optional) * With 8 Zone panels it may be necessary to use multi- core cables for these relay outputs. 3.2 Quality of Cable and of Cable Installation It is important that good quality cable is used, and that correct installation techniques are followed. In general, the following cable installation requirements must be met: a. All cable sections must be circular to allow effectivecable clamping using the cable glands. b. The cable must be screened (sheathed) to provide protection against Radio Frequency Interference (RFI) and the screen must be connected to the earthing point in the back box (refer to Section 3.1). c. The screen must be continuous. d. Cable recommended for use is MICC with a LSF PVC overcovering, a fire resilient cable to BS7629 or PVC/ SWA/PVC to BS6387. Recommended Cables: Cables should not exceed 40R resistance per core and 300nF core-to-core capacitance. This will correspond to approximately 1km cable length. The following is a list of recommended cables: Manufacturer Product Name Part Number Type1 AEIMICC 2L1.5Enhanced AEI Firetec 298-052Standard Draka FiretufPlus FTPLUS2E1.5RD Enhanced Draka Firetuf FTZ 2E1.5Standard Pirelli FP Plus FP Plus 2x1.5 Red Enhanced Pirelli FP200 Gold FP200 Gold 2x1.5 RedStandard 1For a definition of ‘Standard’ and ‘Enhanced’ cable requirements and their different applications, refer to BS 5839-1, Section 26. Enhanced cable is typically required for spur sounder outputs while standard cables may be adequate for other fire-related I/O, provided there is diverse cable routing.
997-492-000-6, Issue 6 July 201112 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 3.3 EMC Considerations Following the above instructions and by using suitable screened cables EMC problems will be avoided. In particularly difficult EMC environments, or where non- preferred cabling is used, it is possible to fit ferrite sleeves to cables entering the panel, in particular the power supply input, sounder and auxiliary output cables. The ferrite sleeves (A) should be fitted over all the conductor(s) and as close as possible to the entry point of the cable. If required, use a cable tie (B) - not supplied - to hold the ferrite in position. If additional ferrites are required these can be purchased from your supplier (quote part no. 538-143). 3.4 Cables for Sounder Circuits When designing the sounder circuits, check that you are using an adequate cable diameter, considering the cable length, to ensure sounders operate within specification. Example: Sounder circuit output: 20.0V (min); 0.5A (max) Sounder device spec.: 15Vdc (min); 20mA (depends on tone used) Cable type spec.: Pirelli FP200 Gold, 1.5mm 2 core resistance:12.1R/km (per core at 20°C). Maximum number of sounders per sounder output circuit: = 0.5A / 0.020A = 25 Assuming worst case loading with all sounders at the end of the cable: Maximum cable resistance to ensure 15V: = (20-15) / 0.5 = 10R Maximum cable length that will ensure 15V minimum: = 10 / (12.1+ 12.1) = 0.413km If the sounders are more evenly distributed along the length of the cable, then calculations will show that longer cable lengths are permissable. After installation, the following tests will confirm that your installation is functional: a. Activate the sounders and measure the voltage drop along the cable: V drop = Panel Terminal Voltage - End-of-line Voltage b. Subtract this from the mimimum terminal voltage when on battery back up to give the minimum end- of-line voltage (V eolmin): V eolmin = 20 - Vdrop The voltage must exceed the minimum specification of the sounders, i.e. 15V for the Notifier NS14. A B
997-492-000-6, Issue 6July 2011 13 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 4 Field Devices The Fire Control Panel is capable of working with various manucturer’s field devices (for compatible field devices refer to Section 1 Introduction ). Each of these devices is supplied with an instruction leaflet showing the correct interconnections for various applications. Before connecting the panel or devices, the wiring should be tested for insulation and continuity. Once any components are connected, do not use a high-voltage tester, such as a Megger, on the circuitry. Low-voltage multimeters may be used. CAUTION - DO NOT use a Megger on zone wiring with detector heads removed (or fitted) as this will damage the Schottky diodes fitted to the bases and/or detectors. Some manufacturers fit a spring in the detector base which can be used to manually short-circuit the diode for wiring testing prior to fitting detectors. Where a spring is not provided, use a link 1 to short out the diode. Refer to the manuafacturer’s instructions provided. 1DO NOT forget to remove these links at the completion of wiring testing . 4.1 End-of-Line Devices The panel is designed to work with the following zone circuit end-of-line (EOL) devices: •A 0.47μF capacitor, or •A 4k7 resistor* * This EOL device is not recommended for new installations where the latest field devices are to be used. The 4k7 resistor should only be used where the control panel is being installed as a fire control panel replacement and the existing field devices are to be retained. Using the 0.47 μF capacitor will reduce the size of the standby batteries. Refer to Section 6.4.1 Batteries for more information on recommended battery sizes. Where zones are to use a mix of detectors and MCPs a 0.47 μF capacitor EOL device must be used. Retrofit Installations The 4k7 resistor EOL devices may be retained on existing installations. However, existing Active End-of-Line (AEOL) devices must be replaced with a 0.47 μF capacitor or the additional kit (PN: 020-417) must be fitted (refer to Section 6.3 External Wiring for EOL device compatibility issues). Caution: To avoid inadvertant activation of the sounders the panel must be re-configured to work with resistor EOL devices - Refer to Section 7.5.6 EOL Device Type. CAUTION DO NOT use a Megger on zone wiring with diodes in circuit. CAUTION Replace AEOLs on existing installations with a 0.47μ F capacitor or use Additional kit (PN: 020-417). CAUTION AEOL must be configuredor the panel may reportan alarm at power up.