Page 31
997-492-000-6, Issue 6 July 201124 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual No indication on panel - buzzer not sounding Panel in Fire state.No power to panel. Check mains suppl y; Check total battery voltage is >21V. Check mains supply to panel; Check battery connections Carry out visual check; if problems persist replace units/batteries until fault clears. Indication Action Possible Cause Common Fault Indication plus: AC mains failed - panel operating on...
Page 32
997-492-000-6, Issue 6July 2011 25 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 7 Configuration Access Level 3 allows input, output and control functions to be configured. The following sections describe how to configure the panel. Each procedure requires the panel status to be at access Level 3. The state of the configurable options is indicated by the panel LEDs. The table at left shows the functions of each pushbutton at access Level 1/ 2 and Level 3. The...
Page 33
997-492-000-6, Issue 6 July 201126 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 7.2 Panel Options - A Four user-configurable panel options are available: a. Enable/Disable Engineering Mute b. Enable/Disable Commissioning Mode c. ACCEPT pushbutton access level d. LAMP TEST pushbutton access level. e. Delay Lights DISABLEMENT LED 7.2.1 Engineering Mute The operation of the panel’s buzzer can be changed so that it operates only occasionally with a Fire state, fault...
Page 34
997-492-000-6, Issue 6July 2011 27 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual Non-latching only affects the following fault conditions: a. Zone Faults b. Earth Fault c. Power Supply Fault d. Sounder Fault e. Fire Output Fault f. Fault Output Fault g. Auxiliary Supply Fault. Note:System Fault remains latching at all times. 7.3.2 Pulse Fire Routing Outputs When this option is selected the fire routing ouput is activated for a period of 5 secs only (pulsed)....
Page 35
997-492-000-6, Issue 6 July 201128 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 7.5 Fire Zone Input Type Fire input zones can be configured as follows: a. Latching/non-latching alarms b. Alarm or for short-circuit operation c. Auto or manual operation mode d. Coincident-alarm or separate-alarm detection e. Setting a Sprinkler Verification Time. f. EOL Device Type. 7.5.1 Latching/Non-latching Alarms A detection zone can be configured as latching or non- latching....
Page 36
997-492-000-6, Issue 6July 2011 29 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 7.5.5 Sprinkler Verification Time A 2 sec. verification time is applied to all inputs to reduce the occurrence of false indications of alarm due to transient phenomena. When monitoring an input from a sprinkler system it may be necessary to configure a sprinkler verification delay. This is an exceptional situation and will require the approval of a fire officer. 7.5.6 EOL Device...
Page 37
997-492-000-6, Issue 6 July 201130 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual sounder output PCB, NFS-SST(English PN: 020-769- 001) or NFS8V-SST (German PN: 020-769) Display Boxes and Routing Termination kit (020-773). vi If an EN 54-2 or ISO 7240-2, 8.9 monitored fault routing output is required both relay and PSU PCB sounder outputs are unmonitored in this mode. For this application use the optional 4-way sounder output PCB. vii Note: PSU PCB sounder...
Page 38
997-492-000-6, Issue 6July 2011 31 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual g. Fault transmission failed return signal. Class Change: When a class change digital input is activated, all outputs configured as sounders will be activated until the input condition is removed. Alert: When an alert digital input is activated, all outputs configured as sounders and the internal buzzer start pulsing. The sounders and internal buzzer remain pulsing until the digital...
Page 39
997-492-000-6, Issue 6 July 201132 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 7.8 Primary and Secondary Delays A day-time delay strategy can be implemented, if required, which comprises two user-configurable delay periods to allow a fire search to take place. These delay periods are referred to as primary and secondary. On an auto detection zone, every fire state places the panel in a full alarm, hold- off state until the indicated fire event has either: a....
Page 40
997-492-000-6, Issue 6July 2011 33 EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual 7.9 Configuration Examples The following examples are provided to offer guidance when navigating through some of the menu options. Note: If you lose your way at any time, simply press the ‘main menu’ pushbutton to return to the menu select position. Example 1 How do I configure the panel back to the factory default state? Ensuring that the panel is at access Level 3 (refer to...