Honeywell Mabs Ez 2 Manual
Have a look at the manual Honeywell Mabs Ez 2 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
MASTERTROL® AUTOMATIC BALANCING SYSTEM™ (MABS®) EZ ZONE (EZ-2 AND EZ-4) CONTROL PANELS 11 69-1360–2 Thermostats The panel can use almost any four-wire (R,W,Y,G) thermostat. Each zone requires its own switching subbase with either manual or automatic changeover. See Table 1 for recommended thermostats. HEAT PUMP OR MULTI-STAGE THERMOSTATS Heat pump or multi-stage thermostats are not required for the MABS EZ panels because a timer in the panel brings on the second stage. A heat pump thermostat is used only when emergency heat control from the thermostat is desired. Use only Table 1 recommended heat pump thermostats. EMERGENCY HEAT MODE An emergency heat switch is located on the side of the panel and can be accessed without removing the cover. A heat pump thermostat is used only when emergency heat control is desired from the thermostat instead of from the panel. Energizing the L terminal on the zone thermostat or switching the Emergency Heat switch to the On position places the system in Emergency Heat mode. This switch does not initiate a call for emergency heat and prevents the first stage (heat pump) from being used on a call for heat. Fan On In Heat The system fan can be set to come on with a heat call, as required, with a hydro-air, heat pump, or electric heat system. Set DIP switch 8 to the On position to activate this mode. Otherwise, leave it in the default Off position.Second Stage Emergency Heat Jumper A jumper is installed on the jumper block to energize W2 output during a call for emergency heat. If there are two forms of auxiliary heat, one can be connected to W2 as the second stage of heat and the other to E as the emergency heat stage. See Fig. 4. Table 8. DIP Switch Settings. DIP Switch NO.Switch Function with DIP Switch Off (Default)Switch Function with DIP Switch On 1 3.5 minute Purge with fan on2 minute Purge with fan off 2 ZMS 160°F (71°C) heating limitZMS 120°F (49°C) heating limit 3 ZMS 40°F (4°C) cooling limitZMS 48°F (9°C) cooling limit 4 Normal operation Test mode; accelerated timings 5 See Table 4. _. 6 See Table 4. _ 7 See Table 4. _ 8HVAC unit- controlled fanFan on with call for Heat
69-1360–2 G.H. Rev. 9-01 www.honeywell.com/yourhome !#$$ %&! #( Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers. MASTERTROL® AUTOMATIC BALANCING SYSTEM™ (MABS®) EZ ZONE (EZ-2 AND EZ-4) CONTROL PANELS TROUBLESHOOTING The primary diagnostic tools are the system and damper status LEDs. See Table 9 for troubleshooting guide. Table 9. Troubleshooting Guide. Symptom Problem Solution No LEDs light No power to the panel.•Check for 24 Vac across TR2. •Check circuit breaker; if hot, a short exists in thermostat or damper wiring. Erratic operation Insufficient voltage. Incorrect configuration Panel in Emergency Heat mode Panel needs resetting.Check for 24 Vac ±10% across TR1 and TR2. Verify jumpers and DIP switch setting for correct configuration. Check position of Em Heat switch. Press Boot button and recheck system operation. Heat or Cool LEd flashes continuouslyHeat LED flashing. Cool LED flashing.ZoneMAX Sensor tripped on high limit. ZoneMAX Sensor tripped on high limit. Heat pump works in Heat but not in Cool or in Cool but not in HeatIncorrect thermostat. Incorrectly wired.Install the correct thermostat. If equipment is heat pump, be sure there is a Y1 or W1 jumper installed. Emergency heat not coming onIncorrectly wired. Incorrect thermostat.Verify thermostat and equipment wiring. Verify correct thermostat is used.