Honeywell Lr953291 Manual
Here you can view all the pages of manual Honeywell Lr953291 Manual. The Honeywell manuals for Detector are available online for free. You can easily download all the documents as PDF.
Page 11
11 EN1C-0015SZ20 R0314 Fig. 10_3. Wiring diagram for C7061A1020-79/C7061F1003 detec-tor with 7800 SERIES Flame Safeguard controls with shutter drive circuitry.Fig.10_4. Wiring diagram for C7061A1020-79/C7061F1003 detec-tor with R4348B Flame Safeguard controls with shutter drive circuitry.
Page 12
EN1C-0015SZ20 R031412 ADJUSTMENTS AND CHECKOUT Adjust Detector Sighting With the flame detector installed and the burner running, adjust the sighting position of the detector for optimum flame signal. It is suggested that a volt-Ohm meter with a minimum sensitivity of one megohm/volt and a zero to five or ten Vdc scale be used for R7861 amplifier flame signal measure- ments. Measure the flame signal as illustrated in Fig. 11. Be care- ful to make the proper connections of positive...
Page 13
13 EN1C-0015SZ20 R0314 VARIOUS TROUBLESHOOTING CAUTION 1. Be extremely careful while troubleshooting the detector; line voltage is present on some of the terminals when power is on. 2. Open the master switch to disconnect power before removing or installing the detector or its cover. More than one disconnect may be involved. Equipment Required A volt-Ohm meter with a minimum sensitivity of one megohm / Volt and a zero to five or ten Vdc scale is suggested. When the keyboard...
Page 14
EN1C-0015SZ20 R031414 SERVICE CAUTION Open the master switch to disconnect power before removing or installing the detector or its cover. More than one disconnect can be involved. Periodic Maintenance A Clean the viewing window (or focusing lens) when nec- essary. Remove the detector (see Troubleshooting sec- tion) and use a clean cloth over the eraser end of a pencil. Do not remove the window (or lens) to clean it. If it is broken or damaged or it is...
Page 15
15 EN1C-0015SZ20 R0314 Replacing the Quartz Viewing Window (or Focus- ing Lens) C7061A Only IMPORTANT A quartz window or lens must be used. Ordinary glass absorbs or filters out ultraviolet radiation. A Open the master switch; remove the detector from the sight pipe and remove the detector cover. (see appropri- ate sections.) B Remove the ultraviolet sensing tube (steps A through E of Replacing the Ultraviolet Sensing Tube section). C Loosen the three screws holding the back...
Page 16
(2) (1)Equipment andprotectivesystemsintended foruse inpotentially explosiveatmospheres Directive 94/9/EC EC-TYPE EXAMINATION CERTIFICATE (3)NumberoftheEC type examination certificate:INERIS03ATEX0158X (4)Protective systemorequipment : BOX TYPE AD4320001 orAD432002 (5) (6) Manufacturer: Address:IDRM Z.I duSauvoy 25, avenue deMontboulon F - 77165 SAINT -SOUPPLETS (7) Thisprotective system orequipment and anyotherac;ceptablealternativeofthisone aredescribedintheannexof this certificate andthedescriptive...
Page 17
EC-Type Examination CertificateN°INERlS03ATEXO158X (11) This ECtypeexamination certificaterelatesonlytothe design, examination andtestsofthespecified equipment or protective systeminaccordance tothe directive 94/9/EC. Furtherrequirements oftheDirective applytothe manufacturing processandsupply ofthisequipment orprotective system,thesearenot covered bythis certificate. (12) Themarking oftheequipment orthe protective systemwillhavetocontain: \Q1I2GD X.LEFEBVRE Engineer atthe Laboratory...
Page 18
EC-TypeExaminationCertificateN°INERIS 03ATEXO158X (13)ANNEX (14)ECTYPEEXAMINATIONCERTIFICATEN°INERIS03ATEX0158X (15)DESCRIPTIONOFTHEEQUIPMENTORTHEPROTECTIVESYSTEM Thisboxconsistsinabodyclosedbyascrewedcover. Theenclosurecontainsawholeofapparatusdefinedinthedescriptive note. ThisboxcanbefittedwiththefollowingExcomponents: -PneumaticbushingtypeXW8-TL1certificateINERIS03ATEX9014U -AuxiliarycontroltypeTCDcertificateLCIE02ATEX0036U ThisapparatuspresentsthedegreesofprotectionIP65accordingto...
Page 19
EC-Type Examination CertificateN°INERIS 03ATEXO158X MARKING Markingmustbereadableandindelible indications: IDRM F-77165SAINT-SOUPPLETS AD432001orAD432002 INERIS03ATEX0158X (numerodeserie) (Anneedeconstruction) ~II2GD EExdIICT(*) IP65T(*) DONOTOPENWHENENERGIZED (*)seetablebelow itmustcomprisethefollowing Incaseoftheboxisfittedwithadisconnector,theindicationnearto thedisconnector: DONOTOPERATEUNDERLOAD Thewholemarkingcanbecarriedoutinthelanguageofthecountryof use....
Page 20
EC-TypeExamination CertificateN°INERlS 03ATEX0158X (17)SPECIAL CONDITIONSFORSAFEUSE ThecableentrieshavetogetadegreesofprotectionatleastIP65, Foruseinpotentiallyexplosiveatmospheresduetocombustibledust: Thesurfaceofthedifferentsgapshavetobecoveredwithgrease, Userhastodoaregularcleaningofmaterialtolimitdustlayerson thematerial.sides. (18)ESSENTIALREQUIREMENTSOFSAFETYANDHEALTH TherespectoftheEssential.HealthandSafetyRequirementsisensuredby: conformitytotheEuropeanstandardsEN50014,50018andEN50281-1-1....