PRODUCT DATA 68-3041-2 ® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved EMM-3 Electronic MiniZone™ Panel APPLICATION The EMM-3 Electronic MiniZone™ Panel controls single- stage heat/cool equipment and is used on two-and three-zone applications. FEATURES • Uses any Honeywell four-wire thermostat. • Optional C7735 Discharge Air Temperature Sensor Sensor for capacity control. • SYSTEM and ZONE damper status LEDs indicate system status. • Automatic zone changeover with...
Page 2
EMM-3 ELECTRONIC MINIZONE™ PANEL 698-3041-2 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1.Your local Home and Building Control Sales Office (check white pages of your phone directory). 2.Home and Building...
Page 3
EMM-3 ELECTRONIC MINIZONE™ PANEL 3 68-3041-2 Dampers: Power-open/power-closed. Spring-open/power-closed. Spring-closed/power-open. See Table 2 for recommended dampers.Accessories: For required accessories, see Table 3. Table 1. Recommended Thermostats. Logo Standard ThermostatsProgrammable Thermostats Honeywell T87F1859 and Q539A1014 T87F3855 and Q539A1469 T8400C1024 T8401C1015 T8501D1046T8000C1002 T8001C1001 T8600D2069 T8601D2019 T8602D2018 PC8900A1007 and W8900A1004 Trol-A-Temp — T8601D2027 Table 2....
Page 4
EMM-3 ELECTRONIC MINIZONE™ PANEL 68-3041-2 4 INSTALLATION Mounting CAUTION Equipment Damage Hazard. Do not mount EMM-3 inside HVAC equipment. Mount only on wall or on cold air return. 1.Mount the thermostats in each zone of the living space using the installation instructions provided with each thermostat. See Fig. 2. 2.Mount the dampers in the ductwork using the installa- tion instructions provided with each damper. 3.Mount the EMM-3 zone panel near the HVAC equip- ment; locate it on a wall or on the...
Page 5
EMM-3 ELECTRONIC MINIZONE™ PANEL 5 68-3041-2 (1) Zone 3 damper is open. Zone 3 LED on EMM-3 is green. (2) Zone 1 and 2 dampers are closed. Zone 1 and 2 LED on EMM-3 are off. (3) Heating equipment is activated. SYSTEM LED is red. (4) Continue wiring the system. CAUTION Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before continuing installation. 13.Reconnect power to EMM-3. 14.Continue troubleshooting system in Cool mode. a. Set Zone 1 thermostat to Cool mode and...
Page 6
EMM-3 ELECTRONIC MINIZONE™ PANEL 68-3041-2 6 Fig. 3. EMM-3 system wiring diagram. Fig. 4. EMM-3 oil heating, electrical cooling wiring diagram. Fig. 5. Two-transformer system wiring diagram. Fig. 6. Single transformer system wiring diagram. ZONE THERMOSTATS ZONE DAMPER MOTORS M1 - common M4 - power open M6 - power closed 24 Volt Equipment Transformer(s) MOMENTARY PUSHBUTTON SWITCHES: BOOT USE THIS SWITCH TO CLEAR THE SYSTEM AND CLEAR THE MICROPROCESSOR. PURGE OVERRIDE USE THIS SWITCH TO BYPASS...
Page 7
EMM-3 ELECTRONIC MINIZONE™ PANEL 7 68-3041-2 STARTUP AND CHECKOUT After the installation is complete, check to be sure the system is working properly. See Table 4 for sequence of operation. Table 4. Trol-A-Temp Electronic MiniZone Panel Sequence Of Operation. LED DeviceTerminals Energized System Action Comments INITIAL POWERUP SYSTEM (orange)Panel G (fan) System enters Purge mode for 2-1/2 minutes. Damper(s) open to all zones.See Purge mode. Damper M4 IDLE MODE SYSTEM (off)Panel None No call for...
Page 8
EMM-3 ELECTRONIC MINIZONE™ PANEL 68-3041-2 8 ZONE 1 CALLS FOR FAN Zone 1 (green). Zones 2 and 3 (off). SYSTEM (off).Thermostat G (fan) System fan is energized. Zone 1 damper(s) remains open; all others close.When a call for cool is made, panel adjusts dampers and activates equipment as directed. When a call for heat is made, fan stays energized for two minutes of heat call. When fan call ends, Idle mode is entered. Damper Zone 1: M4. Zones 2 and 3: M6. Panel G (fan) DATS TEMPERATURE EXCEEDS...
Page 9
EMM-3 ELECTRONIC MINIZONE™ PANEL 9 68-3041-2 SERVICE Purge timing— fixed at two and one-half minutes; not field- adjustable. Fan operation in Purge mode—fan is on in Purge mode; not field adjustable.DATS Operation—High limit is 160° F (71°C); low limit is 44°F (6°C) and not field-adjustable. TROUBLESHOOTING The primary diagnostic tools are the SYSTEM and ZONE damper status LED and the BOOT and PURGE OVERRIDE buttons. See Fig. 7 and 8 for troubleshooting flowcharts. Fig. 7. Thermostat is calling for...
Page 10
EMM-3 ELECTRONIC MINIZONE™ PANEL 68-3041-2 10 Fig. 8. Thermostat is calling for heating but the system light is not turning red to show a heat call. NO START NO YES DO YOU HAVE 24 VAC ON ALL OF THE ZONES AT R-M1 OR R-C ?NO CHECK THE TRANSFORMER FOR 24 VAC. MAKE SURE THERMOSTAT IS CALLING FOR HEAT. THE PANEL MAY HAVE BEEN DAMAGED. TAKE THE R OR C WIRE OFF AGAIN FOR 10 MINUTES. AFTER 10 MINUTES, RE-ATTACH THE R OR C WIRE AND PRESS THE BOOT BUTTON. CHECK VOLTAGE AT R-M1 OR R-C ON ALL THE ZONES. IF...