Honeywell Emm 3 Manual
Have a look at the manual Honeywell Emm 3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
PRODUCT DATA 68-3041-2 ® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved EMM-3 Electronic MiniZone™ Panel APPLICATION The EMM-3 Electronic MiniZone™ Panel controls single- stage heat/cool equipment and is used on two-and three-zone applications. FEATURES • Uses any Honeywell four-wire thermostat. • Optional C7735 Discharge Air Temperature Sensor Sensor for capacity control. • SYSTEM and ZONE damper status LEDs indicate system status. • Automatic zone changeover with 20-minute changeover timer. • Individual zone fan control. • Thermal circuit breaker protects panel and transformer from damage if miswired. • Purge timer protects equipment between calls for heating and cooling. • Uses spring-open/power-closed, spring-closed/power- open, and power-open/power-closed dampers. • Interfaces with single or dual transformer equipment. For Internet access: www.honeywell.com/yourhome/zoning/zoning_home.htm For technical support: call 1-800-828-8367. To download Zoning literature: http://hbctechlit.honeywell.com Contents Application ......................................................................... 1 Features ............................................................................ 1 Specifications .................................................................... 2 Ordering Information ......................................................... 2 Installation ......................................................................... 4 Startup and Checkout ........................................................ 7 Service .............................................................................. 9 Troubleshooting ................................................................. 9
EMM-3 ELECTRONIC MINIZONE™ PANEL 698-3041-2 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1.Your local Home and Building Control Sales Office (check white pages of your phone directory). 2.Home and Building Control Customer Relations Honeywell, 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A. SPECIFICATIONS Input Ratings: DIscharge Air Temperature Sensor (DATS): 24000 to 1600 ohms. Output Ratings: Equipment Relays and Zone Relays: 1.5A run, 3.5A inrush, 200,000 cycles (30 Vac). 1.5A run, 7.5A inrush, 100,000 cycles (30 Vac). Humidity Ratings: 5% to 90% RH non-condensing. Temperature Ratings: Shipping: -20° to 120°F. Operating: -40° to 150°F. LED: SYSTEM LED: Used to communicate equipment status: Red: Heat mode. Green: Cool mode. Orange: Purge mode. Flashing Red: System exceeds high DATS input. Flashing Green: System exceeds low DATS input. Flashing Orange: No DATS or DATS failure. Off: Idle mode or Fan mode. ZONE LED (3): Used to communicate damper status: Green: Dampers are opening or open. No Color: Dampers are closing or closed. Finish: White. Dimensions: See Fig. 1. Mounting: Mounting screws provided.Wiring: 18 gauge wire for all equipment and system connec- tions. Wiring Connections: Thermostat: R-C-W-Y-G. Dampers: M6 (Closed); M4 (Open); M1 (Common). Discharge AIr Temperature Sensor: ZMS-ZMS. Transformer: R-C. Equipment: RC-RH-Y-W-G. Fig. 1. EMM-3 dimensions in in. (mm). Approvals: Federal Communications Commission: Class B. NEMA DC-3: Not required. Thermostats: Any Honeywell four-wire thermostat. M20867 10-3/4 (273) 12-3/4 (273) 1-7/8 (47) SYSTEM ZONE1 ZONE 2 ZONE 3
EMM-3 ELECTRONIC MINIZONE™ PANEL 3 68-3041-2 Dampers: Power-open/power-closed. Spring-open/power-closed. Spring-closed/power-open. See Table 2 for recommended dampers.Accessories: For required accessories, see Table 3. Table 1. Recommended Thermostats. Logo Standard ThermostatsProgrammable Thermostats Honeywell T87F1859 and Q539A1014 T87F3855 and Q539A1469 T8400C1024 T8401C1015 T8501D1046T8000C1002 T8001C1001 T8600D2069 T8601D2019 T8602D2018 PC8900A1007 and W8900A1004 Trol-A-Temp — T8601D2027 Table 2. Recommended Dampers. Honeywell Damper Type Round Rectangular Power-open/power closed MARD D643 using ML6161 Motor Actuator Spring-open/power-closed ARD ZD Table 3. Required Accessories. Accessory Description 40 VA transformer AT140D1046 Capacity protector DATS C7735A1000 Round static pressure regulator damper7 SPRD 8 SPRD 9 SPRD 10 SPRD 12 SPRD 14 SPRD 16 SPRD 300 cfm 400 cfm 600 cfm 750 cfm 1200 cfm 1800 cfm 2400 cfm Rectangular static pressure regulator damper12 x 8 SPRD 12 x 10 SPRD 12 x 12 SPRD 20 x 8 SPRD 20 x 10 SPRD 20 x 12 SPRD1000 cfm 1200 cfm 1400 cfm 1600 cfm 2000 cfm 3000 cfm
EMM-3 ELECTRONIC MINIZONE™ PANEL 68-3041-2 4 INSTALLATION Mounting CAUTION Equipment Damage Hazard. Do not mount EMM-3 inside HVAC equipment. Mount only on wall or on cold air return. 1.Mount the thermostats in each zone of the living space using the installation instructions provided with each thermostat. See Fig. 2. 2.Mount the dampers in the ductwork using the installa- tion instructions provided with each damper. 3.Mount the EMM-3 zone panel near the HVAC equip- ment; locate it on a wall or on the cold-air return. 4.Level the EMM-3 for appearance only. Fig. 2. EMM-3 mounting location. Wiring Wiring must comply with applicable codes, ordinances, and regulations. See Fig. 3-6 for wiring diagrams. CAUTION Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before beginning installation. 1.Connect 24 Vac transformer to R and C terminals on EMM-3. 2.Connect HVAC equipment to R C,RH,W,Y and G termi- nals on EMM-3. (Use jumper between R C and RH if using single equipment transformer.) 3.Connect the dampers for zone 1, 2 and 3 to EMM-3. See instructions packed with dampers.4.Connect the zone 1 thermostat to EMM-3. 5.Reconnect power to EMM-3. 6.Check out connections made in steps 1 through 5: a. If system is in Purge mode, press PURGE OVER- RIDE on EMM-3. b. Set Zone 1 thermostat to call for heat: (1) Zone 1 damper is open. Zone 1 LED on EMM-3 is green. (2) Zones 2 and 3 dampers are closed. Zones 2 and 3 LED on EMM-3 are off. (3) Heating equipment is activated. SYSTEM LED is red. (4) Continue wiring the system. CAUTION Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before continuing installation. 7.Connect Zone 2 thermostat to EMM-3. 8.Reconnect power to EMM-3. 9.Check out connections made in steps 1 through 8: a. If system is in Purge mode, press PURGE OVER- RIDE on EMM-3. b. Set Zone 2 thermostat to call for heat, set Zone 1 thermostat to off: (1) Zone 2 damper is open. Zone 2 LED on EMM-3 is green. (2) Zones 1 and 3 dampers are closed. Zones 1 and 3 LED on EMM-3 are off. (3) Heating equipment is activated. SYSTEM LED is red. (4) Continue wiring the system. CAUTION Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before continuing installation. 10.Connect zone three thermostat to EMM-3. 11 .Reconnect power to EMM-3. 12.Check out connections made in steps 1 through 11: a. If system is in Purge mode, press PURGE OVER- RIDE on EMM-3. b. Set Zones 1 and 2 thermostats to Off. c. Set Zone 3 thermostat to call for heat. M13540 WATER HEATEREMM-3E LE CTR ONIC A IR CLEA N ER RETURNAIR EMM-3 OPTIONAL LOCATION FURNACE OR BOILER HIGH EFFICIENCY AIR CLEANER System Zone 1 Zone 2 Zone 3 LEDRed Green Off Off System OperationHeat on Open Closed Closed System Zone 1 Zone 2 Zone 3 LEDRed Off Green Off System OperationHeat on Closed Open Closed
EMM-3 ELECTRONIC MINIZONE™ PANEL 5 68-3041-2 (1) Zone 3 damper is open. Zone 3 LED on EMM-3 is green. (2) Zone 1 and 2 dampers are closed. Zone 1 and 2 LED on EMM-3 are off. (3) Heating equipment is activated. SYSTEM LED is red. (4) Continue wiring the system. CAUTION Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before continuing installation. 13.Reconnect power to EMM-3. 14.Continue troubleshooting system in Cool mode. a. Set Zone 1 thermostat to Cool mode and Zones 2 and 3 thermostats to off. b. Zone 1 damper is open. Zone 1 LED on EMM-3 is green. c. Zones 1 and 3 dampers are closed. Zones 2 and 3 LED on EMM-3 are off. d. Cooling equipment is activated. SYSTEM LED is green. e. Repeat procedure for zones 2 and 3. Continue wir- ing the system. CAUTION Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before continuing installation. 15.Reconnect power to EMM-3 16.Check out fan operation. a. Set Zone 1 thermostat fan switch to On, and Zones 2 and 3 thermostats to Auto. b. Zone 1 damper is open. Zone 1 LED on EMM-3 is green. c. Zones 2 and 3 dampers are closed. Zones 2 and 3 LED on EMM-3 are off. d. Fan equipment is activated. SYSTEM LED is off. e. Repeat procedure for zones 2 and 3. Continue wir- ing the system. CAUTION Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before continuing installation. 17.Connect DATS Sensor to EMM-3 (optional). a. Reconnect power to EMM-3. b. If system is in Purge mode, press PURGE OVER- RIDE on EMM-3. c. Verify SYSTEM LED is no longer flashing. This con- firms proper DATS operation. (Flashing occurs in Idle and Fan modes only.) System Zone 1 Zone 2 Zone 3 LEDRed Off Off Green System OperationHeat on Closed Closed Open System Zone 1 Zone 2 Zone 3 LEDGreen Green Off Off System OperationCool on Open Closed Closed System Zone 1 Zone 2 Zone 3 LEDOff Green Off Off System OperationFan on Open Closed Closed
EMM-3 ELECTRONIC MINIZONE™ PANEL 68-3041-2 6 Fig. 3. EMM-3 system wiring diagram. Fig. 4. EMM-3 oil heating, electrical cooling wiring diagram. Fig. 5. Two-transformer system wiring diagram. Fig. 6. Single transformer system wiring diagram. ZONE THERMOSTATS ZONE DAMPER MOTORS M1 - common M4 - power open M6 - power closed 24 Volt Equipment Transformer(s) MOMENTARY PUSHBUTTON SWITCHES: BOOT USE THIS SWITCH TO CLEAR THE SYSTEM AND CLEAR THE MICROPROCESSOR. PURGE OVERRIDE USE THIS SWITCH TO BYPASS THE PURGE CYCLE WHILE TROUBLESHOOTING THE SYSTEM. LED STATES: SYSTEM LED RED HEATING MODE GREEN COOLING MODE ORANGE PURGE MODE FLASHING RED ZMS SENSOR EXCEEDS HIGH LIMIT IN HEATING FLASHING GREEN ZMS SENSOR EXCEEDS LOW LIMIT IN COOLING FLASHING ORANGE NO ZoneMAX SENSOR INSTALLED OR ZoneMAX SENSOR FAILURE DAMPER STATUS LEDS ON (GREEN COLOR) DAMPER IS OPEN OR OPENING OFF (NO COLOR) DAMPER IS CLOSED OR CLOSING R HRCY W G BOOT PURGE OVERRIDE Single Transformer Heating/Cooling systems require a jumper to be installed between R H and RC(factory installed). * C terminal connection is not required on battery powered, power stealing, or some electromechanical thermostats. EQUIPMENTDischarge Ai rTemperature Sensor (See C7735 Installation Instructions for further information.) ZONEMAX R C ZMS ZMS Heating Transformer Cooling Transformer Cool Relay Heat Relay Fan Relay This diagram shows the typical single stage equipment, thermostat, and damper motor connections. For specific wiring for other thermostats, damper motors, and HVAC Equipment, refer to the Installation Instructions.R Y W G C M6M4M1 RYW G 456Z 123XC * Zone 1 Thermostat Power-open Power-closed (Opposed Blade ZONE 1R Y W G C M6M4M1 R YCR WG C * Zone 2 Thermostat Power-closed Spring-open (Model ZD) ZONE 2RYWGCM6M4M1 RYWGC * Zone 3 Thermostat Power-closed Spring-open (Model ARD) ZONE 3 24 Volt 40VA Transformer 24VAC 40VA ZONE PANEL TRANSFORMER SYSTEM LED ZONE 1 ZONE 2 DAMPER STATUS LEDS ZONE 3 TT 24V OIL PRIMARY PANEL R H RC Y W G FAN RELAY COOLING CONTACTOR M13537REMOVE FACTORY INSTALLED RH TO RC JUMPER.11 L1 (HOT) L2 L1 (HOT) L2 COOLING TRANSFORMER HEATING TRANSFORMER PANEL R H RC Y W G M13538REMOVE FACTORY INSTALLED RH TO RC JUMPER.11 L1 (HOT) L2 HEAT RELAY L1 (HOT)L2 FAN RELAY COOLING CONTACTOR TRANSFORMERPANEL R H RC Y W G INSTALL JUMPER BETWEEN RH AND RC.1 1 HEAT RELAY L1 (HOT) L2COOLING CONTACTOR FAN RELAY
EMM-3 ELECTRONIC MINIZONE™ PANEL 7 68-3041-2 STARTUP AND CHECKOUT After the installation is complete, check to be sure the system is working properly. See Table 4 for sequence of operation. Table 4. Trol-A-Temp Electronic MiniZone Panel Sequence Of Operation. LED DeviceTerminals Energized System Action Comments INITIAL POWERUP SYSTEM (orange)Panel G (fan) System enters Purge mode for 2-1/2 minutes. Damper(s) open to all zones.See Purge mode. Damper M4 IDLE MODE SYSTEM (off)Panel None No call for heating or cooling. Equipment terminals are not energized. If SYSTEM LED flashes orange, DATS is not connected or is out- of-range. PURGE MODE ZONE (orange)Thermostat None Damper from last zone to call remains open; all others remain closed for 2-1/2 minutes after thermostat call ends. After 2-1/2 minutes, if no other call for heating or cooling is required, all dampers open.Panel enters Purge mode after each call for heat and cool; this allows heat exchanger to dissipate more conditioned air into the zone. Damper M4 Panel G (fan) ZONE 1 INITIATES CALL FOR HEAT SYSTEM (red) Zone 1 (green).Thermostat W (heat) Zone 1 thermostat calls for heat. Zone 1 damper(s) remains open. Zones 2 and 3 dampers close. Panel calls for heat.Heat is delivered only in zone 1. When another zone calls for heat while zone 1 is calling, that zone damper opens. For electric heat applications, use thermostat that calls for fan with all calls for heat. Damper Zone1: M4 Zones 2 and 3: M6 Panel W (heat) ZONE 1 ENDS CALL FOR HEAT SYSTEM (orange)Thermostat None System enters Purge mode. Damper(s) from zone 1 remains open; all others remain closed for 2-1/2 minutes after zone 1 thermostat call ends. After 2-1/2 minutes, all dampers open (M4 energized).None. Damper Zone 1: M4. Zones 2 and 3: M6. Panel G (fan) ZONE 1 INITIATES CALL FOR COOL SYSTEM (green). Zone 1 (green).Thermostat Y (cool) G (fan)Zone 1 thermostat calls for cool and fan. Zone 1 damper(s) remains open. Zones 2 and 3 dampers close. Panel calls for cool and fan.Cool is delivered only to zone 1. If another zone calls for cool while zone 1 is calling, the damper to that zone opens. In retrofit applications, where only three wires are available, Y signal from thermostat activates Y and G call from panel Damper Zone 1: M4. Zones 2 and 3: M6. Panel Y (cool). G (fan). ZONE 1 ENDS CALL FOR COOL SYSTEM (orange)Thermostat None System enters Purge mode. Damper(s) from zone 1 remains open; all others remain closed for 2-1/2 minutes after zone 1 thermostat call ends. After 2-1/2 minutes, all dampers open (M4 energized).None. Damper Zone 1: M4. Zones 2 and 3: M6. Panel G (fan)
EMM-3 ELECTRONIC MINIZONE™ PANEL 68-3041-2 8 ZONE 1 CALLS FOR FAN Zone 1 (green). Zones 2 and 3 (off). SYSTEM (off).Thermostat G (fan) System fan is energized. Zone 1 damper(s) remains open; all others close.When a call for cool is made, panel adjusts dampers and activates equipment as directed. When a call for heat is made, fan stays energized for two minutes of heat call. When fan call ends, Idle mode is entered. Damper Zone 1: M4. Zones 2 and 3: M6. Panel G (fan) DATS TEMPERATURE EXCEEDS 160° (71°C) IN ZONE 1 CALL FOR HEAT SYSTEM (flashes red)Thermostat W (heat) Thermostat continues to call for heat, but panel ignores call. Damper(s) from zone 1 remains open; all others are closed. Panel activates system fan for 2-1/2 minutes and until DATS temperature drops more than 10°F (-12°C).After 2-1/2 minutes and more than 10°F (-12°C) temperature drop, the panel returns to Heat mode (if call still exists), delivering heat to zone 1 and any other zone calling for heat. Fan stays on first two minutes of heat call. Damper Zone 1: M4. Zones 2 and 3: M6. Panel G (fan) DATS TEMPERATURE FALLS BELOW 44°F (6°C) IN ZONE 1 CALL FOR COOL SYSTEM (flashes green)Thermostat Y (cool) G (fan)Thermostat continues to call for cool and fan, but panel ignores cool call. Damper(s) from zone 1 remains open; all others are closed. Panel activates system fan for 2-1/2 minutes and until DATS temperature rises more than 10°F (-12°C).After 2-1/2 minutes and more than 10°F (-12°C) temperature rise, the panel returns to Cool mode (if call still exists), delivering cooling to zone 1 and any other zone calling for cool. Damper Zone 1: M4. Zones 2 and 3: M6. Panel G (fan) AFTER BOOT BUTTON IS PRESSED SYSTEM (orange)Panel G (fan) System enters Purge mode for 2-1/2 minutes. Dampers to all zones open.See Purge mode. Dampers M4 PURGE OVERRIDE BUTTON IS PRESSED None Panel None Panel exits Purge mode after approximately 2 seconds. Panel waits for next call for heat, cool or fan from zone thermostats. If no calls exist, panel remains in Idle mode.Used to troubleshoot the system. Pressing the button cancels the Purge mode and makes troubleshooting the system quicker and easier. PANEL RECEIVES SIMULTANEOUS CALLS FOR HEAT AND COOL FROM DIFFERENT ZONES None Panel None Panel defaults to the last type of call (heat or cool) to determine which type of conditioning to choose.When the first call for conditioning ends, the panel enters the Purge mode, then delivers conditioning to the other zone(s), as required. WHILE ZONE 1 CALLS FOR HEAT, ZONE 2 CALLS FOR COOL None Panel None Panel delivers heat into zone 1 until call is satisfied or for a 20- minute delay, whichever occurs first. Panel enters Purge mode. Panel delivers cool into zone 2 until call is satisfied, or for a 20-minute delay, whichever occurs first.Prevents one zone from never receiving conditioning because it is requesting the opposite device. Table 4. Trol-A-Temp Electronic MiniZone Panel Sequence Of Operation. (Continued) LED DeviceTerminals Energized System Action Comments
EMM-3 ELECTRONIC MINIZONE™ PANEL 9 68-3041-2 SERVICE Purge timing— fixed at two and one-half minutes; not field- adjustable. Fan operation in Purge mode—fan is on in Purge mode; not field adjustable.DATS Operation—High limit is 160° F (71°C); low limit is 44°F (6°C) and not field-adjustable. TROUBLESHOOTING The primary diagnostic tools are the SYSTEM and ZONE damper status LED and the BOOT and PURGE OVERRIDE buttons. See Fig. 7 and 8 for troubleshooting flowcharts. Fig. 7. Thermostat is calling for cooling but the system light is not turning green to show a cool call. NO START NO YES IS 24 VAC ON ALL OF THE ZONES AT R-M1 OR R-C ?NO CHECK THE TRANSFORMER FOR 24 VAC. THERMOSTAT MAY BE IN A 5 MIN DELAY IN COOLING. MAKE SURE THERMOSTAT IS CALLING FOR COOLING. THE PANEL MAY HAVE BEEN DAMAGED. TAKE THE R OR C WIRE OFF AGAIN FOR 10 MINUTES. AFTER 10 MINUTES, RE-ATTACH THE R OR C WIRE AND PRESS THE BOOT BUTTON. CHECK VOLTAGE AT R-M1 OR R-C ON ALL THE ZONES. IF NO VOLTAGE AT R-M1 OR R-C, REPLACE THE EMM PANEL. RE-ATTACH EACH ZONE THERMOSTAT WIRE. ATTACH EACH ZONE SEPARATELY, CHECKING AFTER EACH ZONE IS ATTACHED IF THE THERMAL FUSE HAS TRIPPED. AFTER ATTACHING THE THERMOSTAT WIRES, ATTACH EACH MOTOR ZONE WIRES, AGAIN CHECKING THE THERMAL FUSE TO SEE IF IT TRIPS. THIS STEP-BY-STEP PROCESS SHOULD HELP YOU IDENTIFY WHAT IS TRIPPING THE THERMAL FUSE ON THE PANEL. YES YES IS 24 VAC AT R AND C ON THE EMM PANEL ? CHECK FOR 24 VAC AT Y-M1 OR Y-C ON THE EMM PANEL. (YOU SHOULD HAVE 24 VAC.) IS THE THERMOSTAT CALLING FOR COOL? IS THERE CONTINUITY AT R C-Y ON THE EQUIPMENT CONTACTS OF THE EMM PANEL?NO NO NOTHE THERMAL FUSE HAS TRIPPED. REMOVE THE R OR C (TRANSFORMER POWER) WIRE FROM THE PANEL FOR 15 SECONDS AND ALLOW THE FUSE TO RESET. TAKE THE THERMOSTAT AND DAMPER WIRES OFF FROM EACH ZONE BEFORE YOU RE-ATTACH THE R OR C WIRE. IS THERE VOLTAGE AT R-M1 OR R-C ON ALL OF THE ZONES?IS THERE 24 VAC AT Y-C ON THE THERMOSTAT? DO YOU HAVE A DATS HOOKED TO THE PANEL?NO YES YES YES YES JUMPER THE R WIRE TO THE Y WIRE ON THE THERMOSTAT. IF THE COOL LIGHT COMES ON, YOU HAVE A BAD THERMOSTAT. REPLACE THERMOSTAT. IF YOU JUMPER R-Y ON THE THERMOSTAT AND THE COOL LIGHT DOES NOT COME ON, YOU MAY HAVE A BAD WIRE. TRY ANOTHER SET OF WIRES OR CHECK CONTINUITY. IT COULD BE A BAD WIRE. IF YOU HAVE VOLTAGE ON THE PANEL AT Y-C BUT NOT AT THE THERMOSTAT, THEN IT IS A WIRE. CHECK FOR VOLTAGE AT R-W, G ON THE THERMOSTAT. IF THERE IS VOLTAGE, IT IS A BAD Y WIRE. IF NO VOLTAGE AT R-ANY OTHER TERMINAL ON THE THERMOSTAT, IT IS A BAD R WIRE. YES NO THE COOLING EQUIPMENT SHOULD BE ON. SEEMS LIKE THE PANEL IS WORKING BUT THE SYSTEM LIGHT IS NOT. REPLACE PANEL. M13543A DID THE EMM PANEL HAVE ANY CONDENSATION ON IT? WAS IT STORED IN A COLD PLACE BEFORE BEING INSTALLED? IF SO, THIS COULD CAUSE THE PANEL TO MALFUNCTION. LET THE PANEL ADAPT TO THE NEW CONDITIONS BEFORE POWER UP. YES REMOVE THE DATS WIRES FROM THE BOARD. RETURN TO “IS THE THERMOSTAT CALLING FOR COOL” PART OF THE FLOWCHART AND BEGIN TROUBLESHOOTING FROM THAT POINT. REMOVE ALL WIRES FROM THE PANEL EXCEPT R AND C (POWER FROM THE TRANSFORMER). JUMPER R-Y ON ONE OF THE ZONES. IF THE SYSTEM LIGHT DOES NOT TURN GREEN, REPLACE THE PANEL.NO
EMM-3 ELECTRONIC MINIZONE™ PANEL 68-3041-2 10 Fig. 8. Thermostat is calling for heating but the system light is not turning red to show a heat call. NO START NO YES DO YOU HAVE 24 VAC ON ALL OF THE ZONES AT R-M1 OR R-C ?NO CHECK THE TRANSFORMER FOR 24 VAC. MAKE SURE THERMOSTAT IS CALLING FOR HEAT. THE PANEL MAY HAVE BEEN DAMAGED. TAKE THE R OR C WIRE OFF AGAIN FOR 10 MINUTES. AFTER 10 MINUTES, RE-ATTACH THE R OR C WIRE AND PRESS THE BOOT BUTTON. CHECK VOLTAGE AT R-M1 OR R-C ON ALL THE ZONES. IF NO VOLTAGE AT R-M1 OR R-C, REPLACE THE EMM PANEL. RE-ATTACH EACH ZONE THERMOSTAT WIRE. ATTACH EACH ZONE SEPARATELY, CHECKING AFTER EACH ZONE IS ATTACHED IF THE THERMAL FUSE HAS TRIPPED. AFTER ATTACHING THE THERMOSTAT WIRES, ATTACH EACH MOTOR ZONE WIRES, AGAIN CHECKING THE THERMAL FUSE TO SEE IF IT TRIPS. THIS STEP-BY-STEP PROCESS SHOULD HELP YOU IDENTIFY WHAT IS TRIPPING THE THERMAL FUSE ON THE PANEL. YES YES IS THERE 24 VAC AT THE TRANSFORMER R AND C ON THE EMM PANEL? CHECK FOR 24 VAC AT W-M1 OR W-C ON THE EMM PANEL. (YOU SHOULD HAVE 24 VAC.) IS THE THERMOSTAT CALLING FOR HEAT? IS THERE CONTINUITY AT R H-W ON THE EQUIPMENT CONTACTS OF THE EMM PANEL?NO NO NOTHE THERMAL FUSE HAS TRIPPED. REMOVE THE R OR C (TRANSFORMER POWER) WIRE FROM THE PANEL FOR 15 SECONDS AND ALLOW THE FUSE TO RESET. TAKE THE THERMOSTAT AND DAMPER WIRES OFF FROM EACH ZONE BEFORE YOU RE-ATTACH THE R OR C WIRE. IS THERE VOLTAGE AT R-M1 OR R-CON ALL OF THE ZONES?IS THERE 24 VAC AT W-C ON THE THERMOSTAT? DO YOU HAVE A DATS HOOKED TO THE PANEL?NO YES YES YES YES JUMPER THE R WIRE TO THE W WIRE ON THE THERMOSTAT. IF THE HEAT LIGHT COMES ON, YOU HAVE A BAD THERMOSTAT. REPLACE THERMOSTAT. IF YOU JUMPER R-W ON THE THERMOSTAT AND THE HEAT LIGHT DOES NOT COME ON, YOU MAY HAVE A BAD WIRE. TRY ANOTHER SET OF WIRES OR CHECK CONTINUITY. IT COULD BE A BAD WIRE. IF YOU HAVE VOLTAGE ON THE PANEL AT W-C BUT NOT AT THE THERMOSTAT, THEN IT IS A WIRE. CHECK FOR VOLTAGE AT R-Y, G ON THE THERMOSTAT. IF THERE IS VOLTAGE, IT IS A BAD W WIRE. IF NO VOLTAGE AT R-ANY OTHER TERMINAL ON THE THERMOSTAT, IT IS A BAD R WIRE. YES NO THE HEATING EQUIPMENT SHOULD BE ON. SEEMS LIKE THE PANEL IS WORKING BUT THE SYSTEM LIGHT IS NOT. REPLACE PANEL. M13546A DID THE EMM PANEL HAVE ANY CONDENSATION ON IT? WAS IT STORED IN A COLD PLACE BEFORE BEING INSTALLED? IF SO, THIS COULD CAUSE THE PANEL TO MALFUNCTION. LET THE PANEL ADAPT TO THE NEW CONDITIONS BEFORE POWERUP. YES REMOVE THE DATS WIRES FROM THE PANEL. RETURN TO “IS THE THERMOSTAT CALLING FOR HEAT” PART OF THE FLOWCHART AND BEGIN TROUBLESHOOTING FROM THAT POINT. REMOVE ALL WIRES FROM THE PANEL EXCEPT R AND C (POWER FROM THE TRANSFORMER). JUMPER R-W ON ONE OF THE ZONES. IF THE SYSTEM LIGHT DOES NOT TURN RED, REPLACE THE PANEL.NO