Home > Honeywell > Thermostat > Honeywell Emm 3 Manual

Honeywell Emm 3 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Emm 3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							PRODUCT DATA
    68-3041-2
    ® U.S. Registered Trademark
    Copyright © 2002 Honeywell •  All Rights Reserved 
    EMM-3
    Electronic MiniZone™ Panel
    APPLICATION
    The EMM-3 Electronic MiniZone™ Panel controls single-
    stage heat/cool equipment and is used on two-and three-zone 
    applications.
    FEATURES
    • Uses any Honeywell four-wire thermostat.
    • Optional C7735 Discharge Air Temperature Sensor 
    Sensor for capacity control.
    • SYSTEM and ZONE damper status LEDs indicate 
    system status.
    • Automatic zone changeover with 20-minute 
    changeover timer.
    • Individual zone fan control.
    • Thermal circuit breaker protects panel and transformer 
    from damage if miswired.
    • Purge timer protects equipment between calls for 
    heating and cooling.
    • Uses spring-open/power-closed, spring-closed/power-
    open, and power-open/power-closed dampers.
    • Interfaces with single or dual transformer equipment.
    For Internet access:
    www.honeywell.com/yourhome/zoning/zoning_home.htm
    For technical support: call 1-800-828-8367.
    To download Zoning literature:
    http://hbctechlit.honeywell.com
    Contents
    Application ......................................................................... 1
    Features ............................................................................ 1
    Specifications .................................................................... 2
    Ordering Information ......................................................... 2
    Installation ......................................................................... 4
    Startup and Checkout ........................................................ 7
    Service .............................................................................. 9
    Troubleshooting ................................................................. 9 
    						
    							EMM-3 ELECTRONIC MINIZONE™ PANEL
    698-3041-2 2
    ORDERING INFORMATION
    When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 
    TRADELINE® Catalog or price sheets for complete ordering number.
    If you have additional questions, need further information, or would like to comment on our products or services, please write or 
    phone:
    1.Your local Home and Building Control Sales Office (check white pages of your phone directory).
    2.Home and Building Control Customer Relations
    Honeywell, 1885 Douglas Drive North
    Minneapolis, Minnesota 55422-4386
    In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
    International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 
    Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
    SPECIFICATIONS
    Input Ratings: DIscharge Air Temperature Sensor (DATS): 
    24000 to 1600 ohms.
    Output Ratings:
    Equipment Relays and Zone Relays:
    1.5A run, 3.5A inrush, 200,000 cycles (30 Vac).
    1.5A run, 7.5A inrush, 100,000 cycles (30 Vac).
    Humidity Ratings:  5% to 90% RH non-condensing. 
    Temperature Ratings:
    Shipping: -20° to 120°F.
    Operating: -40° to 150°F.
    LED:
    SYSTEM LED: Used to communicate equipment status:
    Red: Heat mode.
    Green: Cool mode.
    Orange: Purge mode.
    Flashing Red: System exceeds high DATS input.
    Flashing Green: System exceeds low DATS input.
    Flashing Orange: No DATS or DATS failure.
    Off: Idle mode or Fan mode.
    ZONE LED (3): Used to communicate damper status:
    Green: Dampers are opening or open.
    No Color: Dampers are closing or closed.
    Finish: White.
    Dimensions: See Fig. 1.
    Mounting: Mounting screws provided.Wiring: 18 gauge wire for all equipment and system connec-
    tions.
    Wiring Connections:
    Thermostat: R-C-W-Y-G.
    Dampers: M6 (Closed); M4 (Open); M1 (Common).
    Discharge AIr Temperature Sensor: ZMS-ZMS.
    Transformer: R-C.
    Equipment: RC-RH-Y-W-G.
    Fig. 1. EMM-3 dimensions in in. (mm).
    Approvals:
    Federal Communications Commission: Class B.
    NEMA DC-3: Not required.
    Thermostats:
    Any Honeywell four-wire thermostat.
    M20867
    10-3/4
    (273)
    12-3/4
    (273)
    1-7/8
    (47)
    SYSTEM ZONE1 ZONE 2 ZONE 3 
    						
    							EMM-3 ELECTRONIC MINIZONE™ PANEL
    3 68-3041-2
    Dampers:
    Power-open/power-closed.
    Spring-open/power-closed.
    Spring-closed/power-open.
    See Table 2 for recommended dampers.Accessories: For required accessories, see Table 3.
    Table 1. Recommended Thermostats.
    Logo Standard ThermostatsProgrammable 
    Thermostats
    Honeywell T87F1859 and Q539A1014
    T87F3855 and Q539A1469
    T8400C1024
    T8401C1015
    T8501D1046T8000C1002
    T8001C1001
    T8600D2069
    T8601D2019
    T8602D2018
    PC8900A1007 
    and
    W8900A1004
    Trol-A-Temp — T8601D2027
    Table 2. Recommended Dampers.
    Honeywell Damper Type Round Rectangular
    Power-open/power closed MARD D643 using 
    ML6161 Motor 
    Actuator
    Spring-open/power-closed ARD ZD
    Table 3. Required Accessories.
    Accessory Description
    40 VA transformer AT140D1046
    Capacity protector DATS C7735A1000
    Round static pressure 
    regulator damper7   SPRD
    8   SPRD
    9   SPRD
    10 SPRD
    12 SPRD
    14 SPRD
    16 SPRD 300  cfm
     400  cfm
     600  cfm
     750  cfm
    1200 cfm
    1800 cfm
    2400 cfm
    Rectangular static 
    pressure regulator 
    damper12 x 8   SPRD
    12 x 10 SPRD
    12 x 12 SPRD
    20 x 8   SPRD
    20 x 10 SPRD
    20 x 12 SPRD1000 cfm
    1200 cfm
    1400 cfm
    1600 cfm
    2000 cfm
    3000 cfm 
    						
    							EMM-3 ELECTRONIC MINIZONE™ PANEL
    68-3041-2 4
    INSTALLATION
    Mounting
    CAUTION
    Equipment Damage Hazard.
    Do not mount EMM-3 inside HVAC equipment.
    Mount only on wall or on cold air return.
    1.Mount the thermostats in each zone of the living space 
    using the installation instructions provided with each 
    thermostat. See Fig. 2.
    2.Mount the dampers in the ductwork using the installa-
    tion instructions provided with each damper.
    3.Mount the EMM-3 zone panel near the HVAC equip-
    ment; locate it on a wall or on the cold-air return. 
    4.Level the EMM-3 for appearance only.
    Fig. 2. EMM-3 mounting location.
    Wiring
    Wiring must comply with applicable codes, ordinances, and 
    regulations.
    See Fig. 3-6 for wiring diagrams.
    CAUTION
    Voltage Hazard. 
    Can cause electrical shock or equipment damage.
    Disconnect power before beginning installation.
    1.Connect 24 Vac transformer to R and C terminals on 
    EMM-3.
    2.Connect HVAC equipment to R
    C,RH,W,Y and G termi-
    nals on EMM-3. (Use jumper between R
    C and RH if 
    using single equipment transformer.)
    3.Connect the dampers for zone 1, 2 and 3 to EMM-3. 
    See instructions packed with dampers.4.Connect the zone 1 thermostat to EMM-3.
    5.Reconnect power to EMM-3.
    6.Check out connections made in steps 1 through 5:
    a. If system is in Purge mode, press PURGE OVER-
    RIDE on EMM-3.
    b. Set Zone 1 thermostat to call for heat:
    (1) Zone 1 damper is open. Zone 1 LED on EMM-3 
    is green.
    (2) Zones 2 and 3 dampers are closed. Zones 2 and 
    3 LED on EMM-3 are off.
    (3) Heating equipment is activated. SYSTEM LED is 
    red.
    (4) Continue wiring the system.
    CAUTION
    Voltage Hazard. 
    Can cause electrical shock or equipment damage.
    Disconnect power before continuing installation.
    7.Connect Zone 2 thermostat to EMM-3.
    8.Reconnect power to EMM-3.
    9.Check out connections made in steps 1 through 8:
    a. If system is in Purge mode, press PURGE OVER-
    RIDE on EMM-3.
    b. Set Zone 2 thermostat to call for heat, set Zone 1 
    thermostat to off:
    (1) Zone 2 damper is open. Zone 2 LED on EMM-3 
    is green.
    (2) Zones 1 and 3 dampers are closed. Zones 1 and 
    3 LED on EMM-3 are off.
    (3) Heating equipment is activated. SYSTEM LED is 
    red.
    (4) Continue wiring the system.
    CAUTION
    Voltage Hazard. 
    Can cause electrical shock or equipment damage.
    Disconnect power before continuing installation.
    10.Connect zone three thermostat to EMM-3.
    11 .Reconnect power to EMM-3.
    12.Check out connections made in steps 1 through 11:
    a. If system is in Purge mode, press PURGE OVER-
    RIDE on EMM-3.
    b. Set Zones 1 and 2 thermostats to Off.
    c. Set Zone 3 thermostat to call for heat.
    M13540
    WATER 
    HEATEREMM-3E
    LE
    CTR
    ONIC
     A
    IR 
    CLEA
    N
    ER
    RETURNAIR
    EMM-3
    OPTIONAL
    LOCATION
    FURNACE 
    OR BOILER
    HIGH
     EFFICIENCY
    AIR CLEANER
    System Zone 1 Zone 2 Zone 3
    LEDRed Green Off Off
    System 
    OperationHeat on Open Closed Closed
    System Zone 1 Zone 2 Zone 3
    LEDRed Off Green Off
    System 
    OperationHeat on Closed  Open Closed 
    						
    							EMM-3 ELECTRONIC MINIZONE™ PANEL
    5 68-3041-2
    (1) Zone 3 damper is open. Zone 3 LED on EMM-3 
    is green.
    (2) Zone 1 and 2 dampers are closed. Zone 1 and 2 
    LED on EMM-3 are off.
    (3) Heating equipment is activated. SYSTEM LED is 
    red.
    (4) Continue wiring the system.
    CAUTION
    Voltage Hazard. 
    Can cause electrical shock or equipment damage.
    Disconnect power before continuing installation.
    13.Reconnect power to EMM-3.
    14.Continue troubleshooting system in Cool mode.
    a. Set Zone 1 thermostat to Cool mode and Zones 2 
    and 3 thermostats to off.
    b. Zone 1 damper is open. Zone 1 LED on EMM-3 is 
    green.
    c. Zones 1 and 3 dampers are closed. Zones 2 and 3 
    LED on EMM-3 are off.
    d. Cooling equipment is activated. SYSTEM LED is 
    green.
    e. Repeat procedure for zones 2 and 3. Continue wir-
    ing the system.
    CAUTION
    Voltage Hazard. 
    Can cause electrical shock or equipment damage.
    Disconnect power before continuing installation.
    15.Reconnect power to EMM-3
    16.Check out fan operation.
    a. Set Zone 1 thermostat fan switch to On, and Zones 
    2 and 3 thermostats to Auto.
    b. Zone 1 damper is open. Zone 1 LED on EMM-3 is 
    green.
    c. Zones 2 and 3 dampers are closed. Zones 2 and 3 
    LED on EMM-3 are off.
    d. Fan equipment is activated. SYSTEM LED is off.
    e. Repeat procedure for zones 2 and 3. Continue wir-
    ing the system.
    CAUTION
    Voltage Hazard. 
    Can cause electrical shock or equipment damage.
    Disconnect power before continuing installation.
    17.Connect DATS Sensor to EMM-3 (optional).
    a. Reconnect power to EMM-3.
    b. If system is in Purge mode, press PURGE OVER-
    RIDE on EMM-3.
    c. Verify SYSTEM LED is no longer flashing. This con-
    firms proper DATS operation. (Flashing occurs in 
    Idle and Fan modes only.) System Zone 1 Zone 2 Zone 3
    LEDRed Off Off Green
    System 
    OperationHeat on Closed Closed Open
    System Zone 1 Zone 2 Zone 3
    LEDGreen Green Off Off 
    System 
    OperationCool on Open Closed Closed
    System Zone 1 Zone 2 Zone 3
    LEDOff Green Off Off 
    System 
    OperationFan on Open Closed Closed 
    						
    							EMM-3 ELECTRONIC MINIZONE™ PANEL
    68-3041-2 6
    Fig. 3. EMM-3 system wiring diagram.
    Fig. 4. EMM-3 oil heating, electrical 
    cooling wiring diagram.
    Fig. 5. Two-transformer system wiring diagram.
    Fig. 6. Single transformer system wiring diagram.
    ZONE
    THERMOSTATS
    ZONE DAMPER MOTORS
    M1 - common
    M4 - power open
    M6 - power closed
    24 Volt Equipment
    Transformer(s)
    MOMENTARY PUSHBUTTON SWITCHES:
      BOOT  USE THIS SWITCH TO CLEAR THE SYSTEM
       AND CLEAR THE MICROPROCESSOR.
      PURGE OVERRIDE  USE THIS SWITCH TO BYPASS THE PURGE
        CYCLE WHILE TROUBLESHOOTING THE SYSTEM.
    LED STATES:
     SYSTEM LED
      RED  HEATING MODE
      GREEN  COOLING MODE
      ORANGE  PURGE MODE
        FLASHING RED  ZMS SENSOR EXCEEDS HIGH LIMIT IN HEATING
        FLASHING GREEN  ZMS SENSOR EXCEEDS LOW LIMIT IN COOLING
        FLASHING ORANGE  NO ZoneMAX SENSOR INSTALLED
          OR ZoneMAX SENSOR FAILURE
      DAMPER STATUS LEDS
        ON (GREEN COLOR)  DAMPER IS OPEN OR OPENING
        OFF (NO COLOR)  DAMPER IS CLOSED OR CLOSING R
    HRCY
    W
    G
    BOOT PURGE
    OVERRIDE
    Single Transformer 
    Heating/Cooling systems
    require a jumper to be installed
    between R
    H and RC(factory installed).
    *  C terminal connection is not
      required on battery powered,
      power stealing, or some
     electromechanical thermostats. EQUIPMENTDischarge Ai
    rTemperature
    Sensor
    (See C7735
    Installation Instructions
    for further information.)
    ZONEMAX
    R
    C ZMS
    ZMS
    Heating Transformer
    Cooling Transformer
    Cool Relay
    Heat Relay
    Fan Relay
    This diagram shows the typical single
    stage equipment, thermostat, and
    damper motor connections.  For specific
    wiring for other thermostats, damper
    motors, and HVAC Equipment,
    refer to the Installation Instructions.R Y W G C M6M4M1
    RYW
    G
    456Z
    123XC
    *
    Zone 1 Thermostat
    Power-open
    Power-closed
    (Opposed Blade
    ZONE 1R Y W G C M6M4M1
    R
    YCR
    WG C
    *
    Zone 2 Thermostat
    Power-closed
    Spring-open
    (Model ZD)
    ZONE 2RYWGCM6M4M1
    RYWGC
    *
    Zone 3 Thermostat
    Power-closed
    Spring-open
    (Model ARD)
    ZONE 3
    24 Volt 40VA 
    Transformer 24VAC
    40VA
    ZONE PANEL
    TRANSFORMER
    SYSTEM
    LED
    ZONE 1 ZONE 2
    DAMPER STATUS LEDS
    ZONE 3
    TT
    24V OIL PRIMARY
    PANEL
    R
    H
    RC
    Y
    W
    G
    FAN
    RELAY
    COOLING
    CONTACTOR
    M13537REMOVE FACTORY INSTALLED RH TO RC JUMPER.11
    L1
    (HOT)
    L2
    L1
    (HOT)
    L2
    COOLING
    TRANSFORMER HEATING
    TRANSFORMER
    PANEL
    R
    H
    RC
    Y
    W
    G
    M13538REMOVE FACTORY INSTALLED RH TO RC JUMPER.11
    L1
    (HOT)
    L2
    HEAT
    RELAY L1
    (HOT)L2
    FAN
    RELAY
    COOLING
    CONTACTOR
    TRANSFORMERPANEL
    R
    H
    RC
    Y
    W
    G
    INSTALL JUMPER BETWEEN RH AND RC.1
    1
    HEAT
    RELAY L1
    (HOT)
    L2COOLING
    CONTACTOR
    FAN
    RELAY 
    						
    							EMM-3 ELECTRONIC MINIZONE™ PANEL
    7 68-3041-2
    STARTUP AND CHECKOUT
    After the installation is complete, check to be sure the system is working properly. See Table 4 for sequence of operation.
    Table 4. Trol-A-Temp Electronic MiniZone Panel Sequence Of Operation.
    LED DeviceTerminals 
    Energized System Action Comments
    INITIAL POWERUP
    SYSTEM  
    (orange)Panel G (fan) System enters Purge mode for 2-1/2 minutes.
    Damper(s) open to all zones.See Purge mode.
    Damper M4
    IDLE MODE
    SYSTEM 
    (off)Panel None No call for heating or cooling. Equipment terminals are not 
    energized.
    If SYSTEM LED flashes orange, 
    DATS is not connected or is out-
    of-range.
    PURGE MODE
    ZONE 
    (orange)Thermostat None Damper from last zone to call remains open; all 
    others remain closed for 2-1/2 minutes after 
    thermostat call ends.
    After 2-1/2 minutes, if no other call for heating or 
    cooling is required, all dampers open.Panel enters Purge mode after 
    each call for heat and cool; this 
    allows heat exchanger to 
    dissipate more conditioned air 
    into the zone. Damper M4
    Panel G (fan)
    ZONE 1 INITIATES CALL FOR HEAT
    SYSTEM 
    (red)
    Zone 1 
    (green).Thermostat W (heat) Zone 1 thermostat calls for heat.
    Zone 1 damper(s) remains open.
    Zones 2 and 3 dampers close.
    Panel calls for heat.Heat is delivered only in zone 1.
    When another zone calls for heat 
    while zone 1 is calling, that zone 
    damper opens.
    For electric heat applications, use 
    thermostat that calls for fan with 
    all calls for heat. Damper Zone1: M4
    Zones 2 and 
    3: M6
    Panel W (heat)
    ZONE 1 ENDS CALL FOR HEAT
    SYSTEM 
    (orange)Thermostat None System enters Purge mode.
    Damper(s) from zone 1 remains open; all others 
    remain closed for 2-1/2 minutes after zone 1 
    thermostat call ends.
    After 2-1/2 minutes, all dampers open (M4 
    energized).None.
    Damper Zone 1: M4.
    Zones 2 and 
    3: M6.
    Panel G (fan)
    ZONE 1 INITIATES CALL FOR COOL
    SYSTEM 
    (green).
    Zone 1 
    (green).Thermostat Y (cool)
    G (fan)Zone 1 thermostat calls for cool and fan.
    Zone 1 damper(s) remains open.
    Zones 2 and 3 dampers close.
    Panel calls for cool and fan.Cool is delivered only to zone 1.
    If another zone calls for cool while 
    zone 1 is calling, the damper to 
    that zone opens.
    In retrofit applications, where only 
    three wires are available, Y 
    signal from thermostat activates 
    Y and G call from panel Damper Zone 1: M4.
    Zones 2 and 
    3: M6.
    Panel Y (cool).
    G (fan).
    ZONE 1 ENDS CALL FOR COOL
    SYSTEM 
    (orange)Thermostat None System enters Purge mode.
    Damper(s) from zone 1 remains open; all others 
    remain closed for 2-1/2 minutes after zone 1 
    thermostat call ends.
    After 2-1/2 minutes, all dampers open (M4 
    energized).None.
    Damper Zone 1: M4.
    Zones 2 and 
    3: M6.
    Panel G (fan) 
    						
    							EMM-3 ELECTRONIC MINIZONE™ PANEL
    68-3041-2 8
    ZONE 1 CALLS FOR FAN
    Zone 1 
    (green).
    Zones 2 and 
    3 (off).
    SYSTEM  
    (off).Thermostat G (fan) System fan is energized.
    Zone 1 damper(s) remains open; all others 
    close.When a call for cool is made, panel 
    adjusts dampers and activates 
    equipment as directed.
    When a call for heat is made, fan 
    stays energized for two minutes 
    of heat call.
    When fan call ends, Idle mode is 
    entered. Damper Zone 1: M4.
    Zones 2 and 
    3: M6.
    Panel G (fan)
    DATS TEMPERATURE EXCEEDS 160° (71°C) IN ZONE 1 CALL FOR HEAT
    SYSTEM 
    (flashes red)Thermostat W (heat) Thermostat continues to call for heat, but panel 
    ignores call.
    Damper(s) from zone 1 remains open; all others 
    are closed.
    Panel activates system fan for 2-1/2 minutes 
    and until DATS temperature drops more than 
    10°F (-12°C).After 2-1/2 minutes and more than 
    10°F (-12°C) temperature drop, 
    the panel returns to Heat mode 
    (if call still exists), delivering heat 
    to zone 1 and any other zone 
    calling for heat. Fan stays on first 
    two minutes of heat call. Damper Zone 1: M4.
    Zones 2 and 
    3: M6.
    Panel G (fan)
    DATS TEMPERATURE FALLS BELOW 44°F (6°C) IN ZONE 1 CALL FOR COOL
    SYSTEM 
    (flashes 
    green)Thermostat Y (cool)
    G (fan)Thermostat continues to call for cool and fan, 
    but panel ignores cool call.
    Damper(s) from zone 1 remains open; all others 
    are closed.
    Panel activates system fan for 2-1/2 minutes 
    and until DATS temperature rises more than 
    10°F (-12°C).After 2-1/2 minutes and more than 
    10°F (-12°C) temperature rise, 
    the panel returns to Cool mode 
    (if call still exists), delivering 
    cooling to zone 1 and any other 
    zone calling for cool. Damper Zone 1: M4.
    Zones 2 and 
    3: M6.
    Panel G (fan)
    AFTER BOOT BUTTON IS PRESSED
    SYSTEM 
    (orange)Panel G (fan) System enters Purge mode for 2-1/2 minutes.
    Dampers to all zones open.See Purge mode.
    Dampers M4
    PURGE OVERRIDE BUTTON IS PRESSED
    None Panel None Panel exits Purge mode after approximately 
    2 seconds.
    Panel waits for next call for heat, cool or fan 
    from zone thermostats.
    If no calls exist, panel remains in Idle mode.Used to troubleshoot the system. 
    Pressing the button cancels the 
    Purge mode and makes 
    troubleshooting the system 
    quicker and easier.
    PANEL RECEIVES SIMULTANEOUS CALLS FOR HEAT AND COOL FROM DIFFERENT ZONES
    None Panel None Panel defaults to the last type of call (heat or 
    cool) to determine which type of conditioning 
    to choose.When the first call for conditioning 
    ends, the panel enters the Purge 
    mode, then delivers conditioning 
    to the other zone(s), as required.
    WHILE ZONE 1 CALLS FOR HEAT, ZONE 2 CALLS FOR COOL
    None Panel None Panel delivers heat into zone 1 until call is 
    satisfied or for a 20- minute delay, whichever 
    occurs first.
    Panel enters Purge mode.
    Panel delivers cool into zone 2 until call is 
    satisfied, or for a 20-minute delay, whichever 
    occurs first.Prevents one zone from never 
    receiving conditioning because it 
    is requesting the opposite 
    device. Table 4. Trol-A-Temp Electronic MiniZone Panel Sequence Of Operation. (Continued)
    LED DeviceTerminals 
    Energized System Action Comments 
    						
    							EMM-3 ELECTRONIC MINIZONE™ PANEL
    9 68-3041-2
    SERVICE
    Purge timing— fixed at two and one-half minutes; not field-
    adjustable.
    Fan operation in Purge mode—fan is on in Purge mode; not 
    field adjustable.DATS Operation—High limit is 160° F (71°C); low limit is 44°F 
    (6°C) and not field-adjustable.
    TROUBLESHOOTING
    The primary diagnostic tools are the SYSTEM and ZONE 
    damper status LED and the BOOT and PURGE OVERRIDE 
    buttons. See Fig. 7 and 8 for troubleshooting flowcharts.
    Fig. 7. Thermostat is calling for cooling but the system light is not turning green to show a cool call.
    NO
    START
    NO
    YES
    IS 24 VAC
    ON ALL OF THE
    ZONES AT R-M1
    OR R-C
    ?NO CHECK THE TRANSFORMER
    FOR 24 VAC.
    THERMOSTAT MAY BE IN A 5 MIN DELAY IN COOLING. 
    MAKE SURE THERMOSTAT IS CALLING FOR COOLING.
    THE PANEL MAY HAVE BEEN DAMAGED. 
    TAKE THE R OR C WIRE OFF AGAIN FOR 10 
    MINUTES. AFTER 10 MINUTES, RE-ATTACH 
    THE R OR C WIRE AND PRESS THE BOOT 
    BUTTON. CHECK VOLTAGE AT R-M1 OR R-C 
    ON ALL THE ZONES. IF NO VOLTAGE AT R-M1 
    OR R-C, REPLACE THE EMM PANEL.
    RE-ATTACH EACH ZONE THERMOSTAT WIRE.
    ATTACH EACH ZONE SEPARATELY, CHECKING 
    AFTER EACH ZONE IS ATTACHED IF THE 
    THERMAL FUSE HAS TRIPPED. AFTER 
    ATTACHING THE THERMOSTAT WIRES, ATTACH
    EACH MOTOR ZONE WIRES, AGAIN CHECKING 
    THE THERMAL FUSE TO SEE IF IT TRIPS. THIS 
    STEP-BY-STEP PROCESS SHOULD HELP YOU 
    IDENTIFY WHAT IS TRIPPING THE THERMAL 
    FUSE ON THE PANEL. YES
    YES
    IS 24 VAC
    AT R AND C
    ON THE EMM
    PANEL
    ?
    CHECK FOR
    24 VAC AT Y-M1 OR Y-C
    ON THE EMM PANEL. (YOU 
    SHOULD HAVE 
    24 VAC.)
    IS THE 
    THERMOSTAT CALLING 
    FOR COOL?
    IS THERE
    CONTINUITY AT R
    C-Y 
    ON THE EQUIPMENT 
    CONTACTS OF THE 
    EMM PANEL?NO
    NO
    NOTHE 
    THERMAL FUSE 
    HAS TRIPPED. REMOVE THE 
    R OR C (TRANSFORMER POWER) 
    WIRE FROM THE PANEL FOR 15 SECONDS 
    AND ALLOW THE FUSE TO RESET. TAKE THE 
    THERMOSTAT AND DAMPER WIRES OFF FROM
    EACH ZONE BEFORE YOU RE-ATTACH 
    THE R OR C WIRE. IS THERE 
    VOLTAGE AT R-M1 OR R-C
    ON ALL OF THE 
    ZONES?IS THERE
    24 VAC AT Y-C ON THE 
    THERMOSTAT?
    DO YOU 
    HAVE A DATS 
    HOOKED TO THE 
    PANEL?NO
    YES YES
    YES
    YES
    JUMPER THE R WIRE TO THE Y WIRE ON THE
    THERMOSTAT. IF THE COOL LIGHT COMES ON, YOU 
    HAVE A BAD THERMOSTAT. REPLACE THERMOSTAT.
    IF YOU JUMPER R-Y ON THE THERMOSTAT AND 
    THE COOL LIGHT DOES NOT COME ON, YOU MAY 
    HAVE A BAD WIRE. TRY ANOTHER SET OF WIRES 
    OR CHECK CONTINUITY.
    IT COULD BE A BAD WIRE. IF YOU HAVE 
    VOLTAGE ON THE PANEL AT Y-C BUT NOT AT 
    THE THERMOSTAT, THEN IT IS A WIRE. CHECK 
    FOR VOLTAGE AT R-W, G ON THE THERMOSTAT. 
    IF THERE IS VOLTAGE, IT IS A BAD Y WIRE. 
    IF NO VOLTAGE AT R-ANY OTHER TERMINAL 
    ON THE THERMOSTAT, IT IS A BAD R WIRE.
    YES
    NO
    THE COOLING EQUIPMENT SHOULD BE ON. 
    SEEMS LIKE THE PANEL IS WORKING BUT THE SYSTEM 
    LIGHT IS NOT. REPLACE PANEL.
    M13543A
    DID THE EMM PANEL HAVE ANY CONDENSATION ON IT? 
    WAS IT STORED IN A COLD PLACE BEFORE BEING 
    INSTALLED? IF SO, THIS COULD CAUSE THE PANEL TO
    MALFUNCTION. LET THE PANEL ADAPT TO THE NEW 
    CONDITIONS BEFORE POWER UP.
    YES
    REMOVE THE DATS WIRES FROM THE BOARD. 
    RETURN TO “IS THE THERMOSTAT CALLING FOR 
    COOL” PART OF THE FLOWCHART AND BEGIN 
    TROUBLESHOOTING FROM THAT POINT.
    REMOVE ALL WIRES FROM THE PANEL EXCEPT
    R AND C (POWER FROM THE TRANSFORMER). 
    JUMPER R-Y ON ONE OF THE ZONES. IF THE 
    SYSTEM LIGHT DOES NOT TURN GREEN, REPLACE 
    THE PANEL.NO 
    						
    							EMM-3 ELECTRONIC MINIZONE™ PANEL
    68-3041-2 10
    Fig. 8. Thermostat is calling for heating but the system light is not turning red to show a heat call.
    NO
    START
    NO
    YES
    DO
    YOU HAVE 
    24 VAC ON ALL OF 
    THE ZONES AT 
    R-M1 OR R-C
    ?NO CHECK THE TRANSFORMER
    FOR 24 VAC.
    MAKE SURE THERMOSTAT IS CALLING FOR HEAT.
    THE PANEL MAY HAVE BEEN DAMAGED. 
    TAKE THE R OR C WIRE OFF AGAIN FOR 10 
    MINUTES. AFTER 10 MINUTES, RE-ATTACH 
    THE R OR C WIRE AND PRESS THE BOOT 
    BUTTON. CHECK VOLTAGE AT R-M1 OR R-C 
    ON ALL THE ZONES. IF NO VOLTAGE AT R-M1
    OR R-C, REPLACE THE EMM PANEL.
    RE-ATTACH EACH ZONE THERMOSTAT WIRE.
    ATTACH EACH ZONE SEPARATELY, CHECKING 
    AFTER EACH ZONE IS ATTACHED IF THE 
    THERMAL FUSE HAS TRIPPED. AFTER 
    ATTACHING THE THERMOSTAT WIRES, ATTACH
    EACH MOTOR ZONE WIRES, AGAIN CHECKING 
    THE THERMAL FUSE TO SEE IF IT TRIPS. THIS 
    STEP-BY-STEP PROCESS SHOULD HELP YOU 
    IDENTIFY WHAT IS TRIPPING THE THERMAL 
    FUSE ON THE PANEL. YES
    YES
    IS THERE 
    24 VAC AT THE 
    TRANSFORMER R AND C 
    ON THE EMM 
    PANEL?
    CHECK
    FOR  24 VAC AT
    W-M1 OR W-C ON 
    THE EMM PANEL. (YOU 
    SHOULD HAVE 
    24 VAC.)
    IS THE 
    THERMOSTAT CALLING 
    FOR HEAT?
    IS THERE
    CONTINUITY AT 
    R
    H-W ON THE EQUIPMENT 
    CONTACTS OF THE 
    EMM PANEL?NO
    NO
    NOTHE 
    THERMAL FUSE 
    HAS TRIPPED. REMOVE THE 
    R OR C (TRANSFORMER POWER) 
    WIRE FROM THE PANEL FOR 15 SECONDS 
    AND ALLOW THE FUSE TO RESET. TAKE THE 
    THERMOSTAT AND DAMPER WIRES OFF FROM
    EACH ZONE BEFORE YOU RE-ATTACH 
    THE R OR C WIRE. IS THERE 
    VOLTAGE AT R-M1 OR 
    R-CON ALL OF THE 
    ZONES?IS THERE
    24 VAC AT W-C ON THE 
    THERMOSTAT?
    DO YOU 
    HAVE A DATS 
    HOOKED TO THE 
    PANEL?NO
    YES YES
    YES
    YES
    JUMPER THE R WIRE TO THE W WIRE ON THE
    THERMOSTAT. IF THE HEAT LIGHT COMES ON, YOU 
    HAVE A BAD THERMOSTAT. REPLACE THERMOSTAT. 
    IF YOU JUMPER R-W ON THE THERMOSTAT AND 
    THE HEAT LIGHT DOES NOT COME ON, YOU MAY 
    HAVE A BAD WIRE. TRY ANOTHER SET OF WIRES 
    OR CHECK CONTINUITY.
    IT COULD BE A BAD WIRE. IF YOU HAVE 
    VOLTAGE ON THE PANEL AT W-C BUT NOT AT 
    THE THERMOSTAT, THEN IT IS A WIRE. CHECK 
    FOR VOLTAGE AT R-Y, G ON THE THERMOSTAT. 
    IF THERE IS VOLTAGE, IT IS A BAD W WIRE. IF 
    NO VOLTAGE AT R-ANY OTHER TERMINAL ON 
    THE THERMOSTAT, IT IS A BAD R WIRE.
    YES
    NO
    THE HEATING EQUIPMENT SHOULD BE ON. 
    SEEMS LIKE THE PANEL IS WORKING BUT THE SYSTEM 
    LIGHT IS NOT. REPLACE PANEL.
    M13546A
    DID THE EMM PANEL HAVE ANY CONDENSATION ON IT? 
    WAS IT STORED IN A COLD PLACE BEFORE BEING 
    INSTALLED? IF SO, THIS COULD CAUSE THE PANEL TO
    MALFUNCTION. LET THE PANEL ADAPT TO THE NEW 
    CONDITIONS BEFORE POWERUP.
    YES
    REMOVE THE DATS WIRES FROM THE PANEL. 
    RETURN TO “IS THE THERMOSTAT CALLING FOR 
    HEAT” PART OF THE FLOWCHART AND BEGIN 
    TROUBLESHOOTING FROM THAT POINT.
    REMOVE ALL WIRES FROM THE PANEL EXCEPT
    R AND C (POWER FROM THE TRANSFORMER). 
    JUMPER R-W ON ONE OF THE ZONES. IF THE 
    SYSTEM LIGHT DOES NOT TURN RED, REPLACE 
    THE PANEL.NO 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell Emm 3 Manual