Honeywell control panel VISTA40 Security System User Manual
Here you can view all the pages of manual Honeywell control panel VISTA40 Security System User Manual. The Honeywell manuals for Control panel are available online for free. You can easily download all the documents as PDF.
Page 41
– 41 – Trouble Conditions Typical Trouble Displays The word CHECK on the Keypad’s display, accompanied by a rapid beeping at the Keypad, indicates that there is a trouble condition in the system. To silence the beeping sound for trouble conditions, press any key. • A display of “CHECK” accompanied by a display of CALL SERVICE indicates that a problem exists with the system that eliminates some of the protection. CALL FOR SERVICE IMMEDIATELY. • A display of “CHECK” accompanied by a...
Page 42
– 42 – Trouble Conditions (cont’d) Power Failure If the POWER indicator is off, operating power for the system has stopped and is inoperative. CALL FOR SERVICE IMMEDIATELY. If the POWER indicator is on, but the message AC LOSS is displayed, the Keypad is operating on battery power only. If only some lights are out on the premises, check circuit breakers and fuses and reset or replace as necessary. CALL FOR SERVICE IMMEDIATELY if AC power cannot be restored. SERVICING INFORMATION Your...
Page 43
– 43 – Recommendations For Proper Protection The following recommendations for the location of fire and burglary detection devices help provide proper coverage for the protected premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association’s (NFPA) Standard #72 noted below. Early warning fire detection is best achieved by the installation of fire...
Page 44
– 44 – Recommendations For Proper Protection (cont’d) In addition, we recommend the following: Install a smoke detector inside every bedroom where a smoker sleeps. Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air conditioners or humidifiers) are used. Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway...
Page 45
– 45 – Emergency Evacuation Establish and regularly practice a plan of escape in the event of fire. The following steps are recommended by the National Fire Protection Association: 1. Position your detector or your interior and/or exterior sounders so that they can be heard by all occupants. 2. Determine two means of escape from each room. One path of escape should lead to the door that permits normal exit from the building. The other may be a window, should your path be impassable....
Page 46
– 46 – Maintaining Your System Taking Care of Your System The components of your security system are designed to be as free of maintenance as possible. However, there are some things you can do to make sure that your system is in reliable working condition. 1. Test your system weekly. 2. Test the system after any alarm occurs (see TESTING THE SYSTEM). Replacing Batteries in Wireless Sensors Wireless sensors may not have been used in your security system Each wireless sensor in your...
Page 47
– 47 – Maintaining Your System (cont’d) Silencing Low Battery Warning Tones at the Keypad The keypad’s warning tones can be silenced by performing an OFF sequence (code plus OFF key), but the Keypads low battery message display will remain on as a reminder that you have a low battery condition in one or more of your sensors. When you replace the weak battery with a fresh one, the sensor will send a good battery signal to the control as soon as the sensor is activated (opening/closing of door,...
Page 48
– 48 – Quick Guide To System Functions FUNCTION PROCEDURE COMMENTS Check Zones Press [✱]. To view faulted zones when is system not ready Display All Descriptors Press and hold [✱] for 5 seconds. Displays all alpha descriptors programmed by installer. Arm System Enter code. Press arming key desired (AWAY, STAY, INSTANT, MAXIMUM). Arms system in mode selected. Disarm System Enter code. Press OFF [1]. Disarms system and silences alarms. Bypass Zones Enter code. Press BYPASS [6]....
Page 49
– 49 – Summary Of Audible Notification (Alpha Display Keypads) SOUND CAUSE DISPLAY LOUD, INTERRUPTED* Keypad & External FIRE ALARM FIRE is displayed; descriptor of zone in alarm is displayed. LOUD, CONTINUOUS* Keypad & External BURGLARY/AUDIBLE EMERGENCY ALARM ALARM is displayed; descriptor of zone in alarm is also displayed. ONE SHORT BEEP (not repeated) Keypad only a. SYSTEM DISARM b. SYSTEM ARMING ATTEMPT WITH AN OPEN ZONE. c. BYPASS VERIFY a. DISARMED/READY TO ARM...
Page 50
– 50 – UL NOTICE: This is a “GRADE A” system. “FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENT” This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for your information: This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer’s instructions, may cause interference to radio and television reception. It has been...