Home > Honeywell > Control panel > Honeywell control panel VISTA20SE Security System User Manual

Honeywell control panel VISTA20SE Security System User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell control panel VISTA20SE Security System User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							– 31 –
    TROUBLE CONDITIONS
    Typical Check
    DisplaysThe word CHECK on the Keypads display, accompanied by a rapid beeping at the
    Keypad, indicates that there is a trouble condition in the system. The displays in
    parenthesis may appear on non-alpha keypads when the associated trouble condition
    is present.
    To silence the beeping sound for check conditions, press any key.
    * Note that zonenumber 9 repre-sents a problemwith wireless re-ceivers or othersystem devices,which are not userserviceable.  CALLFOR SERVICEIMMEDIATELY.
    1.CHECK + Indicates that a problem exists with those zone(s)*. First, deter-
    Zone mine if the zone(s) displayed are intact and make them so if they
    Descriptors are not. If the zone uses a wireless detector, check that changes
    in the room (moving furniture, televisions, etc.) are not blocking
    wireless signals from the detector. If the problem has been cor-
    rected, the zone descriptor(s) and CHECK should disappear. If not,
    key an OFF sequence (security code plus OFF) to clear the dis-
    play. A CHECK condition can also indicate a wiring problem. If the
    check display persists, CALL FOR SERVICE IMMEDIATELY.
    Note that the system will not allow arming if a CHECK condition
    exists. To arm the system with a CHECK condition present, you
    must first bypass the zone(s) having the CHECK condition.
    2.Telco Fault
    (or CHECK
    and zone 94)If the telephone line monitor feature has been programmed for your
    system, this display indicates that the telephone line has been
    disconnected or cut. In some systems, this display will be
    accompanied by a trouble sound from the keypad and the external
    sounder may be activated. CONTACT YOUR SERVICE
    COMPANY IMMEDIATELY.
    To silence the trouble sound, enter your security code plus OFF. 
    						
    							– 32 –
    TROUBLE CONDITIONS (Continued)* T
    he beeping that
       accompanies a low   battery display (items   4 and 5) can be   stopped by entering   an OFF sequence   (code + OFF)
    3.COMM. FAILURE (or FC) Indicates that a failure has occurred in the
    telephone communication portion of your system.
    CALL FOR SERVICE IMMEDIATELY.
    4.SYSTEM LO BATIndicates that a low system battery condition exists,
    (or BAT with no zone No.) accompanied by a once-per-minute beeping* at
    the Keypad. CALL FOR SERVICE IMMEDIATELY.
    **  Not all systems use   wireless transmitters.
    5.LO BAT + zone descriptor Indicates that a low battery condition exists in the
    (or BAT with zone No.) wireless transmitter** displayed, and accompanied
    by a once-per-minute beeping* at the Keypad.
    CALL FOR SERVICE IMMEDIATELY.
    6.MODEM COMMIndicates that the control is on-line with the central
    (or CC) stations remote computer. The control will not
    operate while on-line. Wait a few minutes. The
    display should disappear.
    7.POWER indicator (if present) The system is operating on battery power only.
    is off. AC LOSS is displayed  If only some lights are out on the premises, check
    (or NO AC) circuit breakers and fuses and reset or replace as
    necessary. CALL FOR SERVICE IMMEDIATELY if
    AC power cannot be restored to the system.
    8.Busy-Standby (or dI) If this remains displayed for more than 1 minute,
    system is disabled. CALL FOR SERVICE AT ONCE.
    9.OPEN CIRCUIT (or OC) The keypad is not receiving signals from the control.
    10.Long Rng Trbl (or bF) If programmed, back-up Long Range Radio
    communication has failed. CALL FOR SERVICE AT
    ONCE. 
    						
    							– 33 –
    FIRE ALARM SYSTEM (IF INSTALLED)General
    Your fire alarm system (if installed) is active 24 hours a day, providing continuous
    protection. In the event of an emergency, the installed smoke and heat detectors will
    automatically activate you security system, triggering a loud, interrupted sound from
    the Keypad.  An interrupted sound will also be produced by optional exterior sounders.
    A FIRE message will appear at your Keypad and remain on until you silence and clear
    the alarm display.
    In Case Of Fire1. Should you become aware of a fire emergency 
    before
     your detectors sense the
    problem, go to your nearest Keypad and press the single panic key (or panic key
    pair) assigned as FIRE emergency (if programmed by the installer) and hold down
    for at least 2 seconds. The alarm will sound.
    2. Evacuate all occupants from the premises.
    3. If flames and/or smoke are present, leave the premises and notify your local Fire
    Department immediately.
    4. If no flames or smoke are apparent, investigate the cause of the alarm. The zone
    descriptor of the zone(s) in an alarm condition will appear at the Keypad.
    Silencing A Fire
    Alarm1. Silence the alarm by pressing the OFF key. To clear the alarm display, enter your
    code and press the OFF key again.
    2. If the Keypad indicates a trouble condition after the second OFF sequence, check
    that smoke detectors are not responding to smoke or heat producing objects in
    their vicinity. Should this be the case, eliminate the source of heat or smoke.
    3. If this does not remedy the problem, there may still be smoke in the detector.  Clear
    it by fanning the detector for about 30 seconds.
    4. When the problem has been corrected, clear the display by entering your code and
    pressing the OFF key. 
    						
    							– 34 –
    NATIONAL FIRE PROTECTION ASSN.RECOMMENDATIONS ON SMOKE DETECTORSWith regard to the number and placement of smoke/heat detectors, we subscribe to the
    recommendations contained in the National Fire Protection Associations (NFPA) Standard #72
    noted below.
    Early warning fire detection is best achieved by the installation of fire detection equipment in all
    rooms and areas of the household as follows: A smoke detector installed outside of each
    separate sleeping area, in the immediate vicinity of the bedrooms and on each additional story
    of the family living unit, including basements and excluding crawl spaces and unfinished attics.
    In addition, the NFPA recommends that you install heat or smoke detectors in the living room,
    dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms,
    basements and attached garages.
    DININGKITCHEN
    BEDROOMBEDROOMBEDROOM
    BEDROOM
    LIVING ROOM✪
    ✪✪✪
    ✪
    
    BEDROOMBDRM
    BDRM DINING 
    LIVING ROOM TV ROOMKITCHEN
    
    
    ✪
    ✪✪ ✪✪
    ✪
    
    ✪
    ✪✪BEDROOM
    BEDROOM TO
    BR
    
    
     
    LVNG RM
    BASEMENTKTCHN
    
    
    .CLOSED
    DOORGARAGE
    
    Smoke Detectors for Minimum Protection
    Smoke Detectors for Additional Protection
    Heat-Activated Detectors 
    						
    							– 35 –
    EMERGENCY EVACUATION
    Establish and regularly practice a plan of escape in the event of fire. The
    following steps are recommended by the National Fire Protection Association:
    •
    FRONT
    •
    BACK
    •BEDROOM
    BATH
    BEDROOM
    KITCHEN
    BACK DOOR
    1   FLOORSTBEDROOM
    BEDROOM2    FLOORND
    BATH
    BEDROOM
    PORCHCLOSET
    1. Position your detector or your interior and/or exterior sounders so that they
    can be heard by all occupants.
    2. Determine two means of escape from each room. One path of escape
    should lead to the door that permits normal exit from the building. The other
    may be a window, should your path be unpassable. Station an escape
    ladder at such windows if there is a long drop to the ground.
    3. Sketch a floor plan of the building. Show windows, doors, stairs and
    rooftops that can be used to escape. Indicate escape routes for each room.
    Keep these routes free from obstruction and post copies of the escape
    routes in every room.
    4. Assure that all bedroom doors are shut while you are asleep. This will
    prevent deadly smoke from entering while you escape.
    5. Try the door. If the door is hot, check your alternate escape route. If the
    door is cool, open it cautiously. Be prepared to slam the door if smoke or
    heat rushes in.
    6. When smoke is present, crawl on the ground. Do not walk upright, since
    smoke rises and may overcome you. Clearer air is near the floor.
    7. Escape quickly; dont panic.
    8. Establish a common meeting place outdoors, away from your house, where
    everyone can meet and then take steps to contact the authorities and ac-
    count for those missing. Choose someone to assure that nobody returns to
    the house — many die going back. 
    						
    							– 36 –
    MAINTAINING YOUR SYSTEM
    Taking Care of
    Your SystemThe components of your security system are designed to be as maintenance-free as
    possible. However, to make sure that your system is in reliable working condition.
    1. Test your system weekly.
    2. Test your system after any alarm occurs (see 
    TESTING THE SYSTEM)
    .
    Replacing
    Batteries in
    Wireless
    Sensors
    Wireless sensorsmay not have beenused in yoursecurity system
    Each wireless sensor in your system has a 9-volt or 3-volt battery. The system detects
    a low battery in any wireless sensor, including smoke detectors, the optional personal
    emergency transmitter, and the optional portable wireless keypad. (A low battery in a
    portable wireless keypad is detected as soon as one of its keys is pressed, and the
    wired keypad will display 00.)
    Alkaline batteries provide a minimum of 1 year of operation, and in most units and
    applications, provide 2–4 years of service. 3-volt lithium batteries provide up to 4 or
    more years of operation. Actual battery life will depend on the environment in which the
    sensor is used, the number of signals that the transmitter in the sensor has had to
    send, and the specific type of sensor. Factors such as humidity, high or low
    temperatures or large swings in temperature, may all lead to the reduction of actual
    battery life in an installation.
    If you have a low battery in a wireless sensor, a low battery message is
    displayed on the keypad.
    In addition, a battery-operated smoke detector with a low battery also emits a single
    chirp sound approximately once every 20–30 seconds, identifying itself as the smoke
    detector with the weak battery.Note: 
    The low battery message comes on as a warning that battery replacement in
    indicated sensor(s) is due within 30 days. In the meantime, a sensor causing a low
    battery indication is still fully operational.
    Important:  Use only batteries recommended by your installer as replacement. 
    						
    							– 37 –
    MAINTAINING YOUR SYSTEM
    Silencing Low
    Battery Warning
    Tones at the
    KeypadYou can silence the keypad’s warning tones by pressing the OFF key, but the
    keypads low battery message display will remain on as a reminder that you have a
    low battery condition in one or more of your sensors. When you replace the weak
    battery with a fresh one, the sensor will send a good battery signal to the control as
    soon as the sensor is activated (opening/closing of door, window, etc.), causing the
    low battery display to turn off. If the sensor is not activated, the display will
    automatically clear within approximately 1 hour.
    Routine Care
    •Treat the components of your security
     system as you would any other electrical
    equipment. Do not slam sensor-protected doors or windows.
    •Keep dust from accumulating on the keypad and all protective sensors, particularly on
    motion sensors and smoke detectors.•The keypad and sensors should be cleaned carefully with a dry soft cloth. 
    Do not
    spray water or any other fluid on the  units. 
    						
    							– 38 –
    QUICK GUIDE TO
    SYSTEM FUNCTIONS
    FUNCTION PROCEDURE COMMENTSCheck Zones Press [
    ] Do this to view faulted zones when system not ready.
    Arm System Enter code Do this to arm the system in the mode selected.
    Press arming key desired
      (AWAY, STAY, INSTANT,
    MAXIMUM)
    Disarm System Enter code Do this to disarm the system and silences alarms.
    Press OFF [1]
    Bypass zones Enter code Do this to bypass protection zones.  Bypassed zones are un-
    Press BYPASS [6] protected and will not cause an alarm if violated.Enter zone numbers to bebypassed (use 2-digit entries)
    Quick Bypass Enter code Do this to bypass all faulted zones automatically, if programmed.
    Press BYPASS [6] and stop
    Chime Mode ON Enter code Do this to turn on chime mode. Keypad will sound if doors or
    Press CHIME [9] windows are violated while system disarmed.
    Chime Mode OFF Enter code Do this to turn chime mode off.
    Press CHIME [9]
    Test Mode ON Enter code Do this to enter test mode.  Sounds alarm sounder and allows
    Press TEST [5] sensors to be tested.
    Test Mode OFF Enter code Do this to turn test mode off. System returns to normal mode.
    Press OFF [1] 
    						
    							– 39 –
    QUICK GUIDE TO
    SYSTEM FUNCTIONS
    FUNCTION PROCEDURE COMMENTSAdd or Change Enter master code Do this to add or change a user code.a User Press CODE [8]
    Enter users 2-digit user No.Enter code for that user
    Delete a User Enter master code Do this to delete a user code from the system.
    Press CODE [8]Enter user number to bedeleted
    Change a Master Enter master code Do this to change the existing master code.Code Press CODE [8]
    Press [0] + [2] 
    (master user no.)
    Enter new 4-digit master codeEnter new master code again 
    						
    							– 40 –
    SUMMARY OF AUDIBLE NOTIFICATION
    (ALPHA DISPLAY KEYPADS)
    SOUND CAUSE DISPLAY
    LOUD, INTERRUPTED*
    Keypad & ExternalFIRE ALARMFIREis displayed; descriptor of zone in alarm is displayed.LOUD, CONTINUOUS*
    Keypad & ExternalBURGLARY/AUDIBLE
    EMERGENCY ALARMALARM is displayed; descriptor of zone in alarm is also displayed.ONE SHORT BEEP
    (not repeated)
    Keypad onlya. SYSTEM DISARM
    b. SYSTEM ARMING  ATTEMPT
        WITH AN OPEN ZONE.
    c. BYPASS VERIFYa. DISARMED/READY TO ARM is displayed.
    b. The number and descriptor of the open protection zone is displayed.
    c. Numbers and descriptors of the bypassed protection zones are displayed
       (One beep is heard for each zone displayed). Subsequently, the following is
        displayed: DISARMED BYPASS Ready to ArmONE SHORT BEEP
    (once every 40 seconds)
    Keypad onlySYSTEM IS IN TEST MODE Opened Zone identifications will appear.ONE BEEP 
    every 40 sec.
    Keypad only
    LOW BATTERY AT A TRANSMITTERLO BAT displayed with description of transmitter.
    TWO SHORT BEEPS
    Keypad onlyARM AWAY OR MAXIMUMARMED AWAY or ARMED MAXIMUMdisplayed. Red ARMED indicator lit.THREE SHORT BEEPS
    Keypad onlya.  ARM STAY OR INSTANT
    b.  ZONE OPENED WHILE SYSTEM
     IS IN CHIME MODE.a. ARMED STAY  or ARMED INSTANT  displayed. Red ARMED indicator lit.
    b. CHIME displayed, descriptor of open protection zone will be displayed if the
        [Q] key is pressed.RAPID BEEPING
    Keypad onlya. TROUBLE
    b. MEMORY OF ALARMa. CHECKdisplayed.  Descriptor of troubled protection zone is displayed.
    b. FIRE or ALARM  is displayed; descriptor of zone in alarm is displayed.SLOW BEEPING
    Keypad onlya. EXIT DELAY WARNING (if
        programmed)
    b. ENTRY DELAY WARNINGa.
     ARMED AWAY or ARMED MAXIMUM is displayed along with You May
    Exit Now
    b. DISARM SYSTEM OR ALARM WILL OCCUR is displayed. Exceeding the
    delay time without disarming causes alarm.
    * If a bell is used as external sounder, fire alarm is 
    pulsed ring;
     burglary/audible emergency is 
    steady ring
    . 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell control panel VISTA20SE Security System User Manual