    							K3590-2CF   9/08  Rev. B   
     
    ADEMCO 6160CR
    ADEMCO 6160CRADEMCO 6160CR ADEMCO 6160CR-
    -- -2
    22 2
    Commercial Alpha Keypad
    Commercial Alpha KeypadCommercial Alpha Keypad Commercial Alpha Keypad
    INSTALLATION AND SETUP GUIDE 
    Keypad Features 
    • Programmable function keys 
    • Built-in sounder 
    • ARMED, READY, POWER, FIRE ALARM, SILENCED, 
    SUPERVISORY, TROUBLE LEDs  (see note 1) 
    • RED keypad for Commercial Fire applications 
    • 
    Supervised by control panel (required for Commercial Fire 
    installations) 
     
     
    Supported Control Panels 
    • VISTA-32FB (see note 2) 
    • VISTA-128FBP (see note 2) 
    • VISTA-250FBP (see note 2)    
    Notes:  1.  Trouble and Supervisory LEDs are supported only in the panels listed above. 
     2. Keypad address may be set to address 00 through 30 to operate with these controls (see controls instructions for 
     details). 
     
    GENERAL INFORMATION 
    The 6160CR-2 is an addressable remote keypad intended for 
    use in commercial applications with Honeywell control panels 
    listed above. The 6160CR-2’s address is set locally, via the 
    keypad’s keys (see note 2, above). The keys are continuously 
    backlit for convenience. The LCD display is backlit only when 
    a key is depressed, or when the system is in alarm or trouble 
    condition.  
    Note:   On some controls, the LCD may be programmed to 
    remain on at all times (see control’s instructions for details). 
     
    KEYPAD LED INDICATIONS 
    The keypad’s LEDs will light under the following conditions: 
    ARMED (Red)  ON 
    OFF System is Armed 
    System is Disarmed 
    READY (Green)  ON 
    OFF System is Ready  
    System is Not Ready 
    POWER (Green)   ON 
    OFF AC power is O.K.  
    AC power is removed 
    FIRE ALARM 
    (Red)  ON 
    OFF Fire Alarm has occurred 
    Normal 
    SILENCED 
    (Yellow) ON 
    OFF Fire Alarm has been silenced 
    Normal 
    SUPERVISORY 
    (Yellow) ON 
     
     
    OFF Supervisory condition exists 
    (see control’s instructions for 
    details) 
    Normal 
    TROUBLE  
    (Yellow) ON 
     
     
    OFF Trouble condition exists (see 
    control’s instructions for details) 
    Normal 
     
    SPECIAL FUNCTION KEYS 
    The keypad also features programmable function keys labeled 
    A, B, and C. These keys may be programmed to initiate panic 
    or emergency alarms. Refer to the individual control panel’s 
    instructions for details.)  
     These keys must be held down for at least 2 seconds to 
    initiate the assigned function. 
     
     WIRING AND INSTALLATION 
    The keypad may be surface-mounted directly to a dry wall or 
    to a single- or double-gang electrical box. If this is the primary 
    Fire Keypad, connect to Keypad Port 2, wire in conduit, and 
    mount within 20 ft. of the control. 
    1.  Detach the case back by pushing up into one of the two slots 
    at the bottom of the keypad with the blade of a small 
    screwdriver (this will push in the release tab), then pull 
    that side of the case back away. Repeat for the other side. 
    Refer to Figure 1 for location of the case back release tabs. 
    2.  Route wiring through the large rectangular opening in the 
    case back. 
    3.  Mount the case back to the wall or electrical box. 
    4.  Wire directly from the keypad’s terminal block (see Figure 
    2) to the terminal block on the control panel (see control’s 
    Summary of Connections label for correct terminal 
    connections).   
     NOTE: No more than one wire per terminal may be 
    connected. If daisy-chained configuration is required, pig-
    tail wires together so that only one wire is terminated 
    under the screw. 
    Use 16-24  AWG wire only! 
    TABLE 1 - Wiring Connections 
    Keypad  Control Panel   Wire Color 
     Y  Data Out   Yellow 
    +  + Aux. Pwr   Red 
     –    – Aux Pwr (GND)  Black 
     G Data In  Green 
    5. Reattach the keypad to its case back. Attach the top of 
    the keypad first, and then press the bottom section down 
    until it snaps into place securely.
     
    6160CR-006-V2
    A
    B
    C
    D
    ARMED
    POWER
    FIRE TROUBLE
    FIRE SUPERVISORY
    READY
    SILENCED FIRE ALARM
     
    Figure 1 – Removing the Case Back  
    						
    							 
    6160CR-004-V1
    +
    +
    + +
    RED BLACK
    +
    +
    + +
    YG+
     
    Figure 2 – 6160CR-2 Wiring Details 
    SETTING THE KEYPAD ADDRESS 
    The keypad address must be set according to the control 
    panel being used (refer to the individual control panel’s 
    instructions for details). Available addresses are from 00 
    through 30. The keypad is shipped with a default address 
    of 31 (non-addressable mode). To change the address, do 
    the following: 
     
    1. Enter keypad address mode: 
    Power up the keypad. Within 60 seconds of power-up, 
    press and hold down the [1] and [3] keys together for 3- 
    seconds. The current address will be displayed and the 
    cursor will be under the “tens” digit (3
    1).  
    Notes:  
    • If the system has been powered up for more than 60 
    seconds, you must power the keypad down, and then 
    power it up again in order to change the keypad’s 
    address. 
    • The keypad will not enter the address mode if the system 
    is in the program mode. 
    • If 10 seconds have passed with no key entry, the keypad 
    automatically exits the address mode. 
    Set the desired address: 
    Enter the desired address. For example, for address 12, 
    enter 1, then 2. Display shows (12). 
    2. Exit the address mode: 
    Press the “star” key (
    ✻) to save the displayed address 
    and exit the address mode.  The current address may be 
    viewed at any time by pressing and holding [1] and [3] 
    keys together. 
     
    KEYPAD LABELS 
    Function key labels: A set of adhesive-backed labels 
    with some typical function symbols (e.g., police, 
    emergency, etc.) is provided. These labels come in four 
    colors (red, blue, green, and white) and may be placed on 
    the appropriate function keys (A, B, or C) for ease of 
    identifying the individual key’s function (as determined by 
    the control panel’s capability and programming). 
    OPERATING THE KEYPAD 
    For operating instructions, see the User Guide for the 
    control panel with which this keypad is used. 
    SPECIFICATIONS 
    Physical: 5.25” H x 7.437” W x 1.312” D 
    Display:  Alphanumeric, 32-character (2 lines x 16 
    characters), LCD back-lit 
      
    Sounder: High-quality speaker 
    Electrical:  Voltage: +12VDC (from power-limited 
    source) 
     Current: 45mA standby; 
      160mA in alarm (sounder, back 
    light and LEDs on)
     
     
    NFPA-72 Compliant
     
    FOR WARRANTY INFORMATION AND LIMITATIONS OF THE ENTIRE SYSTEM, REFER TO THE INSTALLATION AND 
    SETUP GUIDE FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED.  
     
     
     
     
     
     
     
     
     
     
     
    ÊK3590-2CF2Š 
    K3590-2CF  9/08  Rev. B  
    2 Corporate Center Drive, Suite 100
    P.O. Box 9040
    Melville, NY 11747
    Copyright © 2007 Honeywell International Inc.