GE Power Break 1 Manual
Have a look at the manual GE Power Break 1 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 45 GE manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Power Break® Circuit Breakers Chapter 3. Accessories 15 Figure 31. Slide reset lever and spring on the mounting plate. Figure 32. Positioning the UVR assembly on the mounting plate. 11 1 1 00 0 0 ... . Use the wire ties provided to secure the leads to the mounting plate and to secure the wire bundle to the inside and outside of the breaker base, as shown in Figure 20. 11 1 1 11 1 1 ... . Reassemble the breaker covers as described in Breaker Cover Reassembly. 11 1 1 22 2 2 ... . Mount the dropping resistor (when supplied) and MOV, shown in Figure 29. Wire these as shown in Figure 30. Figure 33. Installing the UVR mounting screw. 11 1 1 33 3 3 ... . Perform the following functional check of the UVR: aa a a ... . Apply rated voltage to the UVR coil. bb b b ... . Turn the breaker on. cc c c ... . Reduce the control voltage. The breaker should trip when the voltage drops to 35–60% of its rated value. 11 1 1 44 4 4 ... . Apply the UVR descriptive label to the left side of the breaker near the lead-exit area. 3–5 Blown-Fuse Trip Device The blown-fuse trip device (three-coil shunt trip), shown in Figure 34, is intended for applications with breakers and fuses in series. This accessory prevents single-phasing conditions by monitoring the fuses and automatically tripping the circuit breaker when a fuse blows. It does not protect from single-phasing of the power source. Figure 34. Blown-fuse trip device accessory.
Power Break® Circuit Breakers Chapter 3. Accessories 16 Each coil of the blown-fuse trip device is wired across a fuse so that the voltage across an open fuse is fed back to the accessory coil. When the coil is energized, the solenoid core releases the spring-biased latch, allowing the slide to rotate the breaker latch, tripping the breaker. The fuse must be replaced and the breaker reset before the breaker can be reclosed. If the breaker is closed on an open fuse, the blown-fuse trip device will automatically open the breaker. Blown-Fuse Trip Device Installation Installation of the blown-fuse trip device is similar to that of the shunt trip, described above. 11 1 1 ... . The blown-fuse trip device assembles to a mounting plate. Not all breakers are shipped from the factory with a mounting plate. Some breakers have only an L-shaped bracket to retain the molded-plastic crank. A mounting plate is provided in the blown-fuse kit. • If the breaker is supplied with an L-shaped bracket, remove the two retaining screws and dis- card the bracket. • If the breaker is supplied with a mounting plate, follow the instructions under Mounting Plate Removal . 22 2 2 ... . Assemble the blown-fuse trip device to the accessory mounting plate as shown in Figure 26. If a shunt trip had previously been mounted as shown in Figure 25, it must be relocated as shown in Figure 26, with its plunger stop nut in contact with the plunger of the blown-fuse trip device. 33 3 3 ... . Follow the procedure for Mounting Plate Installation. 44 4 4 ... . Perform the following installation checks: aa a a ... . Replace the breaker cover as described above. Close the breaker contacts. bb b b ... . Apply 120 volts to one coil of the blown-fuse trip device for not more than one second. The breaker must trip. Repeat the test for each coil. 55 5 5 ... . Attach the six lead wires from the blown-fuse trip device across the three fuses, as shown in the wiring diagram in Figure 35. 66 6 6 ... . Apply the descriptive label to the front of the breaker. 77 7 7 ... . Reassemble the breaker cover(s) as described in Breaker Cover Reassembly. Figure 35. Blown-fuse trip device wiring diagram. 3–6 Auxiliary Switch The auxiliary switch, shown in Figure 36, is used for remote indication of the breaker’s main contact posi- tion— open or closed. No distinction is made between open or tripped mode. A maximum of 12 switches can be installed per breaker. Each is single-pole, double-throw (AB-type) and rated as listed in Table 7. Two switch posi- tions must be devoted to each shunt trip accessory (if used) per breaker. The auxiliary switch wiring diagram is shown in Figure 37. Figure 36. Auxiliary switch.
Power Break® Circuit Breakers Chapter 3. Accessories 17 Figure 37. Auxiliary switch wiring diagram. Catalog NumberNumber of Switch ElementsMaximum Current Rating TPAS2ABx 1–126 A at 240 Vac .25 A at 250 Vdc .50 A at 125 Vdc * Replace x with a number from 1–12 for the number of switch elements. Table 7. Auxiliary switch electrical characteristics. Auxiliary Switch Installation 11 1 1 ... . Remove the circuit breaker cover(s) as described in Breaker Cover Removal. • If the breaker was supplied with an L-shaped bracket (see Mounting Plate Removal), remove the two retaining screws, discard the bracket, and install the mounting plate provided in the kit (see Mounting Plate Installation). 22 2 2 ... . Both the left and right breaker poles can accept up to six auxiliary switches. If the left pole contains a shunt trip, two of the six auxiliary switch positions must be used for the cut-out switches; thus, only four auxil- iary switches may be used in the left pole. 33 3 3 ... . If auxiliary switches are to be installed in the right pole, remove the trip unit by depressing the lock release lever while lifting up on the trip unit. Remove the trip unit mounting plate, shown in Figure 38. 44 4 4 ... . Position the auxiliary switch assembly so that the tapped mounting holes on its bracket line up with the through holes in the arm stop, as shown in Figure 39. 55 5 5 ... . Secure the auxiliary switch assembly to the arm stop with two #8 × 9/16 screws and lock washers, as shown in Figure 40. Tighten the screws to 23 in-lbs. Figure 38. Trip unit removed from the breaker. Figure 39. Installing the auxiliary switch assembly. Figure 40. Securing the auxiliary switch assembly. 66 6 6 ... . Remove knockouts in the side of the base, as required. Each knockout will accommodate up to three bundles of wire. Remove all sharp edges with a file. 77 7 7 ... . Use the supplied wire ties to secure the leads as shown in Figure 20. 88 8 8 ... . Replace the trip unit mounting plate and trip unit. 99 9 9 ... . Replace the breaker cover(s) as described in Circuit Breaker Cover Reassembly . 11 1 1 00 0 0 ... . Perform the following functional checks: aa a a ... . With the breaker off, use a continuity tester to verify continuity between the white and brown-
Power Break® Circuit Breakers Chapter 3. Accessories 18 white leads. Verify an open circuit between the red and white leads. bb b b ... . With the circuit breaker on, the auxiliary switch contacts should change sense. 11 1 1 11 1 1 ... . Apply the auxiliary switch descriptive label to the front of the breaker cover. 3–7 Remote Close Solenoid and Remote Charge Indication The remote close solenoid is included with electrically operated breakers and may be ordered as a factory- installed option in manually operated breakers. Catalog numbers and specifications are listed in Table 8. Remote charge indication provides for remote indication that the breaker closing springs are charged. Catalog numbers are TPXCAS and TSXCAS for 800–2000 A and for 3000–4000 A frames, respectively. The switch is rated at 15 A for 250 Vac and at 0.5 A for 125 Vdc. Figure 41 is the wiring diagram for remote charge indication. Figure 42 is the wiring diagram for remote charge indication with a remote close solenoid. Figure 41. Wiring diagram for remote charge indication. Figure 42. Wiring diagram for remote charge indication with remote close solenoid. Catalog No.Rated VoltageOperatingRange*, VCurrent at Max. Voltage, AMaximum Closing Time, sMaximum Operating Time, s TPXCC12S 120 Vac 102–132 3.3 0.083 0.050 TPXCC14S 240 Vac 204–264 1.7 0.083 0.050 TPXCC08S 24 Vdc 19–29 13 0.083 0.050 * The power source must stay within the rated operating voltage range of the close solenoid from no load to the full peak current rating of the device. Table 8. Catalog numbers and ratings for the remote close solenoid. 3–8 Optional Features Special features may be ordered as specific accessories or as an integral part of the breaker catalog number. Refer to the BuyLog®, GEP-1100, for these features. Limited Close Access Button This accessory, shown in Figure 43, provides for limited manual access to the ON button. The breaker can be closed in an emergency for maintenance by inserting a 1/8-inch diameter pin or rod into the hole in the center of the button. Manually operated breakers must be ordered with an accessory closing solenoid. Figure 43. Limited close access button.
Power Break® Circuit Breakers Chapter 3. Accessories 19 Padlock Function Handle Button Lock A standard feature on motor-operated breakers that pre- vents manual charging of the mechanism, as shown in Figure 5. OFF Button Padlock with Door Interlock This accessory prevents opening of the panel door when the breaker is ON or CHARGED. It operates as follows: • With the breaker OFF the paddle can be rotated counterclockwise over the breaker nameplate to clear the enclosure panel door. Rotate the paddle clock- wise to lock the door, as shown in Figure 44. • To defeat the interlock when the breaker is ON or CHARGED, depress the spring and rotate the paddle to clear the door, as shown in Figure 45. Figure 44. OFF button padlock with panel door interlock. Figure 45. Defeating the OFF button padlock.
Power Break® Circuit Breakers Chapter 4. Maintenance 20 WW W W AA A A RR R R NN N N II I I NN N N GG G G ::: : Before beginning any maintenance work, disconnect the breaker from all voltage sources, both power and control, and ensure that the breaker is OFF. 4–1 Inspections Circuit breakers should be maintained through the implementation of a systematic maintenance program. A periodic inspection routine is recommended. The fre- quency of inspection should depend on the environ- mental conditions of each breaker. All circuit breakers should be inspected at least annually. It a breaker is oper- ated frequently or installed in an area of high humidity, dust, or dirt, the frequency of maintenance inspections should be increased. Under extremely adverse conditions, monthly inspections are recommended. The maintenance inspection should begin with an overall visual check. If dirt, grease, or any other foreign material is found on or in the breaker, it should be thoroughly and carefully removed. Do not use solvents on insulating mate- rial. A rotating program providing for a periodic withdrawal from service of each breaker in turn for inspection and maintenance is an excellent means of establishing a high level of service reliability. In such cases, one or more spare breakers and all accessories should be available during the maintenance inspection to replace any breaker that may be removed for repairs. NN N N OO O O TT T T EE E E ::: : When ordering spare parts, always enclose com- plete information from the breaker name plate, includ- ing the breaker’s serial number. 4–2 Lubrication Moderate lubrication is all that is required for most circuit breakers. Mechanical bearing points and sliding surfaces should be lubricated at the regular inspection periods with a thin film of molybdenum disulfide (Molykote G) or Mobil 28 grease. GE recommends the use of kerosene for removing hardened grease and dirt from the latch and bearing surfaces. All excess lubricant should be removed to avoid any contamination of dirt or dust. CC C C AA A A UU U U TT T T II I I OO O O NN N N ::: : Under no circumstances should lubricant be applied to contact areas.
g GE Industrial Systems General Electric Company 41 Woodford Ave., Plainville, CT 06062 GEH4693 R05 0998 © 1998 General Electric Company