Home > GE > Power Breaker > GE Power Break 1 Manual

GE Power Break 1 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual GE Power Break 1 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 45 GE manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Power Break® Circuit Breakers
    Chapter 3. Accessories
    15
    Figure 31. Slide reset lever and spring on the mounting plate.
    Figure 32. Positioning the UVR assembly on the mounting plate.
    11 1 1
    00 0 0
    ... .
    Use the wire ties provided to secure the leads to the
    mounting plate and to secure the wire bundle to the
    inside and outside of the breaker base, as shown in
    Figure 20.
    11 1 1
    11 1 1
    ... .
    Reassemble the breaker covers as described in
    Breaker Cover Reassembly.
    11 1 1
    22 2 2
    ... .
    Mount the dropping resistor (when supplied) and
    MOV, shown in Figure 29. Wire these as shown in
    Figure 30.
    Figure 33. Installing the UVR mounting screw.
    11 1 1
    33 3 3
    ... .
    Perform the following functional check of the UVR:
    aa a a
    ... .
    Apply rated voltage to the UVR coil.
    bb b b
    ... .
    Turn the breaker 
    on.
    cc c c
    ... .
    Reduce the control voltage. The breaker should
    trip when the voltage drops to 35–60% of its rated
    value.
    11 1 1
    44 4 4
    ... .
    Apply the UVR descriptive label to the left side of the
    breaker near the lead-exit area.
    3–5 Blown-Fuse Trip Device
    The blown-fuse trip device (three-coil shunt trip), shown
    in Figure 34, is intended for applications with breakers
    and fuses in series. This accessory prevents single-phasing
    conditions by monitoring the fuses and automatically
    tripping the circuit breaker when a fuse blows. It does not
    protect from single-phasing of the power source.
    Figure 34. Blown-fuse trip device accessory. 
    						
    							Power Break® Circuit Breakers
    Chapter 3. Accessories
    16 Each coil of the blown-fuse trip device is wired across a
    fuse so that the voltage across an open fuse is fed back to
    the accessory coil. When the coil is energized, the solenoid
    core releases the spring-biased latch, allowing the slide to
    rotate the breaker latch, tripping the breaker. The fuse
    must be replaced and the breaker reset before the breaker
    can be reclosed.
    If the breaker is closed on an open fuse, the blown-fuse
    trip device will automatically open the breaker.
    Blown-Fuse Trip Device Installation
    Installation of the blown-fuse trip device is similar to that
    of the shunt trip, described above.
    11 1 1
    ... .
    The blown-fuse trip device assembles to a mounting
    plate. Not all breakers are shipped from the factory
    with a mounting plate. Some breakers have only an
    L-shaped bracket to retain the molded-plastic crank.
    A mounting plate is provided in the blown-fuse kit.
    • If the breaker is supplied with an L-shaped
    bracket, remove the two retaining screws and dis-
    card the bracket.
    • If the breaker is supplied with a mounting plate,
    follow the instructions under 
    Mounting Plate
    Removal
    .
    22 2 2
    ... .
    Assemble the blown-fuse trip device to the accessory
    mounting plate as shown in Figure 26. If a shunt trip
    had previously been mounted as shown in Figure 25,
    it must be relocated as shown in Figure 26, with its
    plunger stop nut in contact with the plunger of the
    blown-fuse trip device.
    33 3 3
    ... .
    Follow the procedure for 
    Mounting Plate Installation.
    44 4 4
    ... .
    Perform the following installation checks:
    aa a a
    ... .
    Replace the breaker cover as described above.
    Close the breaker contacts.
    bb b b
    ... .
    Apply 120 volts to one coil of the blown-fuse trip
    device for not more than one second. The
    breaker must trip. Repeat the test for each coil.
    55 5 5
    ... .
    Attach the six lead wires from the blown-fuse trip
    device across the three fuses, as shown in the wiring
    diagram in Figure 35.
    66 6 6
    ... .
    Apply the descriptive label to the front of the breaker.
    77 7 7
    ... .
    Reassemble the breaker cover(s) as described in
    Breaker Cover Reassembly.
    Figure 35. Blown-fuse trip device wiring diagram.
    3–6 Auxiliary Switch
    The auxiliary switch, shown in Figure 36, is used for
    remote indication of the breaker’s main contact posi-
    tion—
    open or closed. No distinction is made between
    open or tripped mode. A maximum of 12 switches can be
    installed per breaker. Each is single-pole, double-throw
    (AB-type) and rated as listed in Table 7. Two switch posi-
    tions must be devoted to each shunt trip accessory (if
    used) per breaker. The auxiliary switch wiring diagram is
    shown in Figure 37.
    Figure 36. Auxiliary switch. 
    						
    							Power Break® Circuit Breakers
    Chapter 3. Accessories
    17
    Figure 37. Auxiliary switch wiring diagram.
    Catalog
    NumberNumber of
    Switch ElementsMaximum
    Current Rating
    TPAS2ABx 1–126 A at 240 Vac
    .25 A at 250 Vdc
    .50 A at 125 Vdc
    * Replace x with a number from 1–12 for
    the number of switch elements.
    Table 7. Auxiliary switch electrical characteristics.
    Auxiliary Switch Installation
    11 1 1
    ... .
    Remove the circuit breaker cover(s) as described in
    Breaker Cover Removal.
    • If the breaker was supplied with an L-shaped
    bracket (see 
    Mounting Plate Removal), remove
    the two retaining screws, discard the bracket, and
    install the mounting plate provided in the kit (see
    Mounting Plate Installation).
    22 2 2
    ... .
    Both the left and right breaker poles can accept up to
    six auxiliary switches. If the left pole contains a shunt
    trip, two of the six auxiliary switch positions must be
    used  for the cut-out switches; thus, only four auxil-
    iary switches may be used in the left pole.
    33 3 3
    ... .
    If auxiliary switches are to be installed in the right
    pole, remove the trip unit by depressing the lock
    release lever while lifting up on the trip unit. Remove
    the trip unit mounting plate, shown in Figure 38.
    44 4 4
    ... .
    Position the auxiliary switch assembly so that the
    tapped mounting holes on its bracket line up with
    the through holes in the arm stop, as shown in
    Figure 39.
    55 5 5
    ... .
    Secure the auxiliary switch assembly to the arm stop
    with two #8 × 
    9/16 screws and lock washers, as shown
    in Figure 40. Tighten the screws to 23 in-lbs.
    Figure 38. Trip unit removed from the breaker.
    Figure 39. Installing the auxiliary switch assembly.
    Figure 40. Securing the auxiliary switch assembly.
    66 6 6
    ... .
    Remove knockouts in the side of the base, as
    required. Each knockout will accommodate up to
    three bundles of wire. Remove all sharp edges with a
    file.
    77 7 7
    ... .
    Use the supplied wire ties to secure the leads as
    shown in Figure 20.
    88 8 8
    ... .
    Replace the trip unit mounting plate and trip unit.
    99 9 9
    ... .
    Replace the breaker cover(s) as described in 
    Circuit
    Breaker Cover Reassembly
    .
    11 1 1
    00 0 0
    ... .
    Perform the following functional checks:
    aa a a
    ... .
    With the breaker 
    off, use a continuity tester to
    verify continuity between the white and brown- 
    						
    							Power Break® Circuit Breakers
    Chapter 3. Accessories
    18 white leads. Verify an open circuit between the
    red and white leads.
    bb b b
    ... .
    With the circuit breaker 
    on, the auxiliary switch
    contacts should change sense.
    11 1 1
    11 1 1
    ... .
    Apply the auxiliary switch descriptive label to the
    front of the breaker cover.
    3–7 Remote Close Solenoid and
    Remote Charge Indication
    The remote close solenoid is included with electrically
    operated breakers and may be ordered as a factory-
    installed option in manually operated breakers. Catalog
    numbers and specifications are listed in Table 8.
    Remote charge indication provides for remote indication
    that the breaker closing springs are charged. Catalog
    numbers are TPXCAS and TSXCAS for 800–2000 A and
    for 3000–4000 A frames, respectively. The switch is rated
    at 15 A for 250 Vac and at 0.5 A for 125 Vdc. Figure 41 is
    the wiring diagram for remote charge indication. Figure
    42 is the wiring diagram for remote charge indication
    with a remote close solenoid.
    Figure 41. Wiring diagram for remote charge indication.
    Figure 42. Wiring diagram for remote charge indication with remote
    close solenoid.
    Catalog No.Rated
    VoltageOperatingRange*, VCurrent at Max.
    Voltage, AMaximum
    Closing Time, sMaximum
    Operating Time, s
    TPXCC12S 120 Vac 102–132 3.3 0.083 0.050
    TPXCC14S 240 Vac 204–264 1.7 0.083 0.050
    TPXCC08S 24 Vdc 19–29 13 0.083 0.050
    * The power source must stay within the rated operating voltage range of the close solenoid from no load to the full peak
    current rating of the device.
    Table 8. Catalog numbers and ratings for the remote close solenoid.
    3–8 Optional Features
    Special features may be ordered as specific accessories or
    as an integral part of the breaker catalog number. Refer to
    the BuyLog®, GEP-1100, for these features.
    Limited Close Access Button
    This accessory, shown in Figure 43, provides for limited
    manual access to the 
    ON button. The breaker can be
    closed in an emergency for maintenance by inserting a
    1/8-inch diameter pin or rod into the hole in the center of
    the button. Manually operated breakers must be ordered
    with an accessory closing solenoid.
    Figure 43. Limited close access button. 
    						
    							Power Break® Circuit Breakers
    Chapter 3. Accessories
    19
    Padlock Function
    Handle Button Lock
    A standard feature on motor-operated breakers that pre-
    vents manual charging of the mechanism, as shown in
    Figure 5.
    OFF Button Padlock with Door Interlock
    This accessory prevents opening of the panel door when
    the breaker is 
    ON or CHARGED. It operates as follows:
    • With the breaker 
    OFF the paddle can be rotated
    counterclockwise over the breaker nameplate to clear
    the enclosure panel door. Rotate the paddle clock-
    wise to lock the door, as shown in Figure 44.
    • To defeat the interlock when the breaker is 
    ON or
    CHARGED, depress the spring and rotate the paddle
    to clear the door, as shown in Figure 45.
    Figure 44. OFF button padlock with panel door interlock.
    Figure 45. Defeating the OFF button padlock. 
    						
    							Power Break® Circuit Breakers
    Chapter 4. Maintenance
    20
    WW W W
    AA A A
    RR R R
    NN N N
    II I I
    NN N N
    GG G G
    ::: : Before beginning any maintenance work,
    disconnect the breaker from all voltage sources, both
    power and control, and ensure that the breaker is OFF.
    4–1 Inspections
    Circuit breakers should be maintained through the
    implementation of a systematic maintenance program. A
    periodic inspection routine is recommended. The fre-
    quency of inspection should depend on the environ-
    mental conditions of each breaker. All circuit breakers
    should be inspected at least annually. It a breaker is oper-
    ated frequently or installed in an area of high humidity,
    dust, or dirt, the frequency of maintenance inspections
    should be increased. Under extremely adverse conditions,
    monthly inspections are recommended.
    The maintenance inspection should begin with an overall
    visual check. If dirt, grease, or any other foreign material
    is found on or in the breaker, it should be thoroughly and
    carefully removed. Do not use solvents on insulating mate-
    rial.
    A rotating program providing for a periodic withdrawal
    from service of each breaker in turn for inspection and
    maintenance is an excellent means of establishing a high
    level of service reliability. In such cases, one or more spare
    breakers and all accessories should be available during the
    maintenance inspection to replace any breaker that may
    be removed for repairs.
    NN N N
    OO O O
    TT T T
    EE E E
    ::: : When ordering spare parts, always enclose com-
    plete information from the breaker name plate, includ-
    ing the breaker’s serial number.
    4–2 Lubrication
    Moderate lubrication is all that is required for most circuit
    breakers. Mechanical bearing points and sliding surfaces
    should be lubricated at the regular inspection periods
    with a thin film of molybdenum disulfide (Molykote G) or
    Mobil 28 grease. GE recommends the use of kerosene for
    removing hardened grease and dirt from the latch and
    bearing surfaces. All excess lubricant should be removed
    to avoid any contamination of dirt or dust.
    CC C C
    AA A A
    UU U U
    TT T T
    II I I
    OO O O
    NN N N
    ::: : Under no circumstances should lubricant be
    applied to contact areas. 
    						
    							g
    GE Industrial Systems
                                                                                                       
    General Electric Company
    41 Woodford Ave., Plainville, CT 06062
    GEH4693  R05  0998 © 1998 General Electric Company 
    						
    All GE manuals Comments (0)