Home > GE > Power Breaker > GE Power Break 1 Manual

GE Power Break 1 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual GE Power Break 1 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 45 GE manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Power Break® Circuit Breakers
    Chapter 2. Breaker Operation
    5 charge as soon as the breaker is opened, whether from a
    fault trip or from being intentionally opened.
    CC C C
    AA A A
    UU U U
    TT T T
    II I I
    OO O O
    NN N N::: :
     Do not wire breakers for both automatic
    charge and automatic close unless a bell alarm with
    overcurrent lockout is incorporated. Otherwise, the
    breaker may repeatedly close into an overcurrent fault.
    CC C C
    AA A A
    UU U U
    TT T T
    II I I
    OO O O
    NN N N
    ::: : The bell alarm lockout and undervoltage
    release both hold the breaker latch open when activated.
    To prevent continuous cycling (see Application Notes)
    when the breaker is wired for automatic charging, inter-
    connect the bell alarm switch to the motor operator ter-
    minal board as shown in Figures 7 and 8.
    NN N N
    OO O O
    TT T T
    EE E E
    ::: : The motor operator contains a feature that shuts
    off control power if the OFF button is held depressed.
    Thus, electrical operation is prevented if a key interlock
    or padlock accessory is applied in the breaker OPEN con-
    dition. If the breaker is equipped with a draw-out inter-
    lock (TPDO-1), electrical operation is permitted only if
    the draw-out carriage is in the ENGAGED or TEST posi-
    tion.
    Figure 7. Bell alarm wiring to prevent continuous cycling of the
    automatic charging mechanism.
    Figure 8. Wiring for optional bell alarm lockout applications.
    Wiring Notes
    Observe the following notes when wiring the breaker for
    operation:
    • Customer-supplied contacts (such as 
    CHARGE and
    CLOSE) should be momentary action, rated for 0.25
    A at 125 Vdc for dc motor operators or rated for 3 A
    at 120 Vac for ac motor operators.
    • Do not apply power to any terminal board point
    other than points 1 and 2.
    • Observe the proper polarity for dc motor operators
    (point 1 is positive).
    • When performing hi-pot or dielectric tests:
    – Remove all power leads, both control and power.
    – Short all motor operator terminal board points.
    – Open the circuit breaker.
    – Test between the motor operator terminal board
    points and the load side of the breaker’s center
    pole (this pole is connected to the frame).
    – Test at 2200 Vac for one minute using a current-
    limited, nondestructive ac hi-pot tester with
    maximum output of 20 mA.
    OperatingMotor Current, A
    Close Nominal Maximum Maximum
    Rated
    VoltageVoltage
    RangeLocked
    RotorFull
    Load AverageSolenoid,
    peak AFuses (Slo
    Blo 125 V)Charge
    Time , sClose
    Time, sOpening
    Time, s
    120 Vac 102–132 8 2.5 1.5 3.0 2 A 5.0 0.83 0.05
    125 Vdc 100–140 10 2.5 1.5 3.5 2 A 6.0 0.83 0.05
    72 Vdc 57–81 13 3.0 2.0 5.0 3 A 6.0 0.83 0.05
    48 Vdc 38–58 20 5.0 2.5 6.6 4 A 6.0 0.83 0.05
    24 Vdc 19–29 24 7.0 3.0 13.2 6.25 A 7.5 0.83 0.05
    Table 3. Application data for control power. 
    						
    							Power Break® Circuit Breakers
    Chapter 2. Breaker Operation
    6
    Application Notes
    • Size the control power source according to the
    information in Table 3. If a single source is to supply
    several motor operators, it must be sized appropri-
    ately. Where breakers are wired for automatic
    charge, it may be necessary to supply power to several
    motor operators simultaneously during start up.
    • The control power source should be sized so that the
    drop in voltage from no load to full load does not
    exceed 7%.
    • Acceptable dc power sources are the following:
    – dc generator,
    – battery,
    – three-phase, full-wave rectified ac, or
    – any other dc power source with a peak-to-peak
    ripple voltage of not more than 15% of the rated
    voltage at motor full-load current.
    • Breakers built after approximately June 1978 are
    equipped with an anticycling circuit that will lock out
    the breaker if the latch fails to reset (such as due to a
    deenergized UVR). Lockout occurs if the charge
    time exceeds 20 seconds. Reset a locked-out breaker
    locally by pushing the 
    OFF button or remotely by
    momentarily removing control power from the
    motor operator.
    2–3 Trip Unit Setup
    NN N N
    OO O O
    TT T T
    EE E E
    ::: : MicroVersaTrip RMS-9 trip unit rating plugs may
    be changed per GEH-5369 and GEH-5371 without void-
    ing the UL listing. MicroVersaTrip trip units and tap
    changer cards may be installed or replaced per GEH-
    4657 and this manual without voiding the UL listing.
    MicroVersaTrip Plus and MicroVersaTrip PM trip units
    and rating plugs may be changed or replaced per GEH-
    6273 without voiding the UL listing.
    MicroVersaTrip® and MicroVersaTrip®
    RMS-9 Trip Units
    Trip settings are installed at the factory with minimum
    values on all functions. Customers will generally want to
    adjust settings to their own requirements.
    Adjusting Trip Settings
    Use the following procedure to adjust trip settings on
    these trip units:
    11 1 1
    ... .
    Remove the clear plastic protective window, shown in
    Figure 4.22 2 2
    ... .
    Change the settings by twisting the indicator switches
    to the desired values or multipliers. See GEH-4657 for
    definitions of MicroVersaTrip functions and GEH-
    5369 for MicroVersaTrip RMS-9 functions.
    33 3 3
    ... .
    Reinstall the window.
    Rating Plugs
    MicroVersaTrip RMS-9 trip units require the installation
    of a rating plug in accordance with GEH-5369 and GEH-
    5371 to set the maximum continuous current rating.
    Tap Changer Card
    Some MicroVersaTrip models include a tap changer card,
    shown in Figure 9. When provided, this function allows
    the customer to change the rating of the breaker frame.
    Figure 9. Tap changer cards. 
    						
    							Power Break® Circuit Breakers
    Chapter 2. Breaker Operation
    7 All breakers provided with tap cards are shipped with both
    HIGH (100% of the current rating Sensor  Amp on the
    breaker name plate) and 
    low (50–75% of the current
    rating 
    Sensor  Amp on the breaker name plate). The low
    card is packed and supported on the breaker handle. The
    high card is installed in the breaker frame. To change
    settings use the following procedure:
    WW W W
    AA A A
    RR R R
    NN N N
    II I I
    NN N N
    GG G G
    ::: : The circuit breaker must be removed from
    the electrical system before attempting any operations
    that involve removing the breaker’s cover.
    11 1 1
    ... .
    Turn the breaker off.
    22 2 2
    ... .
    Remove the four cover mounting screws and remove
    the top cover. On motor operator-equipped breakers,
    remove only the top cover.
    33 3 3
    ... .
    Withdraw the card from the tap changer support and
    replace with the other card, as shown in Figure 10.
    The print on the top of the card should be oriented
    the same as the breaker cover name plate.
    Figure 10. Cover and trip unit removed from the breaker.
    44 4 4
    ... .
    Trip units providing ground fault protection must
    also have the tap setting changed on the tapped neu-
    tral CT (four-wire systems). Change the black wire
    lead from the 
    high or low terminal to match the
    desired tap setting of the breaker frame, as shown in
    Figure 11.
    55 5 5
    ... .
    Replace the breaker cover.
    66 6 6
    ... .
    Operate the breaker manually through the
    charge–close–open cycle to ensure that the breaker is
    properly functioning mechanically before energizing
    or connecting it to the electrical system.
    NN N N
    OO O O
    TT T T
    EE E E
    ::: : A deenergized undervoltage release will not allow
    the mechanism to charge and close.
    77 7 7
    ... .
    Store the extra tap card in a convenient place.
    Figure 11. Neutral CT connection for four-wire ground fault.
    Neutral Current Transformer (Four-Wire Ground
    Fault System)
    Ground fault protection is offered as an optional function
    of the MicroVersaTrip® trip unit. However, all MicroVer-
    saTrip-generation breaker frames are provided with ter-
    minal board points for connection to a neutral CT. 
    Do
    not short these terminals if there is no neutral CT
    connected.
    Always match the rating of the CT to the rating of the cir-
    cuit breaker; specifically, use the following criteria:
    •
    Fixed-rated breaker frames – match the neutral CT
    amp rating to the breaker sensor amp rating.
    •
    Tapped or high/low-rated breaker frames – match
    the neutral CT amp rating to the 
    high/low setting of
    the breaker sensor amp rating.
    Note that MicroVersaTrip RMS-9-equipped breakers are
    not available with inverted construction (formerly desig-
    nated by Cat. No. suffix B). These breakers may be either
    top fed, as illustrated in Figure 12, or bottom fed, as illus-
    trated in Figure 13.
    NN N N
    OO O O
    TT T T
    EE E E
    ::: : The neutral CT is mounted in reverse in Figure
    13 when the breaker is bottom (reverse) fed.
    CC C C
    AA A A
    UU U U
    TT T T
    II I I
    OO O O
    NN N N
    ::: : Match the tapped terminal for the black lead
    to the tap setting, if provided, on the breaker frame.
    CC C C
    AA A A
    UU U U
    TT T T
    II I I
    OO O O
    NN N N
    ::: : Observe the polarity markings on the neutral
    CT shell and the breaker frame.
    CC C C
    AA A A
    UU U U
    TT T T
    II I I
    OO O O
    NN N N
    ::: : When a neutral CT is not used or not
    required (three-wire ground fault), do not short  the
    ground fault terminal points on the breaker frame.
    Leave them open as supplied by the factory. 
    						
    							Power Break® Circuit Breakers
    Chapter 2. Breaker Operation
    8
    Figure 12. Wiring diagram for MicroVersaTrip and MicroVersaTrip
    RMS-9 trip units with ground fault on a top-fed four-wire load.
    Figure 13. Wiring diagram for MicroVersaTrip and MicroVersaTrip
    RMS-9 trip units with ground fault on a bottom-fed four-wire load.
    MicroVersaTrip RMS-9 Trip Units
    The trip units on MicroVersaTrip RMS-9-equipped break-
    ers are not interchangeable. The breaker rating may be
    adjusted by changing the rating plug installed in the face
    of the trip unit. See GEH-5369 and GEH-5371 for instruc-
    tions.
    MicroVersaTrip Trip Units
    MicroVersaTrip-equipped breakers were ordered complete
    or as a frame and trip unit only. Some trip units and
    frames have rejection schemes to prevent mismatching of
    functions.
    The limits of interchangeability  are as follows:• High short-time or H-function trip units may not be
    used in frames that are not wired for H function
    (special CTs).
    • Special trip units for AK breakers with the M (no
    instantaneous) function may not be used with Power
    Break breakers.
    Refer to GEH-4657 for installation or replacement of
    MicroVersaTrip trip units with remote overload indication
    and for recommended wiring for zone-selective interlock.
    To change or install trip units without remote indication,
    use the following procedure.
    WW W W
    AA A A
    RR R R
    NN N N
    II I I
    NN N N
    GG G G
    ::: : The circuit breaker must be removed from
    the electrical system before attempting any operations
    that involve removing the breaker’s cover.
    11 1 1
    ... .
    Remove the four cover-mounting screws and remove
    the top cover. On motor-operated breakers, remove
    only the top cover to replace the trip unit.
    22 2 2
    ... .
    Remove the trip unit as follows:
    aa a a
    ... .
    Push in the trip unit-cover interlock, as illustrated
    in Figure 14.
    bb b b
    ... .
    Lift the trip unit off the mounting plate and ter-
    minal plug.
    cc c c
    ... .
    The trip unit-cover interlock will now swing out
    and lock over the base to prevent reinstallation of
    the breaker cover when no trip unit is installed.
    Figure 14. Releasing the trip unit cover interlock to remove or install
    the trip unit. 
    						
    							Power Break® Circuit Breakers
    Chapter 2. Breaker Operation
    9 33 3 3
    ... .
    Install the replacement trip unit as shown in Figure
    15:
    aa a a
    ... .
    Align the holes in the bottom of the trip unit with
    the guide pins in the mounting plate. Lower the
    trip unit until it is fully down on the mounting
    plate and the connecting plug is secure.
    bb b b
    ... .
    Push in the trip unit-cover interlock until it locks
    in place, as shown in Figure 14.
    NN N N
    OO O O
    TT T T
    EE E E
    ::: : The trip unit has a stud on the bottom to defeat
    the trip unit-cover interlock locking spring.
    Figure 15. Aligning the trip unit to the mounting plate.
    44 4 4
    ... .
    Replace the top cover and secure with the four cover-
    mounting screws.
    55 5 5
    ... .
    Operate the breaker manually through the
    charge–close–open cycle to ensure that the breaker is
    properly functioning mechanically before energizing
    or connecting it to the electrical system.
    NN N N
    OO O O
    TT T T
    EE E E
    ::: : A deenergized undervoltage release will not allow
    the mechanism to charge and close.
    66 6 6
    ... .
    For trip units with ground fault, a neutral CT must be
    provided if a four-wire system is to be used. See the
    section on neutral CTs for instructions and precau-
    tions. 
    Do not short the ground fault terminals pro-
    vided on the breaker frame if a neutral CT is not
    used.
    MagneTrip™ Trip Units
    Use the following procedure to change trip settings on
    MagneTrip trip units:
    11 1 1
    ... .
    Remove the protective trip unit cover.
    22 2 2
    ... .
    Change the trip setting by rotating the plastic buttons
    in the base with a screw driver, as shown in Figure 16.
    33 3 3
    ... .
    Replace the protective cover.
    Figure 16. Adjusting the settings on a MagneTrip trip unit.
    MicroVersaTrip Plus™ and MicroVersaTrip
    PM™ Trip Units
    See GEH-6273 for detailed instructions for setting up
    MicroVersaTrip Plus and MicroVersaTrip PM trip units. 
    						
    							Power Break® Circuit Breakers
    Chapter 3. Accessories
    10
    3–1 Introduction
    These instructions cover the field installation of internally
    mounted electrical accessories. They are UL listed for use
    in all 800–2000 A frame Power Break® circuit breakers
    with MicroVersaTrip® trip units. These accessories may
    also be installed in 800–1600 A frame Power Break break-
    ers with MagneTrip™ trip units, but the UL listing is
    voided.
    The control leads of internally mounted accessories exit in
    pigtail form from the side of the breaker. These leads are
    terminated at the secondary disconnect points of draw-out
    breakers or at optional terminal blocks when specified for
    stationary-mounted breakers. All leads are color coded as
    listed in Table 4.
    Accessory Lead ColorNo. of
    Leads
    Shunt Trip Black 2
    Undervoltage
    ReleaseBlue 2
    Auxiliary SwitchWhite – common
    Red – OPEN (NO)
    Brown/White – CLOSED (NC)3 per
    switch
    Bell Alarm
    (Overcurrent
    Lockout)Yellow – common
    Purple – CLOSED (NC)
    Brown – OPEN (NO)3
    Blown-Fuse Trip
    (3-Coil Shunt Trip)    Line End      Load End      Phase   
    Red Brown-White A
    Blue White B
    Yellow Black C6
    Closing Solenoid
    (Manual Breakers
    only)White – common
    Black – remote indication
    Orange – remote close3
    Table 4. Accessory lead color codes.
    3–2 Circuit Breaker Cover
    Before any accessories can be installed in a Power Break
    circuit breaker, the cover(s) must be removed, as
    described in the following sections.
    WW W W
    AA A A
    RR R R
    NN N N
    II I I
    NN N N
    GG G G
    ::: : Before installing any accessories, completely
    de-energize the circuit breaker and disconnect it from
    the electrical circuit. This is mandatory, since the
    breaker must be ON during certain stages of installation
    and testing.
    CC C C
    AA A A
    UU U U
    TT T T
    II I I
    OO O O
    NN N N
    ::: : Do not turn the breaker upside down, since
    loose parts may become lost.
    NN N N
    OO O O
    TT T T
    EE E E
    ::: : All breakers are equipped with mechanical inter-
    locks that automatically trip the breaker when the cover
    is removed with the breaker closed.
    Breaker Cover Removal
    Manual Breaker
    Use the following procedure to remove the cover of a
    manually operated breaker:
    11 1 1
    ... .
    Press the 
    off button to open the circuit breaker.
    22 2 2
    ... .
    Remove the four cover-mounting screws.
    33 3 3
    ... .
    Remove the breaker cover.
    Electrically Operated Breaker
    Use the following procedure to remove the cover of an
    electrically operated breaker. An 800 A frame breaker is
    shown in Figure 17 and a 1600–2000 A frame breaker is
    shown in Figure 18.
    11 1 1
    ... .
    Press the 
    off button to open the circuit breaker.
    22 2 2
    ... .
    Disconnect all external leads from the terminal
    board.
    33 3 3
    ... .
    Remove the four cover mounting screws.
    44 4 4
    ... .
    Remove the outer cover.
    55 5 5
    ... .
    On 1600-2000 A framer breakers only, remove the two
    inner-cover mounting screws, as shown in Figure 18.
    66 6 6
    ... .
    Loosen the captive inner-cover lock screw, as shown
    in Figure 19.
    77 7 7
    ... .
    Remove the inner cover.
    Figure 17. 800 A frame electrically operated breaker. 
    						
    							Power Break® Circuit Breakers
    Chapter 3. Accessories
    11
    Figure 18. 1600–2000 A frame electrically operated breaker.
    Figure 19. 1600–2000 A frame electrically operated breaker with the
    outer cover removed.
    Breaker Cover Reassembly
    Manually Operated Breakers
    11 1 1
    ... .
    Verify that all connections are secure and the breaker
    is free of debris.
    22 2 2
    ... .
    Verify that the breaker is 
    off.
    CC C C
    AA A A
    UU U U
    TT T T
    II I I
    OO O O
    NN N N
    ::: :
         Verify that the accessory mounting plate
    insulator, shown in Figure 20, is properly located so it
    will not be damaged when the cover is replaced. The
    cover phase barrier must pass to the right side of this
    insulator.
    33 3 3
    ... .
    Position the charging handle at the home position (6
    o’clock) on the cover. Align the cover mounting
    screw holes with the breaker base and install the four
    cover screws. Tighten the screws to 50–60 in-lbs.
    Figure 20. Wire ties on the accessory leads and mounting plate
    insulator.
    Electrically Operated Breakers
    11 1 1
    ... .
    Verify that all connections are secure and the breaker
    is free of debris.
    CC C C
    AA A A
    UU U U
    TT T T
    II I I
    OO O O
    NN N N
    ::: : Verify that the accessory mounting plate
    insulator is properly located, as shown in Figure 26.
    22 2 2
    ... .
    Slide the inner cover assembly onto the breaker base.
    Ensure that the crossbar hook engages the drive stud,
    as shown in Figure 21.
    Figure 21. Crossbar hook engaging the drive hook.
    33 3 3
    ... .
    Tighten the inner cover lock screw, shown in Figure
    19,  to 10 in-lbs.
    44 4 4
    ... .
    On 1600–2000 A frame breakers only, replace the two
    inner cover mounting screws and tighten to 50–60 in-
    lbs. 
    						
    							Power Break® Circuit Breakers
    Chapter 3. Accessories
    12 55 5 5
    ... .
    Position the charging handle at the home position (6
    o’clock) on the outer cover. Align the outer cover-
    mounting screw holes with those on the inner cover
    and install the four cover-mounting screws. Tighten
    to 50–60 in-lbs.
    NN N N
    OO O O
    TT T T
    EE E E
    ::: : Ensure that the control terminal board properly
    engages the cover retaining slots.
    66 6 6
    ... .
    Connect the control and power wiring as per the
    instructions supplied with the circuit breaker.
    3–3 Shunt Trip Device
    The shunt trip, shown in Figure 22, allows the breaker to
    be tripped electrically from a remote location. A cut-off
    switch is supplied as part of the shunt trip to automatically
    remove power from the shunt trip coil when the breaker is
    tripped. The electrical characteristics of the shunt trip are
    listed in Table 5. Figure 23 is the shunt trip wiring dia-
    gram.
    Figure 22. Shunt trip device with cut-off switch.
    Catalog No.Voltage
    RatingMax. Inrush
    Current, A
    TPST 12S120 Vac
    240 Vac2.25
    4.50
    TPST13S480 Vac
    600 Vac1.64
    2.05
    TPST7S 12 Vdc 4.00
    TPST8S 24 Vdc 2.18
    TPST9S 48 Vdc 1.09
    TPST10S 125 Vdc 1.00
    TPST11S 250 Vdc 0.21
    Table 5. Shunt Trip electrical characteristics.
    Figure 23. Shunt trip wiring diagram.
    Mounting Plate Removal
    The mounting plate is used as the anchor position for the
    shunt trip, blown-fuse trip, and undervoltage release
    accessories. Breakers are shipped from the factory with
    either a mounting plate or an L-shaped bracket to retain
    the molded-plastic crank. A new mounting plate is pro-
    vided in the shunt trip kit, blown-fuse trip kit, undervol-
    tage release kit, and auxiliary switch kit.
    • If the breaker was supplied with an L-shaped bracket,
    remove the two retaining screws, discard the bracket,
    and skip to the appropriate installation instructions.
    • If the breaker was supplied with a mounting plate,
    remove it with the following procedure:
    11 1 1
    ... .
    Remove the three mounting plate retaining screws
    and the isolation barrier, shown in Figure 24.
    22 2 2
    ... .
    Lift out the accessory mounting plate and remove the
    molded drive crank.
    33 3 3
    ... .
    If a tap changer was supplied, remove the two screws
    from the phenolic block before removing the mount-
    ing plate.
    Figure 24. Locations of the mounting plate retaining screws, isolation
    barrier, and molded drive crank. 
    						
    							Power Break® Circuit Breakers
    Chapter 3. Accessories
    13
    Shunt Trip Installation
    NN N N
    OO O O
    TT T T
    EE E E
    ::: : If the shunt trip is being replaced because of a
    defective coil, the cause of the initial failure should first
    be determined. If necessary, consult the factory for fur-
    ther guidance.
    11 1 1
    ... .
    Assemble the coil to the mounting plate as shown in
    Figure 25. If a blown-fuse trip device is also to be
    installed on the mounting plate, mount the shunt
    trip coil as shown in Figure 26.
    22 2 2
    ... .
    When a blown-fuse trip device is included, place the
    shunt trip plunger stop nut in contact with the
    plunger of the blown-fuse trip device.
    33 3 3
    ... .
    Depress the actuator on the cut-off switch. Align the
    tapped holes in the switch bracket with the holes in
    the arm stop (left pole) and secure with #8-32 × 
    9/16
    screws and lock washers, as shown in Figure 27.
    Tighten to 23 in-lbs torque.
    44 4 4
    ... .
    Remove the knockouts in the side of the base, as
    required. Each knockout will accommodate up to
    three bundles of wire. Remove all sharp edges with a
    file.
    55 5 5
    ... .
    Clean all debris from the inside of the breaker.
    NN N N
    OO O O
    TT T T
    EE E E
    ::: : Shunt trip coils rated at 12 Vdc or 24 Vdc must be
    mounted in the position nearest the latch. These coils
    may not develop enough force to drive both the latch
    and the blown-fuse trip device.
    Figure 25. Shunt trip coil position with no blown-fuse trip device.
    Mounting Plate Installation
    11 1 1
    ... .
    Replace the molded drive crank onto the mechanism
    drive pin, as shown in Figure 24, engaging the roll
    pins into the slot in the drive crank.
    Figure 26. Shunt trip coil position with blown-fuse trip device.
    Figure 27. Attaching the switch bracket to the arm stop.
    22 2 2
    ... .
    Place the mounting plate in position so that its two
    operating studs engage the molded drive crank, as
    shown in Figure 24. Ensure that the isolating barrier
    is in place.
    33 3 3
    ... .
    Attach the three retaining screws. Tighten the two
    small screws to 20 in-lbs and the large screw with tub-
    ing to 75 in-lbs.
    44 4 4
    ... .
    Attach wire ties to the leads and secure them to the
    mounting plate, as shown in Figure 20.
    55 5 5
    ... .
    Insert the leads into the knockout in the base side
    wall, ensuring that one tie is on the inside of the base
    and the other is on the outside.
    66 6 6
    ... .
    Apply the descriptive label to the front of the breaker
    cover. 
    						
    							Power Break® Circuit Breakers
    Chapter 3. Accessories
    14
    3–4 Undervoltage Release Device
    The undervoltage release device (UVR), shown in Figure
    28, opens the circuit breaker when the supply voltage
    drops to 35–60% of its rated value. Figure 29 shows the
    dropping resistor supplied with 240–600 volt UVRs. The
    UVR electrical characteristics are listed in Table 6. The
    UVR wiring diagram is in Figure 30.
    Figure 28. Undervoltage release device.
    Figure 29. Dropping resistor supplied with 240–600 V UVRs.
    Figure 30. UVR wiring diagram.
    Catalog
    NumberVoltage
    RatingContinuous
    Current, mADropping
    Resistor*
    TPUV1S 120 Vac 25 none
    TPUV2S 240 Vac 25 5000 ?, 25 W
    TPUV2S 480 Vac 25 15,000 ?, 50 W
    TPUV6S 600 Vac 25 20,000 ?, 50 W
    TPUV7S 12 Vdc 211 none
    TPUV8S 24 Vdc 104 none
    TPUV9S 48 Vdc 54 none
    TPUV10S 125 Vdc 24 none
    TPUV11S 250 Vdc 24 5000 ?, 25 W
    * Ohmite Type 270
    Table 6. UVR electrical characteristics.
    UVR Installation
    11 1 1
    ... .
    Remove the circuit breaker cover(s) as described
    above in 
    3–2 Circuit Breaker Cover.
    22 2 2
    ... .
    The UVR assembles to a mounting plate. Not all
    breakers are shipped from the factory with a mount-
    ing plate. Some breakers have only an L-shaped
    bracket to retain the molded-plastic crank. A mount-
    ing plate is provided in the UVR kit.
    • If the breaker is supplied with an L-shaped
    bracket, remove the two retaining screws and dis-
    card the bracket. Follow the 
    Mounting Plate
    Installation
     instructions and continue on to step
    3.
    • If the breaker is supplied with a mounting plate,
    continue with step 3.
    33 3 3
    ... .
    Remove the slide reset lever spring from the mount-
    ing plate, as shown in Figure 31. Be careful not to
    nick or damage the spring in any way, since it will be
    needed for reassembly.
    44 4 4
    ... .
    Push the latch and slide reset lever forward to pro-
    vide mounting clearance for the UVR assembly.
    55 5 5
    ... .
    Position the UVR assembly mounting bracket so that
    its retaining hole engages the latch pivot post, as
    shown in Figure 32.
    66 6 6
    ... .
    Line up the UVR bracket’s mounting hole with the
    tapped hole in the accessory mounting plate. Install
    the screw and lock washer, as shown in Figure 33.
    Tighten the screw to 9–11 in-lbs.
    77 7 7
    ... .
    Replace the slide reset lever spring, shown in Figure
    31.
    88 8 8
    ... .
    Remove the knockouts in the side of the base, as
    required. Each knockout will accommodate up to
    three bundles of wire. Remove all sharp edges with a
    file.
    99 9 9
    ... .
    Remove all debris from the inside of the breaker. 
    						
    All GE manuals Comments (0)