Home > Data Delivery Devices > Communications receiver > Data Delivery Devices VHF, UHF & ISM Wireless RTU RFScada 8ADI-9DO 4ADI-5DO User Manual

Data Delivery Devices VHF, UHF & ISM Wireless RTU RFScada 8ADI-9DO 4ADI-5DO User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Data Delivery Devices VHF, UHF & ISM Wireless RTU RFScada 8ADI-9DO 4ADI-5DO User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 2 Data Delivery Devices manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 61 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990  
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 63 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
    Special Control Modes. 
    The RFScada units allow remote signal routing of analog and digital signals. In some 
    situations additional control modes are needed, for example controlling outputs depending on input 
    conditions, or sequences of input conditions. Typically a PLC or similar control computer is used to 
    provide this control ‘logic’. The RFScada devices have certain control routines built in, for common 
    control applications, saving the expense of additional controls. The 
    special control modes may be enabled via Modbus register 615, or 
    by using the drop down ‘Control Mode’ selection in the configuration 
    program. All other RFScada functions operate normally even when 
    the special control mode is enabled.  
    Generally all of the special control modes operate by 
    ‘overwriting’ the non existent unit 31’s registers, so the special 
    modes may only run in systems with less than 30 units. Each mode 
    has specific registers in Unit 31 assigned for specific functions, 
    depending on the mode selected. By routing signals in the normal 
    way to and from Unit 31’s registers any input or output on the system 
    may be used as the control logic ‘source’ and ‘destination’. A 
    physical unit assigned to ‘Unit 31’ need not be present for special 
    control mode operation, and the master configuration should be set 
    to ‘disable’ unit 31, although it may be temporarily enabled to allow 
    changes in Unit 31 routing and assignments.   
    Additional control modes may have been added since this 
    was written, please contact the factory for further details or special requirements.  
      
    Digital Pump(s) Control Mode (1)   
    This mode is typically used to control the level in a tank, where the tank is equipped with a 
    ‘Full’ level switch and also an ‘Low’ level switch. The tank is filled by one or more pumps, driven from 
    relay outputs on the RFScada. In normal operation the pump is on until both the low and full inputs 
    are active, when the pump will switch off (i.e. tank is full). The pump will remain off until both the full 
    and low inputs become inactive, when the pump will turn back on (i.e. the level is just below the low 
    switch). An error relay output will activate (and the pump / pumps will shut off) if just the ‘full’ but not 
    the ‘low’ switch is active, since this condition should never occur in normal operation. Additional inputs 
    can also be used to force the pump / pumps off and activate the error relay, these inputs would 
    typically be connected to access door switches, gate interlocks etc. The full and low inputs may be 
    supplied by any digital input on the network, and the pump and error relays may be any one (or more) 
    relays on the network.  
    Many systems just run one pump at a time but have two for backup purposes, and a common 
    requirement is to operate them sequentially, to verify operation of both units and to share wear 
    between them. The control mode supports toggling of dual pumps, effectively replacing more external 
    control logic. 
       
    In this mode the following assignments need to be made.  
     
    Unit 31 Relay 1 must be assigned to the ‘Full’ input (any digital input on any physical unit) 
    Unit 31 Relay 2 must be assigned to the ‘Low’ input (any digital input on any physical unit) 
    Unit 31 Relay 3 may be assigned to cause an error (Optional, any digital input on any unit) 
    Unit 31 Relay 4 may be assigned to cause an error (Optional, any digital input on any unit) 
    Unit 31 Relay 5 may be assigned to cause an error (Optional, any digital input on any unit) 
    Unit 31 Relay 6 may be assigned to cause an error (Optional, any digital input on any unit) 
    Unit 31 Relay 7 may be assigned to cause an error (Optional, any digital input on any unit) 
    Unit 31 Relay 8 may be assigned to cause an error (Optional, any digital input on any unit) 
     
    Unit 31 Digital Input 1 is ‘active’ to run a single pump. (assign pump relay to this input) 
    Unit 31 Digital Input 2 is ‘active’ to for an error. (assign error relay to this input)  
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 64 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
    Unit 31 Digital Input 3 is ‘active’ to run the toggling pump 1. (assign pump 1 relay to this input) 
    Unit 31 Digital Input 4 is ‘active’ to run the toggling pump 2. (assign pump 2 relay to this input) 
     
      
    Tank
    RFScada Full Switch 
    RFScada 
    Pump 
    Low Switch 
    Error Alarm Out 
    Error Alarm Out 
    Complete, Standalone, Remote Pump & Tank Control System Using 
    RFScada Digital Pump Control Mode 
    Pump  
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 65 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
     
    Analog Pump(s) Control Mode (2)   
    This mode is typically used to control the 
    level in a tank, where the tank is equipped with 
    an analog level transducer. Two analog ‘trigger’ 
    levels are set by the operator by using the 
    configuration program, one for the full tank level 
    and another for the empty tank level. The tank is 
    filled by one or more pumps, driven from relay 
    outputs on the RFScada. In normal operation the 
    pump is on until the measured level is above the 
    full set point, when the pump will switch off (i.e. 
    tank is full). The pump will remain off until the 
    level drops below the ‘empty’ set point, when the 
    pump will turn back on. The dialog to set the full 
    and empty points may be found by using the 
    ‘Special Control Settings’ menu. The units are 
    displayed in raw analog input levels for the 4-
    20mA input, from 0 to 1023, (4mA = 204, 20mA 
    =1023) and may be scaled to match the tanks 
    feet, PSI or whatever scale is used. The actual 
    reading being measured may be viewed on the 
    ‘Display Registers’ screen. 
    Additional inputs can also be used to 
    force the pump / pumps off and activate the error 
    relay, these inputs would typically be connected to access door switches, gate interlocks, tank 
    overflow switch etc. The analog level may be supplied by any analog input on the network, and the 
    pump and error relays may be any one (or more) relays on the network.  
    Many systems just run one pump at a time but have two for backup purposes, and a common 
    requirement is to operate them sequentially, to verify operation of both units and to share wear 
    between them. The control mode 2 also supports toggling of dual pumps, effectively replacing more 
    external control logic.   
    In this mode the following assignments need to be made.  
    Unit 31 Analog Output 1 must be assigned to the level transducer source (any analog input on 
    any physical unit)  
     
    Unit 31 Relay 1 may be assigned to cause an error (Optional, any digital input on any unit) 
    Unit 31 Relay 2 may be assigned to cause an error (Optional, any digital input on any unit) 
    Unit 31 Relay 3 may be assigned to cause an error (Optional, any digital input on any unit) 
    Unit 31 Relay 4 may be assigned to cause an error (Optional, any digital input on any unit) 
    Unit 31 Relay 5 may be assigned to cause an error (Optional, any digital input on any unit) 
    Unit 31 Relay 6 may be assigned to cause an error (Optional, any digital input on any unit) 
    Unit 31 Relay 7 may be assigned to cause an error (Optional, any digital input on any unit) 
    Unit 31 Relay 8 may be assigned to cause an error (Optional, any digital input on any unit) 
     
    Unit 31 Digital Input 1 is ‘active’ to run a single pump. (assign pump relay to this input) 
    Unit 31 Digital Input 2 is ‘active’ to indicate an error shutdown. (assign error relay to this input) 
    Unit 31 Digital Input 3 is ‘active’ to run the toggling pump 1. (assign pump 1 relay to this input) 
    Unit 31 Digital Input 4 is ‘active’ to run the toggling pump 2. (assign pump 2 relay to this input) 
     
      
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 66 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
    Tank
    RFScada 
    4-20mA 
    Level 
    Transmitte
    r
    RFScada 
    Pump 
    Error Alarm Out 
    Error Alarm Out 
    Complete, Standalone, Remote Pump & Tank Control System Using 
    RFScada Analog Pump Control Mode 
    Pump 
    Error shutdown 
    Switch (optional) 
    Error shutdown 
    Switch (optional)  
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 67 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990    
    Analog Store Control Mode (3).   
      In some situations it may be required for the RFScada system to store (and preserve 
    through power fails) analog values. In a typical application analog process values may be written via 
    Modbus to an RFScada device, which outputs these values as normal to another device depending 
    on its configuration. Rather than being a typical constant Modbus connection, these writes to the 
    RFScada device may occur sporadically, for example via a low orbiting satellite that may only be in 
    contact occasionally or perhaps via a dial up phone line that incurs call charges. If power to the 
    RFScada is interrupted it needs to maintain the analog values that were written before the power 
    failed. Selecting the Analog Store control mode allows these functions.  
    In this mode the following registers are affected. 
     
    Unit 31 Analog inputs 1 to 8 (Modbus Registers 311 to 318) will retain their last written value 
    indefinitely. Even if the Modbus timeout occurs these registers will be preserved. These registers are 
    stored in non-volatile memory which has a write limitation of 1 million writes, so the RFScada will only 
    store the value in non volatile memory if it has not changed for more than two minutes (this time is 
    pre-set at the factory, it may be displayed in the ‘About’ menu using the configuration software). 
    Therefore for the process values to be stored correctly the power must remain on and the process 
    values must not change for at least two minutes.  
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 68 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
    Mixed Operation with RFScada 2DI-4DO Models.   
      If fitted with the low power ISM radio modules the RFScada 8ADI-9DO and 4ADI-5DO units 
    may communicate with the RFScada 2DI-4DO models, typically for systems that require limited inputs 
    and outputs without analog signals in some locations. In this case any 2DI-4DO models will be pre-
    configured at the factory with unique slave addresses (1 to 31) and they may then be accessed just 
    like a normal 8ADI-9DO model. Instead of 8 digital inputs there will be three transmitted (the two 
    physical inputs plus the state of the 2DI-4DO AC power). The four outputs, normally configured for 2 
    standard outputs, plus remote AC state and network integrity now reflect 3 outputs and the network 
    state. The network state will respond in a similar manner to the standard 8ADI-9DO mode, on 
    continually for correct network operation, toggling on and off for a network error, and off for no signals 
    detected at all. All analog levels reported from the 2DI-4DO units will be zero. The 2DI-4DO models 
    only operate with the low power ISM radios so can only communicate with other models that have the 
    same radio options installed. 
     
      The following tables summarize the capability. 
     
    RFScada 2DI-4DO Transmitted  Inputs  Physical Input 
    Digital 1  1 
    Digital 2  2 
    Digital 3  State of AC power (1 = OK) 
    Digital 4-8  All reported as zero (off) 
     
     
     
    RFScada 2DI-4DO Relay Outputs  Physical Output 
    Relay 1 (SPDT)  Output 1 
    Relay 2 (SPDT)  Output 2 
    Relay 3 (SPST)  AC OK Output / Output 3 
    Relay 4 (SPST)  Network State 
      
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 69 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
    Standalone ‘Master’ System with no slaves.   
      This mode allows remote control and monitoring of a single unit. Simply set the units 
    configuration as a Master and disable all slave units. By using Modbus or the configuration program 
    all the inputs and outputs on this unit may be monitored and controlled remotely, via the RS-232, RS-
    485 or over a phone line if suitable modems are used. Since the unit does not expect a response from 
    any other units it may be operated in a standalone mode without any errors being generated. It may 
    also be configured to route all its own inputs to outputs.  
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 70 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
    Comm Fail Override Mode.   
      Normally the RFScada devices will only maintain outputs when all of the units in a network are 
    communicating correctly. If communications are lost then all remaining units still communicating will 
    turn off all outputs (analog and relays) and the communication status relay and LED (by J11) will 
    toggle. For most applications this is the optimum way to handle signal loss; as a failure anywhere in 
    the system will result in the complete system shutdown, and typically alarm generation, plus complete 
    network integrity may be monitored from all locations.  
    For some specialized applications it would be better for the remaining units to maintain 
    outputs, and the RFScada devices may be programmed to operate this way. This may be required for 
    example where several remote pumps, each controlled by an RFScada device, fill a common tank 
    where another RFScada device monitors the fluid level then sends commands to the remote pumps. If 
    one well is down for service its RFScada device may be without power, resulting in communications 
    failure in the network and a shutdown of the remaining wells. By selecting the ‘Comm Fail Override’ 
    mode the remaining units may continue operation when signals are lost from one (or more) units. The 
    slaves will not be aware that one (or more) other slaves are not operating. The master unit will toggle 
    the comms status LED and relay however, so the error will be detected. If response from all slave 
    devices is lost the masters ‘comms status’ relay and LED will become inactive. 
    The ‘comm fail override’ mode may be selected from a menu when the master configuration 
    screen is displayed. A warning will be displayed during selection and when the feature is enabled.  
        
        
     
     
    As always ensure that the settings are saved using the ‘Write to RFScada EEPROM’ button so 
    the changes will survive subsequent power fails.   
    						
    All Data Delivery Devices manuals Comments (0)

    Related Manuals for Data Delivery Devices VHF, UHF & ISM Wireless RTU RFScada 8ADI-9DO 4ADI-5DO User Manual