Home
>
Data Delivery Devices
>
Communications receiver
>
Data Delivery Devices VHF, UHF & ISM Wireless RTU RFScada 8ADI-9DO 4ADI-5DO User Manual
Data Delivery Devices VHF, UHF & ISM Wireless RTU RFScada 8ADI-9DO 4ADI-5DO User Manual
Have a look at the manual Data Delivery Devices VHF, UHF & ISM Wireless RTU RFScada 8ADI-9DO 4ADI-5DO User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 2 Data Delivery Devices manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 61 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 63 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 Special Control Modes. The RFScada units allow remote signal routing of analog and digital signals. In some situations additional control modes are needed, for example controlling outputs depending on input conditions, or sequences of input conditions. Typically a PLC or similar control computer is used to provide this control ‘logic’. The RFScada devices have certain control routines built in, for common control applications, saving the expense of additional controls. The special control modes may be enabled via Modbus register 615, or by using the drop down ‘Control Mode’ selection in the configuration program. All other RFScada functions operate normally even when the special control mode is enabled. Generally all of the special control modes operate by ‘overwriting’ the non existent unit 31’s registers, so the special modes may only run in systems with less than 30 units. Each mode has specific registers in Unit 31 assigned for specific functions, depending on the mode selected. By routing signals in the normal way to and from Unit 31’s registers any input or output on the system may be used as the control logic ‘source’ and ‘destination’. A physical unit assigned to ‘Unit 31’ need not be present for special control mode operation, and the master configuration should be set to ‘disable’ unit 31, although it may be temporarily enabled to allow changes in Unit 31 routing and assignments. Additional control modes may have been added since this was written, please contact the factory for further details or special requirements. Digital Pump(s) Control Mode (1) This mode is typically used to control the level in a tank, where the tank is equipped with a ‘Full’ level switch and also an ‘Low’ level switch. The tank is filled by one or more pumps, driven from relay outputs on the RFScada. In normal operation the pump is on until both the low and full inputs are active, when the pump will switch off (i.e. tank is full). The pump will remain off until both the full and low inputs become inactive, when the pump will turn back on (i.e. the level is just below the low switch). An error relay output will activate (and the pump / pumps will shut off) if just the ‘full’ but not the ‘low’ switch is active, since this condition should never occur in normal operation. Additional inputs can also be used to force the pump / pumps off and activate the error relay, these inputs would typically be connected to access door switches, gate interlocks etc. The full and low inputs may be supplied by any digital input on the network, and the pump and error relays may be any one (or more) relays on the network. Many systems just run one pump at a time but have two for backup purposes, and a common requirement is to operate them sequentially, to verify operation of both units and to share wear between them. The control mode supports toggling of dual pumps, effectively replacing more external control logic. In this mode the following assignments need to be made. Unit 31 Relay 1 must be assigned to the ‘Full’ input (any digital input on any physical unit) Unit 31 Relay 2 must be assigned to the ‘Low’ input (any digital input on any physical unit) Unit 31 Relay 3 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Relay 4 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Relay 5 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Relay 6 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Relay 7 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Relay 8 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Digital Input 1 is ‘active’ to run a single pump. (assign pump relay to this input) Unit 31 Digital Input 2 is ‘active’ to for an error. (assign error relay to this input)
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 64 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 Unit 31 Digital Input 3 is ‘active’ to run the toggling pump 1. (assign pump 1 relay to this input) Unit 31 Digital Input 4 is ‘active’ to run the toggling pump 2. (assign pump 2 relay to this input) Tank RFScada Full Switch RFScada Pump Low Switch Error Alarm Out Error Alarm Out Complete, Standalone, Remote Pump & Tank Control System Using RFScada Digital Pump Control Mode Pump
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 65 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 Analog Pump(s) Control Mode (2) This mode is typically used to control the level in a tank, where the tank is equipped with an analog level transducer. Two analog ‘trigger’ levels are set by the operator by using the configuration program, one for the full tank level and another for the empty tank level. The tank is filled by one or more pumps, driven from relay outputs on the RFScada. In normal operation the pump is on until the measured level is above the full set point, when the pump will switch off (i.e. tank is full). The pump will remain off until the level drops below the ‘empty’ set point, when the pump will turn back on. The dialog to set the full and empty points may be found by using the ‘Special Control Settings’ menu. The units are displayed in raw analog input levels for the 4- 20mA input, from 0 to 1023, (4mA = 204, 20mA =1023) and may be scaled to match the tanks feet, PSI or whatever scale is used. The actual reading being measured may be viewed on the ‘Display Registers’ screen. Additional inputs can also be used to force the pump / pumps off and activate the error relay, these inputs would typically be connected to access door switches, gate interlocks, tank overflow switch etc. The analog level may be supplied by any analog input on the network, and the pump and error relays may be any one (or more) relays on the network. Many systems just run one pump at a time but have two for backup purposes, and a common requirement is to operate them sequentially, to verify operation of both units and to share wear between them. The control mode 2 also supports toggling of dual pumps, effectively replacing more external control logic. In this mode the following assignments need to be made. Unit 31 Analog Output 1 must be assigned to the level transducer source (any analog input on any physical unit) Unit 31 Relay 1 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Relay 2 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Relay 3 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Relay 4 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Relay 5 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Relay 6 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Relay 7 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Relay 8 may be assigned to cause an error (Optional, any digital input on any unit) Unit 31 Digital Input 1 is ‘active’ to run a single pump. (assign pump relay to this input) Unit 31 Digital Input 2 is ‘active’ to indicate an error shutdown. (assign error relay to this input) Unit 31 Digital Input 3 is ‘active’ to run the toggling pump 1. (assign pump 1 relay to this input) Unit 31 Digital Input 4 is ‘active’ to run the toggling pump 2. (assign pump 2 relay to this input)
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 66 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 Tank RFScada 4-20mA Level Transmitte r RFScada Pump Error Alarm Out Error Alarm Out Complete, Standalone, Remote Pump & Tank Control System Using RFScada Analog Pump Control Mode Pump Error shutdown Switch (optional) Error shutdown Switch (optional)
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 67 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 Analog Store Control Mode (3). In some situations it may be required for the RFScada system to store (and preserve through power fails) analog values. In a typical application analog process values may be written via Modbus to an RFScada device, which outputs these values as normal to another device depending on its configuration. Rather than being a typical constant Modbus connection, these writes to the RFScada device may occur sporadically, for example via a low orbiting satellite that may only be in contact occasionally or perhaps via a dial up phone line that incurs call charges. If power to the RFScada is interrupted it needs to maintain the analog values that were written before the power failed. Selecting the Analog Store control mode allows these functions. In this mode the following registers are affected. Unit 31 Analog inputs 1 to 8 (Modbus Registers 311 to 318) will retain their last written value indefinitely. Even if the Modbus timeout occurs these registers will be preserved. These registers are stored in non-volatile memory which has a write limitation of 1 million writes, so the RFScada will only store the value in non volatile memory if it has not changed for more than two minutes (this time is pre-set at the factory, it may be displayed in the ‘About’ menu using the configuration software). Therefore for the process values to be stored correctly the power must remain on and the process values must not change for at least two minutes.
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 68 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 Mixed Operation with RFScada 2DI-4DO Models. If fitted with the low power ISM radio modules the RFScada 8ADI-9DO and 4ADI-5DO units may communicate with the RFScada 2DI-4DO models, typically for systems that require limited inputs and outputs without analog signals in some locations. In this case any 2DI-4DO models will be pre- configured at the factory with unique slave addresses (1 to 31) and they may then be accessed just like a normal 8ADI-9DO model. Instead of 8 digital inputs there will be three transmitted (the two physical inputs plus the state of the 2DI-4DO AC power). The four outputs, normally configured for 2 standard outputs, plus remote AC state and network integrity now reflect 3 outputs and the network state. The network state will respond in a similar manner to the standard 8ADI-9DO mode, on continually for correct network operation, toggling on and off for a network error, and off for no signals detected at all. All analog levels reported from the 2DI-4DO units will be zero. The 2DI-4DO models only operate with the low power ISM radios so can only communicate with other models that have the same radio options installed. The following tables summarize the capability. RFScada 2DI-4DO Transmitted Inputs Physical Input Digital 1 1 Digital 2 2 Digital 3 State of AC power (1 = OK) Digital 4-8 All reported as zero (off) RFScada 2DI-4DO Relay Outputs Physical Output Relay 1 (SPDT) Output 1 Relay 2 (SPDT) Output 2 Relay 3 (SPST) AC OK Output / Output 3 Relay 4 (SPST) Network State
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 69 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 Standalone ‘Master’ System with no slaves. This mode allows remote control and monitoring of a single unit. Simply set the units configuration as a Master and disable all slave units. By using Modbus or the configuration program all the inputs and outputs on this unit may be monitored and controlled remotely, via the RS-232, RS- 485 or over a phone line if suitable modems are used. Since the unit does not expect a response from any other units it may be operated in a standalone mode without any errors being generated. It may also be configured to route all its own inputs to outputs.
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 70 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 Comm Fail Override Mode. Normally the RFScada devices will only maintain outputs when all of the units in a network are communicating correctly. If communications are lost then all remaining units still communicating will turn off all outputs (analog and relays) and the communication status relay and LED (by J11) will toggle. For most applications this is the optimum way to handle signal loss; as a failure anywhere in the system will result in the complete system shutdown, and typically alarm generation, plus complete network integrity may be monitored from all locations. For some specialized applications it would be better for the remaining units to maintain outputs, and the RFScada devices may be programmed to operate this way. This may be required for example where several remote pumps, each controlled by an RFScada device, fill a common tank where another RFScada device monitors the fluid level then sends commands to the remote pumps. If one well is down for service its RFScada device may be without power, resulting in communications failure in the network and a shutdown of the remaining wells. By selecting the ‘Comm Fail Override’ mode the remaining units may continue operation when signals are lost from one (or more) units. The slaves will not be aware that one (or more) other slaves are not operating. The master unit will toggle the comms status LED and relay however, so the error will be detected. If response from all slave devices is lost the masters ‘comms status’ relay and LED will become inactive. The ‘comm fail override’ mode may be selected from a menu when the master configuration screen is displayed. A warning will be displayed during selection and when the feature is enabled. As always ensure that the settings are saved using the ‘Write to RFScada EEPROM’ button so the changes will survive subsequent power fails.