RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 21 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 J4 5 Relay two contact normally open J4 6 Relay two contact common J5 1 Relay three contact normally closed J5 2 Relay three contact normally open J5 3 Relay three contact common J5 4 Relay four contact normally closed J5 5 Relay four contact normally open J5 6 Relay four contact common J7* 1 Relay five contact normally closed...
Page 22
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 22 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 J1, AC Line Input This is 115 VAC line power and ground connection to the unit. Note, depending upon local codes grounding may also need to be provided from the steel plate which supports the main board. The non-metallic enclosure does not provide grounding from any conduit connections. Always use a ground wire from the external power...
Page 23
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 23 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 When configured for 4-20 mA each of the inputs presents a load of 250 Ohms to ground for the external circuit, so each input may also be used for a 0 to 5 Volt DC input providing the external circuit is capable of driving the load. On the 8ADI-9DO each analog input is protected against external overloads to approximately 40mA, or 10 Volts DC, and on...
Page 24
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 24 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 External DC power supply and 4-20mA transducers If possible each input should have its own current return (the odd numbered pins on these connectors) to maintain highest accuracy, however they may share ground connections in some cases to save wiring. Do not use the system ground as a return for the current loops when using an external...
Page 25
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 25 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 J12, J3 Local Contact Inputs These are transient protected, dry-contact switch or logic level inputs to the RFScada device. Each of the inputs is pulled up to 5 Volts DC via a 1K Ohm resistor, so the inputs may be activated either by a shorting switch contact to ground or they may be directly driven from an ‘open collector’ logic level. Each...
Page 26
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 26 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 be disabled by moving a jumper on the board. All the software settings are unaffected by this jumper; it merely physically disables power to the relay. Once the system has been verified fully operational the jumper may be placed in the power save position; of course it may be placed back in the normal position to verify correct operation at any time....
Page 27
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 27 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 electronic fuse tripping. If this occurs remove DC power, wait a few seconds then restore DC power; normal operation should resume. The 4ADI-5DO unit is diode protected from reverse polarity, has an electronic fuse protecting the on board components, a mechanical (2A 250VDC) fuse protecting the ‘pass thru’ external radio connection (J17) and is also...
Page 28
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 28 – Bartlesville OK Tel 918-335-3318 FAX 918-398-9990 The fuse will blow if there is a malfunction in the circuit, or a voltage greater than the board rating is applied to the AC line input. The fuse is located underneath a safety cover. To test and replace the fuse proceed as follows: First remove the AC and DC (if used) power to the unit. Then open the unit and unplug the AC power connector J1 to allow...