Home > Carrier > Thermostat > Carrier Tstatccnhp01 B Manual

Carrier Tstatccnhp01 B Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Carrier Tstatccnhp01 B Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Non-Programmable Thermostats
    Installation, Start-Up, and Operating Instructions
    NOTE:Read the entire instruction manual before starting the
    installation.
    This symbol®indicates a change since the last issue.
    SAFETY CONSIDERATIONS
    Read and follow manufacturer instructions carefully. Follow all
    local electrical codes during installation. All wiring must conform
    to local and national electrical codes. Improper wiring or installa-
    tion may damage thermostat.
    Recognize safety information. This is the safety-alert symbol
    .
    When you see this symbol on the equipment and in the instruction
    manual, be alert to the potential for personal injury.
    Understand the signal words DANGER, WARNING, and CAU-
    TION. These words are used with the safety-alert symbol. DAN-
    GER identifies the most serious hazards whichwillresult in severe
    personal injury or death. WARNING signifies a hazard which
    couldresult in personal injury or death. CAUTION is used to
    identify unsafe practices whichwouldresult in minor personal
    injury or product and property damage.
    INTRODUCTION
    Carrier thermostats are wall-mounted, low-voltage thermostats
    which maintain room temperature by controlling the operation of
    a heating and air conditioning system. Separate heating and
    cooling setpoints, plus auto changeover provide maximum comfort
    and flexibility. Batteries are not required; temperature and mode
    settings are preserved with the power off.
    INSTALLATION CONSIDERATIONS
    Power
    Note that all thermostat models require no batteries and are not
    power stealing. They do require 24vac (both R and C terminals)
    to be connected for proper operation. Thermostat will not operate
    without these 2 connections.
    Models
    There are 3 different models. The 9th and 10th letters of the part
    number indicate the model. These 2 letters also appear on the
    package and on the circuit board. Be sure to have the proper
    thermostat for the intended application. Models are:
    AC Ð 1-stage cool, 1-stage heat for AC systems only.
    HP Ð 1-stage cool, 2-stage heat for either HP, or AC with 2-stage
    heat.
    2S Ð 2-stage cool, 2-stage heat for 2-speed AC systems, or
    2-stage cool, 3-stage heat for 2-speed HP systems.
    Use each only for its intended purpose. See Table 1.
    INSTALLATION
    Step 1ÐThermostat Location
    Thermostat should be mounted:
    · Approximately 5 ft (1.5m) from floor.
    · Close to or in a frequently used room, preferably on an inside
    partitioning wall.
    · On a section of wall without pipes or duct work.Thermostat should NOT be mounted:
    · Close to a window, on an outside wall, or next to a door leading
    to the outside.
    · Exposed to direct light and heat from a lamp, sun, fireplace, or
    other temperature-radiating object which may cause a false
    reading.
    · Close to or in direct airflow from supply registers and return-air
    grilles.
    · In areas with poor air circulation, such as behind a door or in
    an alcove.
    Step 2ÐSelect Model and Jumper
    AC Model(1-stage cool, 1-stage heat) is to be used for single-
    stage heating and/or cooling applications only. It CANNOT be
    used with optional outdoor temperature sensor. (See Table 1 and
    Fig. 2, 3, 4, 14, and 19.)
    HP Model(1-stage cool, 2-stage heat) can be used with a
    single-speed heat pump (HP), or an air conditioner (AC) with a
    2-stage furnace or fan coil. A resistor (R19) serves as a HP/AC
    selector jumper. This thermostat comes configured from the
    factory as a heat pump thermostat. Leave R19 installed for HP
    operation. Cut and discard for AC operation. When AC operation
    is selected, the O/W2 terminal is converted from a reversing valve
    output (O) to a second-stage heat output (W2). This output can be
    used to control 2-stage furnaces or 2-stage electric heat in fan coils.
    (See Table 1 and Fig. 5, 6, 7, 15, 17, and 21.)
    2S Modelis for 2-speed compressor HP and AC systems only.
    Output Y1 controls compressor low speed and output Y/Y2
    controls compressor high speed. Jumper resistor R19 serves as
    HP/AC selector exactly as described above for HP model. (See
    Table 1 and Fig. 8 through 13, 16, and 18.)
    HEIGHT (IN.) WIDTH (IN.) DEPTH (IN.)
    3-1/25-3/4 1-3/8
    Fig. 1ÐCarrier Non-Programmable Thermostat
    A98422
    Visit www.carrier.com
    Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
    Book 1 4
    Tab misc. misc.
    PC 101 Catalog No. 03TS-TA5 Printed in U.S.A. Form TSTAT-16SI Pg 1 10-98 Replaces: TSTAT-14SI 
    						
    							Step 3ÐInstall Thermostat
    Before installing thermostat, turn off all power to unit. There
    may be more than 1 power disconnect. Electrical shock can
    cause personal injury or death.
    1. Turn OFF all power to unit.
    2. If an existing thermostat is being replaced:
    a. Remove existing thermostat from wall.
    b. Disconnect wires from existing thermostat, 1 at a time. Be
    careful not to allow wires to fall back into the wall.
    c. As each wire is disconnected, record wire color and
    terminal marking.
    d. Discard or recycle old thermostat.
    NOTE:Mercury is a hazardous waste and MUST be disposed of
    properly.
    3. Open thermostat rear door (mounting base) to expose mount-
    ing holes. The base can be removed to simplify mounting.
    Snap apart carefully at hinge to separate mounting base from
    remainder of thermostat.
    4. Route thermostat wires through large hole in mounting base.
    Level mounting base against wall (for aesthetic value
    onlyÐthermostat need not be leveled for proper operation)
    and mark wall through 2 mounting holes.
    5. Drill two 3/16-in. mounting holes in wall where marked.
    6. Secure mounting base to wall with 2 anchors and screws
    provided, (additional anchoring holes available for more
    secure mounting if needed) making sure all wires extend
    through hole in mounting base.
    7. Adjust length and routing of each wire to reach proper
    terminal and connector block on mounting base with 1/4 in. of
    extra wire. Strip only 1/4 in. of insulation from each wire to
    prevent adjacent wires from shorting together when con-
    nected.
    8. Match and connect equipment wires to proper terminals of the
    connector blocks. (See Table 1 and Fig. 2 through 24.) Both R
    and C must be connected for proper thermostat operation.
    Improper wiring or installation may damage the thermostat.
    Check to make sure wiring is correct before proceeding with
    installation or turning on unit.
    9. Push any excess wire into wall and against mounting base.
    Seal hole in wall to prevent air leaks. Leaks can affect
    operation.
    10. Snap hinge back together.
    11. Close thermostat assembly making sure pins on back of circuit
    board align with sockets in connector.12. Turn ON power to unit.
    On power up, LCD readout will display AC, HP, A2, or H2
    depending on the thermostat model and jumper status. See Power
    On Check under Operational Information on page 11 for
    explanation.
    Step 4ÐSet Thermostat Configuration
    Configuration options, like the R19 configuration jumper are
    intended to be selected at installation and are normally not
    modified by the homeowner. These options are not discussed in the
    Homeowners Guide and therefore must be made as part of the
    installation. A special procedure allows entry into the configura-
    tion mode. The thermostat will automatically exit this mode if no
    button is pressed for 3 minutes. While in the configuration mode,
    up to 8 option choices can be made:
    Option 01:Anticipator adjustment
    Option 02: Clean filter timer adjustment
    Option 03: Fahrenheit or Celsius operation
    Option 04: Enable fan (G) on with any heat (W)
    Option 07: Enable zoning
    Option 08: Auxiliary heat lockout temperature adjustment
    Option 13: Room temperature offset adjustment
    Option 15: Enable AUTO mode
    An explanation for each of these and how to enter the configura-
    tion mode follows.
    To enter the configuration mode:
    Press and hold the FAN button for approximately 10 sec until
    room temperature disappears and display reads 01. You are now
    in the configuration mode.
    NOTE:If the FAN button is pressed again or if no button is
    pressed for 3 min, the thermostat will exit the configuration mode
    and return to normal operation. To re-enter the configuration
    mode, the FAN button must be pressed and held for 10 sec again.
    While in configuration mode:
    The display is used to show both the option number and the
    selection choice within that option.
    OPTION 1ÐANTICIPATOR ADJUSTMENT
    This adjustment controls the sensitivity and cycle rate of the
    thermostat. Higher numbers decrease the sensitivity and slow the
    cycle rate. Lower numbers increase sensitivity and increase cycle
    rate. However, a limiting feature will not allow more than 4
    equipment cycles per hr, regardless of setting. Values can range
    from 1 to 9. Factory default setting is 3. This default selection will
    provide optimum performance in nearly all installations. Try it
    first. Do not change setting unless there is evidence of need to do
    so.
    Unlike conventional anticipators, this setting is not to be deter-
    mined by current draw. There is no need to measure, know, or
    Table 1ÐModel Selection and Wiring Diagram Chart
    OUTDOOR UNITAIR CONDITIONER HEAT PUMP
    1 Speed 2 Speed 1 Speed 2 Speed
    1-Stage
    FurnaceModel AC
    See Fig. 2Model 2S
    See Fig. 8Requires
    Dual Fuel ThermostatModel 2S
    See Fig. 11
    2-Stage
    FurnaceModel AC
    See Fig. 3Model HP
    See Fig. 5Model 2S
    See Fig. 9Requires
    Dual Fuel ThermostatModel 2S
    See Fig. 12
    Typical Fan CoilModel AC
    See Fig. 4Model HP
    See Fig. 6Model 2S
    See Fig. 10Model HP
    See Fig. 7Model 2S
    See Fig. 13
    Variable-Speed
    Fan Coil
    (FK4C, FV4A, 40FKA)Model AC
    See Fig. 14Model HP
    See Fig. 15Model 2S
    See Fig. 16Model HP
    See Fig. 17Model 2S
    See Fig. 18
    2
    ®
    ® 
    						
    							compensate for current. There is also no droop with this thermo-
    stat, regardless of anticipator setting. This adjustment controls only
    sensitivity and cycle rate up to the maximum of 4 cycles per hr.
    TO ADJUST:
    1. Enter configuration mode (if not already there).
    2. Use up and down buttons to display 01. This selects Option 1.
    The SET icon should be off.
    3. Press MODE button once. The SET icon will come on. The
    display now shows Option 1 setting.
    4. Use up and down buttons to move between the available
    Option 1 values of 01 to 09. Factory default is 03.
    5. Press MODE button again to return to Option 1 indication of
    01. The SET icon will now be off.
    6. Use up and down buttons to select another Option, or press
    FAN button to exit configuration mode.
    OPTION 2ÐCLEAN FILTER TIMER
    This option selects the number of hours of blower operation
    (heating, cooling, or fan) before FILTER icon is displayed. With
    OF selected, the icon will never come on, disabling this feature.
    Time selection can be from 400 to 3600 hours by selecting
    numbers 01 through 09. (Time is 400 X number selected.) Factory
    default is 2 (800 hours). Recommended selections are: disposable
    filter 800 hr, media filter 1200 to 1600 hr, or electronic air cleaner
    1600 to 2400 hr of blower operation.
    TO ADJUST:
    1. Enter configuration mode (if not already there).
    2. Use up and down buttons to display 02. This selects Option 2.
    The SET icon should be off.
    3. Press MODE button once. The SET icon will come on. The
    display now shows Option 2 setting.
    4. Use up and down buttons to move between the available
    Option 2 values of OF and 01 through 09. Factory default is
    02.
    5. Press MODE button again to return to Option 2 indication of
    02. The SET icon will now be off.
    6. Use up and down buttons to select another Option, or press
    FAN button to exit configuration mode.
    OPTION 3ÐFAHRENHEIT/CELSIUS SELECTION
    This option selects Fahrenheit or Celsius operation.
    TO SELECT:
    1. Enter configuration mode (if not already there).
    2. Use up and down buttons to display 03. This selects Option 3.
    The SET icon should be off.
    3. Press MODE button once. The SET icon will come on. The
    display now shows Option 3 setting.
    4. Use up and down buttons to move between the available
    Option 3 choices of F (Fahrenheit) or C (Celsius). Factory
    default is F.
    5. Press MODE button again to return to Option 3 indication of
    03. The SET icon will now be off.
    6. Use up and down buttons to select another Option, or press
    FAN button to exit configuration mode.
    OPTION 4ÐG (FAN) ON WITH ANY W (HEAT)
    This selection determines whether the G (fan) output is to be ON
    or OFF when any W (furnace or strip heat) output is ON. Most
    furnaces and fan coils manage their own blowers and do not
    require a separate G signal. For these applications, select OFF.Some auxiliary heaters require a separate G signal to turn on the
    blower. In this case, select ON. Factory default is OFF.
    TO SELECT:
    1. Enter configuration mode (if not already there).
    2. Use up and down buttons to display 04. This selects Option 4.
    The SET icon should be off.
    3. Press MODE button once. The SET icon will come on. The
    display now shows Option 4 setting.
    4. Use up and down buttons to move between available Option 4
    choices of ON or OF. Factory default is OF.
    5. Press MODE button again to return to Option 4 indication of
    04. The SET icon will now be off.
    6. Use up and down buttons to select another Option, or press
    FAN button to exit configuration mode.
    OPTION 7ÐZONING ON/OFF SELECTION
    This selection enables or defeats the 15 minute cycle timer, the 15
    minute staging timer, and the 5 minute compressor timeguard. (See
    Operational Information on page 11 for details.) These timers
    MUST be enabled (zoning OFF) for normal operation and disabled
    (zoning ON) for zoning applications. In zoning applications, the
    zone control center performs these timing functions. Factory
    default is OF.
    TO SELECT:
    1. Enter configuration mode (if not already there).
    2. Use up and down buttons to display 07. This selects Option 4.
    The SET icon should be off.
    3. Press MODE button once. The SET icon will come on. The
    display now shows Option 7 setting.
    4. Use up and down buttons to move between available Option 7
    choices of ON or OF.
    5. Press MODE button again to return to Option 7 indication of
    07. The SET icon will now be off.
    6. Use up and down buttons to select another Option, or press
    FAN button to exit configuration mode.
    OPTION 8ÐHIGH AMBIENT AUXILIARY HEAT LOCKOUT
    Present in HP and 2S models only when configured as a heat
    pump. Outdoor temperature sensor must be attached. This selec-
    tion allows lockout of any electric heat (W output) when outdoor
    temperature is above a selected temperature. Temperatures of 5É to
    55ÉF (or equivalent values in C) can be selected. Feature can be
    disabled by selecting OFF. Emergency heat (EHEAT mode)
    always overrides this feature.
    TO SELECT or ADJUST:
    1. Enter configuration mode (if not already there).
    2. Use up and down buttons to display 08. This selects Option 8.
    The SET icon should be off.
    3. Press MODE button once. The SET icon will come on. The
    display now shows Option 8 setting.
    4. Use up and down buttons to move between available Option 8
    choices of OF, or 5 through 55 in 5É steps.
    5. Press MODE button again to return to Option 8 indication of
    08. The SET icon will now be off.
    6. Use up and down buttons to select another Option, or press
    FAN button to exit configuration mode.
    OPTION 13ÐROOM TEMPERATURE OFFSET
    This option allows calibration (or deliberate miscalibration) of
    room temperature sensor. There are various reasons why the
    homeowner may want to have displayed temperature adjusted to a
    3 
    						
    							higher or lower value. The selected number is the number of
    degrees, plus or minus, which will be added to the actual
    temperature. The number can range between -5 and +5. Factory
    default is 0. This adjusted value will be used as actual temperature
    for both display and control action. For example, if 2 is selected,
    72ÉF actual will read 74ÉF. If set point is 72, the room will control
    to an actual value of 70 which will be displayed and acted upon as
    if it were 72. The effect is that a positive number selection will
    make the room temperature lower and vice versa. This thermostat
    is factory calibrated within an accurancy of plus or minus 1ÉF, so
    this adjustment will provide the best accuracy when set to 0.
    TO SELECT:
    1. Enter configuration mode (if not already there).
    2. Use up and down buttons to display 13. This selects Option
    13. The SET icon should be off.
    3. Press MODE button once. The SET icon will come on. The
    display now shows Option 13 setting.
    4. Use up and down buttons to move between available Option
    14 choices of -5 through +5 in 1É steps.
    5. Press MODE button again to return to Option 13 indication of
    13. The SET icon will now be off.
    6. Use up and down buttons to select another Option, or press
    FAN button to exit configuration mode.
    OPTION 15ÐAUTO MODE ON/OFF SELECTION
    This options allows the installer to enable or disable AUTO mode
    (automatic changeover between heat and cool). When disabled,
    AUTO icon does not appear when successive presses of MODE
    button are used to move between OFF, HEAT, and EHEAT (in
    heat pump systems). Factory default is ON (AUTO mode enabled).
    TO SELECT:
    1. Enter configuration mode (if not already there).
    2. Use up and down buttons to display 15. This selects Option
    15. The SET icon should be off.
    3. Press MODE button once. The SET icon will come on. The
    display now shows Option 15 setting.
    4. Use up and down buttons to move between available Option
    15 choices of ON or OF.
    5. Press MODE button again to return to Option 15 indication of
    15. The SET icon will now be off.
    6. Use up and down buttons to select another Option, or press
    FAN button to exit configuration mode.
    Step 5ÐCheck Thermostat Operation
    FAN OPERATION
    1. Press FAN button, starting fan operation. FAN icon turns on.2. Press FAN button again, stopping fan operation. FAN icon
    turns off. (Some fan coils have 90 sec fan off delay, so fan
    may not stop immediately.)
    HEATING OPERATION
    1. Press and release MODE button until HEAT icon appears.
    This selects heating mode.
    2. Press and release up button until set point is at least 5É above
    room temperature. Within a few seconds, HEAT ON icon will
    either stay on or flash. Flashing indicates a heat demand exists,
    but the cycle timer or timeguard timer is delaying heat turn on.
    (See Operational Information on page 11 for timer explana-
    tion.) To defeat timer, simultaneously press FAN and up
    buttons. Heating will come on within a few seconds and
    HEAT ON icon will stay on. Lowering set point to below
    room temperature will turn off heating and remove HEAT ON
    icon within a few seconds.
    COOLING OPERATION
    1. Press and release MODE button until COOL icon appears.
    This selects cooling mode.
    2. Press and release down button until set point is at least 5É
    below room temperature. Within a few seconds, COOL ON
    icon will either stay on or flash. Flashing indicates a cooling
    demand exists, but cycle timer or timeguard timer is delaying
    cooling turn on. (See Operational Information on page 11
    for timer explanation.) To defeat timer, simultaneously press
    FAN and up buttons. Cooling will come on within a few
    seconds and COOL ON icon will stay on. Raising set point to
    above room temperature will turn off cooling and remove
    COOL ON icon within a few seconds.
    OUTDOOR TEMPERATURE
    If system is equipped with an outdoor temperature sensor, check its
    operation by pressing the up and down buttons together. Outdoor
    temperature will be displayed for about 5 sec. If -- is displayed,
    the outdoor temperature sensor is absent or not properly connected.
    Step 6ÐChecklist
    1. Run equipment through several heating and cooling cycles to
    ensure proper operation.
    2. If equipment is to be left in operation, set point and operating
    mode must be properly selected.
    3. Put away tools and instruments, and clean up debris.
    4. Review Homeowners Guide with owner.
    5. Leave literature packet with owner.
    4 
    						
    							®Table 2ÐNon-Programmable Thermostat Quick Reference
    THERMOSTAT OUTPUT
    TSTAT ModelOutdoor Unit R-19 Jumper24v
    HotCommon FanHeat
    Stage 1Heat
    Stage 2Heat
    Stage 3Cool
    Stage 1Cool
    Stage 2Reversing Valve
    AC01-BAC N/A R C G W/W1 N/A N/A Y/Y2 N/A N/A
    HP01-BHP Uncut R C G Y/Y2 W/W1 N/A Y/Y2 N/A O/W2
    HP01-BAC Cut R C G W/W1 O/W2 N/A Y/Y2 N/A N/A
    2S01-B2-Speed AC Cut R C G W/W1 O/W2 N/A Y1 Y/Y2 N/A
    2S01-B2-Speed HP Uncut R C G Y1 Y/Y2 W/W1 Y1 Y/Y2 O/W2
    Model Numbers: TSTATCCNAC01-B, TSTATCCNHP01-B, TSTATCCN2S01-B
    Note: AC = Air Conditioner, HP = Heat Pump, 2S = 2-Speed, N/A = Not Applicable
    ®Fig 4ÐSingle-Speed Air Conditioner
    with Typical Fan Coil
    A98453
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    
    
    
    COOL STAGE 1
    
    
    
    R
    C
    G
    W/W1Y/Y2
    R
    CC
    Y
    MODEL AC
    THERMOSTATTYPICAL
    FAN COILSINGLE-SPEED
    AIR CONDITIONER
    See notes 6 and 11
    Y G*
    W2
    E
    W3
    HEAT STAGE 1FAN
    Fig. 2ÐSingle-Speed Air Conditioner
    with Single-Stage Furnace
    A97237
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 1
    
    
    COOL STAGE 1
    
    
    FANR
    C
    G
    W/W1
    Y/Y2
    R
    CC
    MODEL AC
    THERMOSTATSINGLE-STAGE
    FURNACESINGLE-SPEED
    AIR CONDITIONER
    G
    W
    Y
    Y
    ®Fig. 5ÐSingle-Speed Air Conditioner
    with 2-Stage or Variable-Speed Furnace
    A98454
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 1
    
    
    COOL STAGE 1
    
    
    FANR
    C
    G
    W/W1
    Y/Y2
    R
    C
    W2
    HUM
    C
    Y
    MODEL HP
    THERMOSTATTWO-STAGE OR
    VARIABLE-SPEED
    FURNACESINGLE-SPEED
    AIR CONDITIONER
    See notes 2 and 3 W/W1
    Y/Y2
    G
    HEAT STAGE 2
    
    
    N/A
    
    
    N/A
    
    
    OUTDOOR
    
    SENSOR
    
    CONNECTIONY1
    B
    S1
    S2
    O/W2
    ®Fig. 3ÐSingle-Speed Air Conditioner
    with 2-Stage or Variable-Speed Furnace
    A98452
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 1
    
    
    COOL STAGE 1
    
    
    FANR
    C
    G
    W/W1
    Y/Y2
    R
    CC
    MODEL AC
    THERMOSTATTWO-STAGE OR
    VARIABLE-SPEED
    FURNACESINGLE-SPEED
    AIR CONDITIONER
    See note 1 G
    Y
    W/W1
    Y/Y2
    HUM
    W2
    5 
    						
    							®Fig. 8ÐTwo-Speed Air Conditioner
    with Single-Stage Furnace
    A98457
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 1
    
    
    COOL STAGE 2
    
    
    FANR
    C
    G
    W/W1
    Y/Y2
    R
    C
    N/A
    
    
    COOL STAGE 1
    
    
    N/A
    
    
    OUTDOOR
    
    SENSOR
    
    CONNECTIONY1
    B
    S1
    S2
    C
    MODEL 2S
    THERMOSTATSINGLE-STAGE
    FURNACETWO-SPEED
    AIR CONDITIONER
    See notes 2, 5,  and 8
    G
    O/W2
    WR
    YY2
    Y1
    ®Fig. 6ÐSingle-Speed Air Conditioner
    with Typical Fan Coil
    A98455
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 1
    
    
    COOL STAGE 1
    
    
    FANR
    C
    G
    W/W1
    Y/Y2
    R
    C
    HEAT STAGE 2
    
    
    N/A
    
    
    N/A
    
    
    OUTDOOR
    
    SENSOR
    
    CONNECTIONY1
    B
    S1
    S2
    C
    Y
    MODEL HP
    THERMOSTATTYPICAL
    FAN COILSINGLE-SPEED
    AIR CONDITIONER
    See notes 2, 4, 6, and 11
    Y
    G
    O/W2
    *
    W2
    E
    W3
    ®Fig. 9ÐTwo-Speed Air Conditioner
    with 2-Stage or Variable-Speed Furnace
    A98458
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 1
    
    
    COOL STAGE 2
    
    
    FANR
    C
    G
    W/W1
    Y/Y2
    R
    C
    HEAT STAGE 2
    
    
    COOL STAGE 1
    
    
    N/A
    
    
    OUTDOOR
    
    SENSOR
    
    CONNECTIONY1
    B
    S1
    S2
    C
    MODEL 2S
    THERMOSTATTWO-STAGE OR
    VARIABLE-SPEED
    FURNACETWO-SPEED
    AIR CONDITIONER
    See notes 2, 3, 6, and 8G
    O/W2
    R
    Y2
    W/W1
    Y/Y2
    W2
    Y1
    Y1*
    HUM
    ®Fig. 7ÐSingle-Speed Heat Pump
    with Typical Fan Coil
    A98456
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    
    R
    C
    G
    W/W1Y/Y2
    R
    C
    RVS COOLING
    
    
    N/A
    
    
    
    
    
    OUTDOOR
    
    SENSOR
    
    CONNECTIONY1
    B
    S1
    S2
    C
    Y
    MODEL HP
    THERMOSTATTYPICAL
    FAN COILSINGLE-SPEED
    HEAT PUMP
    See notes 6, 7, and 11
    Y G
    O/W2
    *
    W2
    R
    W2
    OE
    W3
    COOL/ HEAT 
    STAGE 1FAN
    N/A
    
    
     HEAT STAGE 2
    6 
    						
    							®Fig. 12ÐTwo-Speed Heat Pump
    with 2-Stage or Variable-Speed Furnace
    A98461
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 3
    
    
    COOL/HEAT
    STAGE 2
    
    FANR
    C
    G
    W/W1
    Y/Y2
    R
    C
    RVS COOLING
    
    
    COOL/HEAT
    STAGE 1
    
    
    N/A
    
    
    OUTDOOR
    
    SENSOR
    
    CONNECTIONY1
    B
    S1
    S2
    C
    MODEL 2S
    THERMOSTATTWO-STAGE OR
    VARIABLE-SPEED
    FURNACETWO-SPEED
    HEAT PUMP
    See notes 1, 6, 7, 8, and 10G
    O/W2
    HUM
    R
    Y2
    Y1
    O
    W2
    W3
    W2
    O
    Y1
    W/W1
    Y/Y2
    * *
    ®Fig. 10ÐTwo-Speed Air Conditioner
    with Typical Fan Coil
    A98459
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 1
    
    
    COOL STAGE 2
    
    
    FANR
    C
    G
    W/W1
    Y/Y2
    R
    C
    HEAT STAGE 2
    
    
    COOL STAGE 1
    
    
    N/A
    
    
    OUTDOOR
    
    SENSOR
    
    CONNECTIONY1
    B
    S1
    S2
    C
    Y1
    MODEL 2S
    THERMOSTATTYPICAL
    FAN COILTWO-SPEED
    AIR CONDITIONER
    See notes 2, 4, 5, 6, 8, and 11
    Y
    G
    O/W2
    *
    W2
    R
    Y2
    E
    W3
    ®Fig. 13ÐTwo-Speed Heat Pump
    with Typical Fan Coil
    A98462
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    
    
    
    COOL/HEAT
    STAGE 2
    
    
    R
    C
    G
    W/W1Y/Y2
    R
    C
    RVS COOLING
    
    
    COOL/HEAT
    STAGE 1
    
    N/A
    
    
    OUTDOOR
    
    SENSOR
    
    CONNECTIONY1
    B
    S1
    S2
    W3
    C
    Y1
    MODEL 2S
    THERMOSTATTYPICAL
    FAN COILTWO-SPEED
    HEAT PUMP
    See notes  5, 6, 7, 8, 10, and 11
    Y G
    O/W2
    *
    W2
    R
    Y2
    E
    W3
    O
    W2HEAT STAGE 3
    
    
     FAN
    ®Fig. 11ÐTwo-Speed Heat Pump
    with Single-Stage Furnace
    A98460
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 3
    
    
    COOL/HEAT
    STAGE 2
    
    FANR
    C
    G
    W/W1
    Y/Y2
    R
    C
    RVS COOLING
    
    
    COOL/HEAT
    STAGE 1
    
    
    N/A
    
    
    OUTDOOR
    
    SENSOR
    
    CONNECTIONY1
    B
    S1
    S2
    C
    MODEL 2S
    THERMOSTATSINGLE-STAGE
    FURNACETWO-SPEED
    HEAT PUMP
    See note 5, 7, 8, and 10
    G
    O/W2
    WR
    YY2
    Y1
    O
    W2
    W3
    7 
    						
    							®Fig. 16ÐTwo-Speed Air Conditioner with Variable-
    Speed (FK4C, FV4A, 40FKA) Fan Coil
    A98465
    24 VOLT HOT
    
    
    24 VOLT COMM
    
    
    FAN
    
    
    COOL STAGE 2
    
    
    HEAT STAGE 1R
    Y/Y2
    R
    Y2
    CCC
    R
    L
    Y1
    MODEL 2S
    THERMOSTATEASY SELECT
    TERMINAL BOARDTWO-SPEED
    AIR CONDITIONER
    J1 JUMPER
    REMOVE
    J2 JUMPER
    FOR HEAT
    STAGING
    See notes 2, 4, 8, and 11
    GG
    Y/Y2
    DH
    W/W1W1
    HEAT STAGE 2
    
    
    COOL STAGE 1
    
    Y1O/W2
    Y1
    O
    W2
    B
    S1
    S2
    N/A
    
    OUTDOOR
    
    SENSOR
    
    CONNECTION
    ®Fig. 14ÐSingle-Speed Air Conditioner with
    Variable-Speed (FK4C, FV4A, 40FKA) Fan Coil
    A98463
    R
    Y/Y2
    R
    Y
    W/W1W1
    C
    MODEL AC
    THERMOSTATEASY SELECT
    TERMINAL BOARDSINGLE-SPEED
    AIR CONDITIONER
    J1 JUMPER
    J2 JUMPER
    See note 11 W2
    Y/Y2
    DH
    GG
    Y1
    O
    C
    HEAT STAGE 124 VAC HOT
    C
    COOL STAGE 1
    FAN
    24 VAC COMM
    ®Fig. 17ÐSingle-Speed Heat Pump with
    Variable-Speed (FK4C, FV4A, 40FKA) Fan Coil
    A98466
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    FAN
    
    
    COOL/HEAT
    STAGE 1
    
    HEAT STAGE 2R
    Y/Y2
    R
    CCC
    R
    MODEL HP
    THERMOSTATEASY SELECT
    TERMINAL BOARDSINGLE-SPEED
    HEAT PUMP
    J1 JUMPER
    J2 JUMPER
    See notes 7, 8, and 11
    GG
    Y/Y2
    DH
    W/W1W1
    N/A
    
    
    RVS COOLING
    
    
    N/A
    
    
    OUTDOOR
    
    SENSOR
    
    CONNECTIONY1
    B
    S1
    S2
    O/W2
    Y1
    O
    W2W2
    Y
    O
    ®Fig. 15ÐSingle-Speed Air Conditioner with
    Variable-Speed (FK4C, FV4A, 40FKA) Fan Coil
    A98464
    24 VAC HOT
    
    
    HEAT STAGE 1
    
    
    24 VAC COMM
    
    
    COOL STAGE 1
    
    
    FANR
    G
    W/W1
    Y/Y2
    R
    Y
    CCC
    MODEL HP
    THERMOSTAT
    EASY SELECT
    TERMINAL BOARDSINGLE-SPEED
    AIR CONDITIONER
    J1 JUMPER
    REMOVE
    J2 JUMPER
    FOR HEAT
    STAGING
    See notes 2, 4, and 11 G
    W1
    Y/Y2
    DH
    HEAT STAGE 2
    
    
    N/A
    
    
    N/A
    
    
    OUTDOOR
    
    SENSOR
    
    CONNECTIONY1
    B
    S1
    S2
    O/W2
    Y1
    O
    W2
    8 
    						
    							®Fig. 20ÐSingle-Speed Packaged Air Conditioner
    with Single-Speed Electric Heat (50SS, SX, ZP)
    A98470
    SPLICE
    BOX
    RED
    YELWHT
    See notes 8 and 12HEATER
    CONTROL BOX
    GRN
    BRN
    BRN
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 1
    
    
    COOL STAGE 1
    
    
    FANCR
    G
    W/W1
    Y/Y2
    MODEL AC
    THERMOSTAT
    ®Fig. 18ÐTwo-Speed Heat Pump with
    Variable-Speed (FK4C, FV4A, 40FKA) Fan Coil
    A98467
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    FAN
    
    
    COOL/HEAT
    STAGE 2
    
    HEAT STAGE 3R
    Y/Y2
    R
    CCC
    R
    MODEL 2S
    THERMOSTATEASY SELECT
    TERMINAL BOARDTWO-SPEED
    HEAT PUMP
    J1 JUMPER
    J2 JUMPER
    See notes 5, 7, 8, 10, and 11
    GG
    Y/Y2
    DH
    W/W1W1
    W2W2
    RVS COOLING
    
    
    COOL/HEAT
    STAGE 1
    
    N/A
    
    
    OUTDOOR
    
    SENSOR
    
    CONNECTIONY1
    S1
    S2
    B
    Y1Y1
    Y2
    O/W2OO
    ®Fig. 21ÐSingle-Speed Packaged Air Conditioner
    with 2-Stage Electric Heat (50SS, SX, ZP)
    A98471
    B
    S1
    S2
    SPLICE
    BOX
    YELWHT
    PNK
    See notes 2, 8, 9, and 12
    O/W2HEAT STAGE 2
    N/AY1
    N/A
    
    OUTDOOR
    
    SENSOR
    
    CONNECTION
    HEATER
    CONTROL BOX
    GRN
    VIO
    BRN
    BRN
    RED
    RED24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 1
    
    
    COOL STAGE 1
    
    
    FANCR
    G
    W/W1
    Y/Y2
    MODEL HP
    THERMOSTAT
    RED (TRAN)
    ®Fig. 19ÐSingle-Speed Packaged Air Conditioner
    with Single-Stage Gas Furnace (48SS, SX)
    A98469
    24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 1
    
    
    COOL STAGE 1
    
    
    FANCR
    G
    W/W1
    Y/Y2
    MODEL AC
    THERMOSTATSPLICE
    BOX
    RED
    BRN
    WHT
    YEL
    GRN
    See note 8
    9 
    						
    							®Fig. 22ÐSingle-Speed Packaged Heat Pump with
    Single-Stage Electric Heat (50HS, HX, ZH)
    A98472
    B
    S1
    S2
    SPLICE
    BOX
    YELWHT
    See notes  8, and 12
    O/W2RVS COOLING
    N/AY1
    N/A
    
    OUTDOOR
    
    SENSOR
    
    CONNECTION
    HEATER
    CONTROL BOX
    GRN
    ORN
    BRN
    BRN
    RED24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 2
    
    
    COOL/HEAT
     STAGE 1
    
    FANCR
    G
    W/W1
    Y/Y2
    MODEL HP
    THERMOSTAT
    ®Fig. 23ÐSingle-speed Packaged Heat Pump with
    2-Stage Electric Heat (50HS, HX, ZH)
    A98473
    B
    S1
    S2
    SPLICE
    BOX
    YELWHT
    O/W2RVS COOLING
    N/AY1
    N/A
    
    OUTDOOR
    
    SENSOR
    
    CONNECTION
    HEATER
    CONTROL BOX
    ORN
    VIO
    BRN
    BRN
    RED
    RED24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 2
    
    
    COOL/HEAT
     STAGE 1
    
    FANCR
    G
    W/W1
    Y/Y2
    MODEL HP
    THERMOSTAT
    PNK RED (TRAN)
    See notes  8, 9, and 12
    ®Fig. 24ÐSingle-Speed Packaged Heat Pump
    with Single-Stage Gas Furnace (48HX)
    A98474
    B
    S1
    S2
    SPLICE
    BOX
    WHT
    YEL
    O/W2RVS COOLING
    N/AY1
    N/A
    
    OUTDOOR
    
    SENSOR
    
    CONNECTION
    GRN
    ORN
    BRN
    RED24 VAC HOT
    
    
    24 VAC COMM
    
    
    HEAT STAGE 2
    
    
    COOL/HEAT
     STAGE 1
    
    FANCR
    G
    W/W1
    Y/Y2
    MODEL HP
    THERMOSTAT
    See notes 8, and 12
    ®WIRING DIAGRAM NOTES:
    1. Furnace must control its own second-stage heat operation via
    furnace control algorithm. Refer to indoor equipment Instal-
    lation Instructions for proper setup.
    2. Cut jumper R19 to convert thermostat to air conditioning
    operation.
    3. As an option, lock the furnace into low-fire operation and let
    O/W2 control high-fire operation. Refer to indoor equipment
    Installation Instructions for proper setup.
    4. O/W2 can control second-stage heat. Refer to indoor equip-
    ment Installation Instructions for proper setup.
    5. Refer to outdoor equipment Installation Instructions for latent
    kit requirements.
    6. Terminals marked with * may not be present on equipment.
    7. O/W2 energizes reversing valve in cooling.
    8. Refer to outdoor equipment Installation Instructions for proper
    setup.
    9. Omit red and pink wires from diagram when wiring a 50ZP,
    ZH with 2-stage heaters.
    10. Select the ZONE position on the 2-speed heat pump control
    board.
    11. Refer to fan coil Installation Instructions for proper wiring.
    12. Program thermostat to bring on G (fan) with any W (heat)
    selection. See section under Set Thermostat Configuration.
    10 
    						
    All Carrier manuals Comments (0)

    Related Manuals for Carrier Tstatccnhp01 B Manual