Home > Carrier > Thermostat > Carrier Systxccuid01 B Manual

Carrier Systxccuid01 B Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Carrier Systxccuid01 B Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							SYSTXCCUID01
    Infinity Control™
    Installation and Start-Up Instructions
    NOTE:Read the entire instruction manual before starting the
    installation.
    This symbol→indicates a change since the last issue.
    TABLE OF CONTENTS
    SAFETY CONSIDERATIONS .....................................................1
    INTRODUCTION ..........................................................................1
    INSTALLATION AND START-UP OVERVIEW ......................1
    INSTALLATION ...........................................................................2
    INITIAL POWER-UP ....................................................................5
    QUICK START..............................................................................6
    INSTALL / SERVICE MENUS ....................................................7
    OPERATIONAL INFORMATION .............................................11
    TROUBLESHOOTING ...............................................................12
    SAFETY CONSIDERATIONS
    Read and follow manufacturer instructions carefully. Follow all
    local electrical codes during installation. All wiring must conform
    to local and national electrical codes. Improper wiring or installa-
    tion may damage Infinity Control System. Recognize safety
    information. This is the safety-alert symbol
    . When you see this
    symbol on the equipment and in the instruction manual, be alert to
    the potential for personal injury. Understand the signal words
    DANGER, WARNING, andCAUTION.These words are used with the safety-alert symbol.DANGER
    identifies the most serious hazards, whichwillresult in severe
    personal injury or death.WARNINGsignifies a hazard, which
    couldresult in personal injury or death.CAUTIONis used to
    identify unsafe practices, whichwouldresult in minor personal
    injury or product and property damage.NOTEis used to highlight
    suggestions which will result in enhanced installation, reliability,
    or operation.
    INTRODUCTION
    The Infinity System consists of intelligent communicating com-
    ponents (User Interface, variable speed furnace or fan coil, AC or
    HP), which continually communicate with each other via a
    four-wire connection called the ABCD bus. Conventional 24-volt
    signals on dedicated wires are not needed. Commands, operating
    conditions, and other data are passed continually between the
    components over the ABCD bus. The result is a new level of
    comfort, versatility, and simplicity.
    An Infinity System consists of a Infinity Control™ (thermostat
    plus much more) and an Infinity furnace or fan coil. All Infinity
    furnaces or fan coils are variable-speed and multi stage for
    maximum flexibility, efficiency, and comfort. They support con-
    trolled ventilation, humidification, dehumidification, and air qual-
    ity control. Either an Infinity dual capacity (communicating), or a
    standard 24 vac controlled outdoor unit may be used.
    When using conventional outdoor units, the Infinity furnace or fan
    coil provides the 24 volt signals needed to control them. Also, the
    Infinity Network Interface Module (NIM) allows connection of a
    conventional HRV or ERV without the need for a separate wall
    control.
    All system components are controlled through the wall mounted
    Infinity Control™, which replaces the conventional thermostat and
    provides the homeowner with a single wall control for all the
    features of the system.
    INSTALLATION AND START-UP OVERVIEW
    This instruction covers installation of the Infinity Control™only.
    Physical installation instructions for the indoor, outdoor equipment
    and accessories are provided with each unit.
    Setup, commissioning, operation, and troubleshooting of the
    Infinity System is coveredonlyin this installation instruction. It is
    your guide to connecting the system components and commission-
    ing the system once all the physical components are installed.
    Special screen prompts and start-up capabilities are provided in the
    Infinity System to simplify and lead you through the initial
    commissioning of the system. So:
     Install the Infinity Control™ according to this instruction.
     Install the indoor unit, outdoor unit, and accessories according
    to their instructions.
     Wire the complete system according to this instruction.
     Setup, commission, and operate the system according to this
    instruction to assure yourself a smooth and trouble free
    start-up.
    HOLDCOOLHEAT
    OFF
    Infinity Control™
    SYSTXCCUID01
    A03149
    Visit www.carrier.com
    Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
    Book 1 4
    Tab misc. misc.
    PC 101 Catalog No. 809-50020 Printed in U.S.A. Form UID01-1SI Pg 1 01-04 Replaces: NEW 
    						
    							INSTALLATION
    STEP 1—CHECK EQUIPMENT AND JOB SITE
    INSPECT EQUIPMENT—File claim with shipping company,
    prior to installation, if shipment is damaged or incomplete.
    STEP 2—INFINITY CONTROL™LOCATION AND WIRING
    CONSIDERATIONS
    ELECTRICAL SHOCK HAZARD
    Failure to follow this warning could result in personal injury
    or possible equipment damage.
    Disconnect Power before routing control wiring.
    All wiring must comply with national, local, and state codes.
    INFINITY CONTROL™LOCATION—The Infinity Control™
    is the command center for the Infinity System. It should be located
    where it is easily accessible and visible to the adult homeowner or
    end user.
    For accurate temperature measurement, the following guidelines
    should be followed:
    The Infinity Control™should be mounted:
    Approximately 5 feet (1.5 meters) from the floor.
    Close to or in a frequently used room, preferably on an inside
    partitioning wall.
    On a section of wall without pipes or duct work.
    The Infinity Control™should NOT be mounted:
    Close to a window, on an outside wall, or next to a door leading
    to the outside.
    Exposed to direct light or heat from a lamp, sun, fireplace, or
    other temperature-radiating objects which could cause a false
    reading.
    Close to or in direct airflow from supply registers.
    In areas with poor air circulation, such as behind a door or in
    an alcove.
    REMOTE SENSOR OPTION—A remote room sensor can be
    used with the Infinity Control™to take the place of the internal
    temperature sensor. This allows the control to be mounted in areas
    with less than optimal airflow (such as near an exterior door,
    window or in a closet). The remote sensor is wired to the terminal
    block connectors labeled S1 and S2. The Infinity Control™will
    automatically detect the remote sensor and ignore its internal
    sensor. It is also important to note the humidity sensor cannot be
    remotely located, so do not locate the Infinity Control™in an area
    where humidity sensing may not be accurate.
    NOTE:S1 & S2 connection on UI back-plate is now used for the
    Remote Room Sensor,NOTfor OAT Sensor hookup (S1 & S2
    was previously used for OAT).
    WIRING CONSIDERATIONS—Ordinary thermostat wire is
    recommended. Use 22 AWG or larger for normal wiring applica-
    tions. Continuous wire lengths over 100 ft. should use 20 AWG or
    larger.
    NOTE:ABCD bus wiring only requires a four-wire connection;
    however, it is good practice to run thermostat cable having more
    than four wires in the event of a damaged or broken wire during
    the installation.
    Each device in the Infinity System has a four-pin connector labeled
    ABCD. It is recommended that the following color code be used
    when wiring each device:
    A—Green = Data A
    B—Yellow = Data B
    C—White = 24VAC (Com)
    D—Red = 24VAC (Hot)It is not mandatory that the above color code be used, but each
    ABCD connector in the systemMUSTbe wired consistently.
    MOUNTING INFINITY CONTROL™—There are two options
    for mounting the Infinity Control™to the wall. First, familiarize
    yourself with all plastic assembly pieces shown in Figs. 2 through
    9. The User Interface will snap together with either the Recess
    Mount or the Surface Mount backplate.
    RECESS MOUNT—This provides the thinnest mounting con-
    figuration (See Fig. 3). The backplate containing the recessed
    terminal block can be mounted directly to the wall by cutting a
    hole 1½″wide by 2 1/8″high. Mark location and cut hole in wall.
    NOTE:Always ensure the Infinity Control™location is accept-
    able before cutting any holes in wall.
    SURFACE MOUNT—This provides surface mounting configu-
    ration, which allows use of a small hole in the wall. A surface
    mount backplate is supplied (See Fig. 4). Attach backplate as
    shown in figure 7, and the assembly will mount directly to the wall
    requiring only a small hole in the wall allowing a four wire
    connection to pass through.
    NOTE:Once Infinity Control™is secured to wall with the
    backplate assembly (snapped together), care must be taken not to
    bend or break the interlocking tabs when removing. Gently remove
    Infinity Control by rocking up/down until interlocking tabs release.
    DECORATIVE BACKPLATE—Supplied, is a thin, decorative
    backplate (see Fig. 5), to hide any marks/screw holes left from the
    previous thermostat. This decorative backplate (or beauty ring) can
    be used in either the recess or surface mount installation by
    snapping it onto the back of the recessed mount backplate or
    surface mount backplate before securing to the wall. See Fig. 8 and
    9 for a larger decorative backplate (5.75″wide X 6″tall), which
    can be ordered separately.
    STEP 3—INSTALLING INFINITY CONTROL™
    ELECTRICAL SHOCK HAZARD
    Failure to follow this warning could result in personal injury
    or death.
    Before installing Infinity Control™, turn off all power to
    equipment. There may be more than one power source to
    disconnect.
    1. Turn off all power to equipment.
    2. If an existing thermostat is being replaced:
    a. Remove existing thermostat from wall.
    b. Disconnect wires from existing thermostat.
    Fig. 2—Infinity Control™
    A03185
    2 
    						
    							c. Discard or recycle old thermostat.
    NOTE:Mercury is a hazardous waste andMUSTbe disposed of
    properly.
    3. Select Infinity Control™mounting plastic (recess mount or
    surface mount and decorative backplate if desired).
    4. Route wires through large hole in mounting plastic. Level rear
    plastic against wall (for aesthetic value only - Infinity Con-
    trol™need not be level to operate properly) and mark wall
    through two mounting holes.
    5. Drill two 3/16 inch mounting holes in wall where marked.
    6. Secure mounting plastic to wall using two screws and anchors
    provided.
    7. Adjust length and routing of each wire to reach each wire
    entry on the connector backplate. Strip¼inch of insulation
    from each wire.8. Match and connect thermostat wires to proper terminals on
    User Interface backplate. See wiring diagram figures 12, 13
    and 14.
    A—Green = Data A
    B—Yellow = Data B
    C—White = 24VAC (Com)
    D—Red = 24VAC (Hot)
    NOTE:It is not mandatory that the above color code be used, but
    each ABCD connection in the systemMUSTbe wired consis-
    tently. A separate ABCD Connector comes inside packaging and
    should be used when connecting to the furnace (or fan coil). (See
    Fig. 10)
    NOTE:Insert connector properly into circuit board.
    Fig. 3—Recessed Mount Backplate
    A03186
    Fig. 4—Surface Mount Backplate
    A03187
    Fig. 5—Thin Decorative Backplate
    A04017
    Fig. 6—Recessed Mount Assembly
    A03190
    Recessed terminal
    block in wall 11/2˝
    wide by 2 1/8˝ high
    Recessed Mount
    Interlocking Tabs (4)
    Fig. 7—Surface Mount Assembly
    A03191
    Surface Mount
    Backplate to wall
    Interlocking Tabs (4)
    Fig. 8—Large Decorative Backplate
    A03188
    3 
    						
    							ELECTRICAL OPERATION HAZARD
    Failure to follow this caution will result in equipment damage
    or improper operation.
    Improper wiring of the ABCD connector will cause the
    Infinity Control™to operate improperly. Check to make sure
    all wiring is correct before proceeding with installation or
    turning on power.
    9. Push any excess wire into the wall. Seal hole in wall to prevent
    any air leaks. Leaks can affect operation.
    10. Attach Infinity Control™to the mounting plastic by lining up
    the plastic guides on the back of the control with the opening
    on the mounting plastic and push on.
    11. Perform installation of all other system equipment (i.e. hu-
    midifier, ventilator, UV lights, etc.)
    12. Turn on power to equipment.
    EQUIPMENT WIRING DIAGRAMS:
    See wiring diagram Figs. 12, 13 and 14.
    NOTE:For other applications not listed, refer to the Network
    Interface Module (NIM) Installation Instructions.
    See wiring diagram figure 12 for a Typical Four-Wire Connection
    Diagram, which includes an Infinity indoor communicating fur-
    nace or FE fan coil with a 2-speed Puron®communicating outdoor
    unit. No additional OAT (outdoor air temperature) sensor is
    required because the Infinity Control will use the temperature
    sensor inside the 2-speed unit.
    See wiring diagram figure 13 for a Typical Connection Diagram,
    which includes an Infinity indoor communicating furnace or FE
    fan coil, with a 1-speed air conditioning unit (non-communicating
    outdoor). An Outdoor Air Temperature sensor may be installed
    (not required) at the indoor furnace or fan coil OAT terminals.
    When OAT is applied, the Infinity System will provide full system
    features and benefits.
    See wiring diagram Fig. 14 for a Typical Connection Diagram for
    FE fan coil with a 1-speed heat pump (using non-communicating
    outdoor unit). When OAT is applied, the Infinity System will
    provide full system features and benenfits.HUMIDIFIER CONNECTION —A 24vac bypass or fan
    powered humidifier may be installed.
    NOTE:Do Not Use a traditional humidistat to control humidifier
    operation. If a humidifier is installed, let the Infinity System
    control humidifier operation.
    Bypass Humidifiers —A bypass humidifier should be wired
    directly to the furnace or fan coil HUM and 24vac COM terminals.
    The Infinity Control will automatically energize the HUM output
    during a call for humidification.
    Fan Powered Humidifiers —Most fan powered humidifiers
    produce internal 24vac in order to energize upon a switch or
    contact closure. For this application, a 24vac N.O. Isolation Relay
    (DPST)MUST be usedto prevent mixing the internal humidifier
    power with the indoor equipment transformer. Applying 24vac
    isolation relay coil to furnace or fan coil HUM and COM terminals
    will allow the Infinity Control to automatically energize the HUM
    output during a call for humidification. The N.O. relay contacts
    will be used to energize the humidifier. See fan powered humidi-
    fier installation instructions for more details.
    Fig. 9—Decorative Backplate Assembly
    A03192
    Fig. 10—4–Wire ABCD Connector
    A03193ABCD
    Fig. 11—Functional Overview
    A03194
    HOLDCOOLHEAT
    SCHEDULE VACATION
    PROGRAMSCROLL
    BASIC
    ADVANCED
    SETUPS
    Schedule
    to program
    temperature
    scheduleVacation
    to start/end
    vacationBasic
    to set time,
    humidityAdvanced
    for all other
    settings
    Scroll
    up & down
    Fan Button
    Display Screen
    (LCD)
    Right-Side
    Button
    Heat Button
    Cool Button
    Temperature
    (+/-) Button
    System
    On/Off Button
    Basic & Advanced
    Setup Buttons
    Flip Down
    Door
    Left-Side
    Button
    Humidity/OAT
    Button
    Hold
    Button Time (+/-)
    Button
    Schedule & Vacation
    Program Buttons
    Up/Down
    Scroll Buttons
    A
    B
    C
    D
    A
    B
    C
    D
    User Interface
    Green
    Yellow
    White
    Red
    OAT
    Optional Remote
    Room Sensor
    HUM
    COM
    24VHumidifier
    ConnectionS2
    S1
    A
    B
    C
    D
    ABCD
    Connections
    2-Spd. AC or HP
    Green
    Yellow
    White
    Red
    OAT
    Sensor
    (Optional)
    Variable-Speed
    Furnace/ Fan Coil
    Fig. 12—Universal Four-Wire Connection DiagramA03146
    4 
    						
    							FIRE OR EQUIPMENT HAZARD
    Failure to follow this warning could result in equipment
    damage or fire.
    Do not apply 24vac fan powered humidifier (with internal
    power supply) direct to indoor unit HUM and COM termi-
    nals.
    INITIAL POWER-UP
    NOTE:Refer to Functional Overview (Fig. 11) to become
    familiar with key function buttons such as″System On/Off″,
    ″Fan″,″Left-Side″and″Right-Side″buttons, etc. These function
    buttons will be used frequently during setup.
    SECTION 1—POWER UP SEQUENCE
    This section addresses initial power up (or commissioning) of a
    new Infinity Control™. The User Interface will communicate and
    identify all Infinity components in the system. The following is atypical example for a communicating Variable-Speed Furnace /
    Fan Coil with a 2-spd. Air Conditioner / Heat Pump (including
    Dual Fuel).
    The User Interface display will light up and indicate that it is now
    ″ESTABLISHING COMMUNICATIONS WITH EQUIPMENT
    PLEASE WAIT″. The User Interface will automatically continue
    by″SEARCHING FOR INDOOR EQUIPMENT″, followed by
    ″SEARCHING FOR OUTDOOR EQUIPMENT″(See Figure 15).
    Once the indoor and outdoor equipment has been found, the
    Installer will be asked to select Accessories. Proceed to Section 4.
    Selecting Accessories.
    NOTE:If the variable-speed indoor equipment (furnace or fan
    coil) cannot be found, the User Interface will display″CANNOT
    COMMUNICATE WITH INDOOR UNIT″. ThisMUSTbe
    corrected before the initial power up sequence can continue. If
    indoor unit is found, but the outdoor unit is not found,″OUT-
    DOOR UNIT NOT IDENTIFIED″will appear. Proceed to the next
    section for Outdoor Unit Identification.
    SECTION 2—SELECTING OUTDOOR UNIT
    If there is no communicating outdoor unit, the screen, shown in
    Fig. 16, will appear. Press either Time or Temp +/- buttons to
    select AC (air conditioner), HP (heat pump), or None (no unit
    installed). Press the right-side button to continue to the next screen.
    If you have selected either AC or HP as the outdoor unit type, the
    following middle screen will appear (See figure 16). Press either
    Time or Temp +/- buttons to select appropriate Btu size of outdoor
    unit, then press right side button to continue. If a NIM (Network
    Interface Module) is applied for non-communicating two-speed
    outdoor equipment, select 1 or 2speed compressor operation , and
    press right-side button to continue.
    NOTE:Range of Btu selection is limited by the model number of
    the indoor unit installed. The Infinity Control™will not allow an
    outdoor unit size that is not supported by the installed indoor unit.
    NOTE:On new system installations, the model and serial number
    will be recognized and displayed. On any indoor/outdoor board
    replacements, the equipment will be recognized but the exact
    model/serial number will not be displayed.
    SECTION 3—SELECTING ELECTRIC HEATER
    If the indoor unit is a fan coil and the electric heater is not
    self-identifying,″ELECTRIC HEATER NOT IDENTIFIED″will
    appear (See figure 17). Press either Time or Temp +/- buttons to
    select appropriate size of electric heater installed, then press the
    right-side button to continue.
    A
    B
    C
    D
    A
    B
    C
    D
    C
    Y
    ABCD
    Connection
    User Interface
    1-Spd. AC
    Green
    Yellow
    White
    Red
    Optional Remote
    Room Sensor
    HUM
    COM
    24VHumidifier
    Connection
       Y/Y2
    S2
    S1
    OATOAT
    Sensor
    Variable-Speed
    Furnace/Fan Coil
    Fig. 13—Connection Diagram for
    Furnace or FE Fan Coil w/1-Spd. AC
    A03147
    A
    B
    C
    D
    A
    B
    C
    D
    ABCD
    Connection
    User Interface
    1-Spd. HP
    Green
    Yellow
    White
    Red
    Optional Remote
    Room Sensor
    HUM
    CHumidifier
    Connection
       Y
    S2
    S1
    W2
     YOC
    RO R
    W
    OAT
    OAT
    Sensor
    Variable-Speed
    Fan Coil
    Fig. 14—Connection Diagram for
    FE Fan Coil w/1-Spd. HP
    A03148
    Fig. 15—Power Up Sequence
    A03195
       ESTABLISHING
    COMMUNICATIONS
              WITH EQUIPMENT 
      PLEASE WAIT
     SOFTWARE
    VERSIONINDOOR UNIT
    SEARCHING FOR
    INDOOR EQUIPMENT
    WORKING
    OUTDOOR UNIT
    SEARCHING FOR
    OUTDOOR EQUIPMENT
    WORKING
    Fig. 16—Selecting Outdoor Unit
    A03196
    OUTDOOR UNIT
    NOT IDENTIFIED
     SELECT TYPE:       NONE
     NONE, AC, HP
    PRESS +/- TO MAKE
    SELECTION
               CONTINUEOUTDOOR UNIT
    ENTER HEAT PUMP
    SIZE               36000 BTU
    18000 TO 60000 BTU
    PRESS +/- TO MAKE
    SELECTION
       BACK          CONTINUEOUTDOOR UNIT
    HEAT PUMP
    ENTER NUMBER OF
    SPEEDS, 1 or 2:              1
    PRESS +/- TO MAKE
    SELECTION
       BACK          CONTINUE
    5 
    						
    							NOTE:Range of electric heaters available is limited by the model
    of the fan coil installed. The Infinity Control™will not allow an
    electric heater size that is not supported by the installed fan coil.
    SECTION 4—SELECTING ACCESSORIES
    Once the indoor and outdoor equipment have been found or
    entered, the following screens will appear allowing the Installer to
    select the AIR FILTER TYPE; HUMIDIFIER INSTALLED; and
    UV LIGHTS INSTALLED″(See Fig. 18). Use either Time or
    Temp +/- buttons to make the appropriate selections in the
    highlighted area on the display screen. Press right-side button to
    continue (or advance) to the next screen.
    AIR FILTER TYPE—This accessory screen will appear first.
    The installer will need to enter the type of filter (MEDIA, EAC, or
    both). See Table 1 and make a selection using Time or Temp +/-
    button, then press right-side button to continue.
    HUMIDIFIER TYPE—This will appear after the Air Filter
    Type screen. Select whether a humidifier is installed on the
    system, YES or NO, then press the right-side button to continue.
    UV LIGHTS INSTALLED—This screen will appear to select
    whether UV lights are installed on the system, select YES or NO,
    then press the right side button to continue.
    SECTION 5—EQUIPMENT SUMMARY
    The″EQUIPMENT SUMMARY″screen will appear after Ac-
    cessories have been selected. This screen will give a summary of
    all equipment automatically found or manually selected. If a wrong
    selection was made, press left-side button (BACK selection) to go
    back to that particular screen and make changes. When everything
    is OK, press right-side button again to continue. (See figure 19)
    The″SETUP COMPLETE! SAVE ALL SELECTIONS?″
    screen will appear after Equipment Summary. To Save All
    Selections press (YES) right-side button. Pressing the left-side
    button (NO selection) will return to the Equipment Summary
    screen where you can back up to any of the equipment selectionscreens and perform changes. After selecting YES, the initial
    power up sequence of the new Infinity Control™is complete. The
    User Interface screen will now display normal operating mode.
    Also, after selecting YES, if the filter type isnotan EAC, the
    indoor unit will operate the blower for one minute to do a system
    static pressure check.
    QUICK START
    For first time installers, Quick Start will allow you to start up the
    Infinity System before you have the chance to learn all the details
    of system operation. However, for the best possible comfort and
    operation we recommend that you refer to the Infinity Control™
    Homeowner’s Guide.
    SET DAY, TIME & DESIRED HUMIDITY
    1. Flip down the door at the base of the Infinity Control™and
    press theBASICbutton.
    2. Adjust the highlightedHOURsetting using theTIME (+/)
    button.
    3. PressSCROLLbutton (down) to highlightMINUTE.
    4. Adjust theMINUTEsetting using theTIME (+/)button.
    5. PressSCROLLbutton (down) to highlightDAY.
    6. Adjust the currentDAYsetting using theTIME (+/)button.
    7. PressSCROLLbutton (down) to highlightHUMIDITY.
    8. Press the redHEATbutton to select heating humidity.
    9. Adjust desired heating humidity level using either(+/)
    button.
    10. Press the blueCOOLbutton to select cooling humidity.
    11. Adjust the desired cooling humidity level using
    either(+/)button.
    12. To exit pressBASICbutton or close door.
    OVERRIDE HEATING SCHEDULE
    1. Press the redHEATbutton. Heating mode is confirmed when
    the red LED next to the redHEATbutton is lit.
    2. Use theTEMP(+/) button to select your desired heating
    temperature.
    3. The default time for temporarily overriding the temperature
    schedule is 2:00 HRS as indicated by the text on the lower left.
    NOTE:Override time will not appear if programming has been
    turned off.
    4. You can change the temporarily override time in 15-minute
    increments by pressing theTIME(+/) button until the
    desired override time is selected, or press theHOLDbutton
    anytime to override the schedule indefinitely.
    OVERRIDE COOLING SCHEDULE
    1. Press the blueCOOLbutton. Cooling mode is confirmed
    when the blue LED next to theCOOLbutton is lit.
    2. Use theTEMP(+/) button to select your desired cooling
    temperature.
    3. The default time for temporarily overriding the temperature
    schedule is 2:00 HRS as indicated by the text on the lower left.
    Fig. 17—Selecting Electric Heater
    A03197
    ELECTRIC HEATER
    NOT IDENTIFIED
     ENTER SIZE:            5 KW
     NONE, 5,10,15 KW
    PRESS +/- TO MAKE
    SELECTION
      BACK           CONTINUE
    INSTALLED FILTER MENU SELECTION
    1 Inch to 4 inch mediaMEDIA
    High voltage EACEAC
    High voltage EAC+1to4inch mediaMEDIA + EAC
    Table 1—Filter Selection
    Fig. 18—Accessories—UV Lights
    A03198
    ACCESSORIES
    HUMIDIFIER
    INSTALLED?              YES
    PRESS +/- TO MAKE
    SELECTION
       BACK          CONTINUEACCESSORIES
    U.V. LIGHTS
    INSTALLED?              YES
    PRESS +/- TO MAKE
    SELECTION
       BACK          CONTINUEACCESSORIES
    AIR FILTER TYPE: 
    EACEAC
    MEDIA
    MEDIA + EAC
    PRESS +/- TO MAKE
    SELECTION
                          CONTINUE
    AIR FILTER MEDIA TYPE HUMIDIFIER INSTALLED? U.V. LIGHTS INSTALLED?
    Fig. 19—Equipment Summary
    A03199
    EQUIPMENT SUMMARY
    FURNACE   58MVP0100-12
    AC                 38TDB036300
    FILTER                          EAC
    HUMIDIFIER                  YES
    UV LIGHTS                    YES
       BACK                     EXIT
    SETUP
    COMPLETE!
    SAVE
    ALL SELECTIONS?
       NO                           YES
    6 
    						
    							NOTE:Override time will not appear if programming has been
    turned off.
    4. You can change the temporary override time in 15-minute
    increments by pressing theTIME(+/) button until the
    desired override time is selected, or press theHOLDbutton
    anytime to override the schedule indefinitely.
    QUICK PROGRAM SCHEDULE FOR ALL DAYS
    This section will give you a quick program schedule forAll Days
    of the week. For more information on how to create customized
    schedules for every day, the entire week, or weekend, refer to the
    Homeowner’s Guide.
    1. Flip down the door at the bottom of the control.
    2. Press theSCHEDULEbutton, which allows you to create one
    schedule for the entire home.
    3. Press either theLEFTorRIGHTside button repeatedly (if
    necessary) until″ALLDAYS″is displayed. TheWAKEtime
    period will be highlighted.
    4. Using theTIME (+/)button, set the start time for this time
    period.
    5. Press the redHEATbutton. Heating temperature will begin
    flashing.
    6. Set the heating temperature using theTEMP (+/)button.
    7. Press the blueCOOLbutton. Cooling temperature will begin
    flashing.
    8. Set the cooling temperature using theTEMP (+/)button.
    9. Set the remaining periods by using theSCROLLbutton to
    select″DAY,″″EVENING,″and″SLEEP″.
    10. Exit the scheduling mode by either closing the door or
    pressing theSCHEDULEbutton.
    11. If changes are made, you will be asked to″SAVE CHANGES
    YES/NO″INSTALL / SERVICE MENUS
    The″INSTALL / SERVICE″menus contain a set of vital
    information. This information enables the Installer or Service
    person to view a summary of what has been installed, etc.
    To enterINSTALL / SERVICEmenus, press and hold the
    ADVANCEDbutton for at least ten seconds. The following menu
    will appear (See figure 20):
    NOTE:TheINSTALL / SERVICEmenu will automatically exit
    after 60 minutes of no push button activity.
    EQUIPMENT SUMMARY:Shows all equipment recognized by
    and attached to the system.
    INSTALL:Used when adding, changing out, or uninstalling
    equipment.
    SETUP:Used to view or modify equipment settings.
    CHECKOUT:Allows testing of equipment operation
    SERVICE:Used to view operation and fault history of equipment
    and enter dealer name/phone number for display.
    EQUIPMENT SUMMARY MENU
    An example screen is shown in Fig. 21:
    This screen shows indoor unit type and model number, outdoor
    unit type (and model number if a 2-speed unit), filter type, any
    accessories that are installed.
    INSTALL MENU
    This menu item will perform start-up process in order to learn all
    equipment in system. Press right side button to initiate the process.
    Fig. 20—INSTALL / SERVICE MENUS
    A03200
    INSTALL/SERVICE
    EQUIPMENT SUMMARY
    INSTALL
    SETUP
    CHECKOUT
    SERVICE
    SOFTWARE VERSION 1
      EXIT                 SELECT
    Fig. 21—EQUIPMENT SUMMARY
    A03201
    EQUIPMENT SUMMARY
    FURNACE   58MVP0100-12
    AC                 38TDB036300
    FILTER                          EAC
    HUMIDIFIER                  YES
    UV LIGHTS                    YES
       BACK
    Fig. 22—INSTALL
    A03202
    INSTALL
    TO ADD, UNINSTALL OR
    RE-INSTALL EQUIPMENT,
    PRESS RIGHT SIDE
    BUTTON
       BACK               INSTALL
    7 
    						
    							SETUP MENU
    This menu has several layers, allowing modification of equipment
    settings. No settings will need to be made at equipment (i.e.dip
    switches on a furnace). All configuration settings are made
    effective from this menu. Fig. 23 shows all the information that
    can be found in theSETUPmenu.
    SETUP = THERMOSTAT:
    AUTO MODE SETUP:
    Enable/Disable Auto Changeover mode (default=Enable).
    Auto Changeover Time may be adjusted 5 to 120 minutes,
    (default = 30 minutes).
    When Auto mode is enabled (factory default) a change from heat
    to cool (or vice versa) will not occur until an opposite mode
    demand has existed for 30 minutes. If the set point is changed, the
    30 minute timer is deleted.
    HEAT/COOL DEADBAND:
    0 to 6 degrees, (default = 2°).
    A minimum difference of 2°is enforced between heating and
    cooling desired temperatures. This will allow one setting to″push″
    the other to maintain this difference.
    OFFSETS: This option allows calibration (or deliberate miscali-
    bration) of the temperature and humidity sensors. These offsets are
    added to the actual temperature/humidity values (defaults = 0).
    Room Temp Offset: -5 to +5 degrees.
    Outside Temp Offset: -5 to +5 degrees.
    Humidity Offset: -10 to +10 percent.
    CYCLES PER HOUR:
    Maximum cycles per hour = 4 (default) or 6.
    Anticipator=1to9(default=3).
    PROGRAMMING:
    On or Off (default=On)
    Periods Per Day=2or4(default=4)
    Programmable Fan On/Off (default=Off)
    SMART RECOVERY:
    On or Off, (default=On)
    Applies to programmable operationonly. Will start recovery 90
    minutes prior to schedule change in both heating and cooling.
    ENGLISH/METRIC DISPLAY:
    °For°C, (default =°F)
    RESET FACTORY DEFAULTS:
    Program Schedule:
    Yes/No to reset back to Energy Star defaults.
    User Settings:
    Yes/No to reset the user settings in the Advanced Setup.
    Install Settings:
    Yes/No to reset install settings in Install/Service menus.SETUP = FURNACE:
    Upon a first time start-up of the Infinity Control™, the furnace dip
    switch settings will be copied to the furnace setup menu. Any
    changes can then be made from the Infinity Control™.
    AIRFLOW:
    COMFORT (default)
    EFFICIENCY
    Selects the airflow of the furnace when heating.EFFICIENCYis
    the airflow used to meet specified ratings,COMFORTis a
    decreased airflow used to increase the output air temperature and
    provide increased comfort.
    AC AIRFLOW:
    COMFORT (default)
    EFFICIENCY
    MAXIMUM
    Selects the airflow of the furnace when cooling.COMFORTis a
    decreased airflow used to improve humidity control.EFFI-
    CIENCYis the airflow used to meet specified ratings.MAXI-
    MUMis a fixed airflow speed of 400 CFM/ton based on the
    outdoor unit size.
    DEHUM AIRFLOW:
    NORMAL (default)
    HIGH
    NORMALairflow adjustment is used during dehumidifying. If
    duct sweating is an issue, selectingHIGHwill increase the
    dehumidifying airflow speed and reduce the sweating.
    LOW HEAT RISE:
    ON
    OFF (default)
    Set this to ON if the system contains a bypass humidifier. The ON
    setting will increase the furnace low heat airflow.
    STAGING:
    SYSTEM (default)
    FURNACE
    LOW
    HIGH
    Controls the staging of the furnace.SYSTEMsetting will allow
    the Infinity Control™to determine furnace staging.FURNACE
    will allow the Furnace algorithm to control staging.LOWwill
    only run the low stage of furnace heat.HIGHwill only run the
    high stage of furnace heat.
    OFF DELAY:
    90 seconds (default)
    120 seconds
    150 seconds
    180 seconds
    Amount of time the blower will continue to run after heating has
    shut off.
    LOCKOUT TEMP:
    NONE (default)
    +5 to 55 deg F
    Appears ondual fuelsystems only (furnace with heat pump).
    Outside temperature above which the furnace will NOT run.
    Fig. 23—SETUP MENU
    A03203
    SETUP
    THERMOSTAT
    FURNACE
    HEAT PUMP
    ACCESSORIES
    SYSTEM MAINTENANCE
       BACK               SELECT
    8 
    						
    							SETUP = FAN COIL:
    HP/AC AIRFLOW:
    COMFORT (default)
    EFFICIENCY
    MAXIMUM
    Selects the airflow of the fan coil when heating or cooling with a
    heat pump (or cooling with an AC unit).COMFORTis a
    decreased airflow used to improve humidity control.EFFI-
    CIENCYis the airflow used to meet specified ratings.MAXI-
    MUMis a fixed airflow speed of 400 CFM/ton based on the
    outdoor unit size.
    DEHUM AIRFLOW:
    NORMAL (default)
    HIGH
    Normal airflow adjustment used during dehumidifying. If duct
    sweating is an issue, selectingHIGHwill increase the dehumidi-
    fying airflow speed and reduce the sweating.
    HEATER SIZE:
    (choices dependent upon fan coil model)
    This will show the heater size entered during the start-up process.
    This value can be changed to another value (limited by the model
    of the fan coil). If the electric heater is self-identifying, this value
    is not shown.
    SETUP = HEAT PUMP / AC:
    COOLING LOCKOUT:
    NONE (default)
    45°F.
    50°F.
    55°F.
    Outside temperature below which cooling will not be provided.
    ENTERED SIZE:
    (dependent on indoor unit model)
    Size of the outdoor unit entered during the start-up process. If the
    outdoor unit is a communicating model, this value will not be
    shown. This size can be changed here but is limited to sizes that the
    indoor unit can handle.
    DEFROST INTERVAL:
    30 minutes
    60 minutes
    90 minutes (default)
    120 minutes
    Time interval at which defrost cycles can occur on a heat pump.
    ELECT HEAT LOCKOUT:
    NONE (default)
    +5 to 55 deg. F
    Outside temperature above which the electric heat will not operate.
    HIGH COOL LATCH:
    NONE (default)
    80 - 110 deg F
    Outside temperature above which only the high speed (of a
    2-speed outdoor unit) will run when cooling.SETUP = ACCESSORIES
    FILTER TYPE:
    MEDIA
    EAC
    MEDIA+EAC
    CLEAN INTERVAL: 30 to 180 days (of blower operation).
    (Default = 90)
    Interval at which the Clean Filter notification will turn on. Applies
    to EAC or MEDIA+EAC filter selection only.
    SETUP = HUMIDIFIER
    HUMIDIFIER INSTALLED:
    NO
    YES
    If YES, indicates to the system whether a humidifier is installed
    and enables humidification functions.
    CHANGE PAD INTERVAL: 1 to 24 months of humidifier
    operation (default=6 months)
    Interval at which the Change Humidify Pad notification will be
    displayed.
    HUMIDIFY WITH FAN:
    NO (default)
    YES
    If YES, the humidifier will run with Continuous Fan if there is a
    humidify demand.
    SETUP = VENTILATOR
    NOTE:Only appears if ventilator is installed.
    CLEAN INTERVAL:
    60 to 180 days of operation (default=90)
    Interval at which the Clean Ventilator Pre-filter notification will
    turn on.
    SETUP = UV LIGHTS
    UV LIGHTS INSTALLED:
    NO
    YES
    If YES, indicates to the system whether UV lights are installed.
    CHANGE INTERVAL:
    6 to 48 months operation time (default=12 months)
    Interval at which the Change UV Lights notification will be
    displayed.
    SETUP = SYSTEM MAINTENANCE
    REMIND OWNER OF ROUTINE MAINTENANCE EVERY:
    This setup is used to adjust the timer interval in which the normal
    System Maintenance notification is turned on for the homeowner.
    Range= OFF, 6 to 24 months, (default=12)
    9 
    						
    							CHECKOUT MENUS
    The Checkout menu will show the equipment installed in the
    system. A sample checkout menu is shown in Fig. 24.
    Checkout = FURNACE
    Make sure the furnace is properly installed before continuing.
    LOW HEAT RUNTIME: 5 min.
    HIGH HEAT RUNTIME: 5 min.
    This menu item allows the furnace to be exercised. First, a low
    heat runtime and high heat runtime are selected.
    If only the low heat is to be exercised:
    The furnace will execute its ignition start-up sequence. This
    sequence will be displayed on the Infinity Control screen. After the
    gas valve and blower motor turn on, the screen will automatically
    change to show the current operating status of the furnace.
    Checkout = FAN COIL
    ELECTRIC HEAT CHECK
    ELECTRIC HEAT RUNTIME: 5 min., Default time = 5 min.,
    Range=0-120min.
    If you have a fan coil with electric heaters, this menu item will
    allow the heaters to be exercised.
    With self-identifying electric heaters, three stages of electric heat
    are available to be exercised in any combination. Non-identifying
    heaters will only provide one stage of heat.
    Enter the run time (in minutes) of each stage of heat to be
    exercised then press START (right-side button). The display will
    change to show the fan coil’s operating status.
    Checkout = HEAT PUMP HEATING
    HIGH HEAT RUNTIME: 5 min.
    LOW HEAT RUNTIME: 5 min.
    DEFROST: NO
    The heat pump heating mode can be exercised with this menu
    option. With a 2-speed heat pump, a low heat runtime and a high
    heat runtime are independently selectable to exercise. A defrost
    cycle is also selectable. Default time = Fixed 5 min. minimum,
    range=5-120min.
    Checkout = HEAT PUMP COOLING OR AC COOLING
    HIGH COOL RUNTIME: 5 min.
    LOW COOL RUNTIME: 5 min.
    The heat pump cooling mode (or AC cooling mode) can be
    exercised with this menu option. With a 2-speed heat pump or AC
    unit, a low cool runtime and a high cool runtime are independently
    selectable to exercise. The display will change to show the heat
    pump or AC operating status. Default time = Fixed 5 min.
    minimum, range=5-120min.Checkout = HUMIDIFIER
    ON
    OFF
    The humidifier can be exercised On and Off with this menu option.
    Checkout = VENTILATOR
    The ventilator can be exercised through all of its operating speeds
    with this menu option.
    SERVICE MENUS
    The Service Info menu will only show the equipment installed in
    the system. Below is a sample using a furnace and a dual fuel heat
    pump. A sample service menu is shown in Fig. 25.
    Service = FURNACE STATUS
    The Status screens will show all of the current operating param-
    eters of each installed piece of equipment.
    HEAT STAGE:OFF, LOW, HIGH
    Displays stage of heat that the furnace is currently delivering.
    AIRFLOW CFM:
    (furnace model dependent)
    Cubic Feet per Minute of air the blower is currently delivering.
    INDUCER RPM (90% furnaces only):
    Inducer motor RPM value.
    BLOWER RPM:
    Blower motor RPM value.
    STATIC PRESS:
    Inches of water. Displays static pressure that the furnace is
    currently experiencing.
    LOCKOUT TIMER:
    Seconds
    If a lockout timer is active, this will show the current time value.
    See furnace manual for details on lockout timers.
    Service = FAN COIL
    ELECTRIC HEAT STATUS:
    OFF, LOW, MED, HIGH
    Displays stages of electric heat that the fan coil is currently
    delivering.
    AIRFLOW CFM:
    (fan coil model dependent)
    Cubic Feet per Minute of air the blower is currently delivering.
    BLOWER RPM:
    Blower motor RPM value
    STATIC PRESS:
    Inches of water
    Displays static pressure that the fan coil is currently experiencing.
    Fig. 24—CHECKOUT MENUS
    A03204
    CHECKOUT
    FURNACE
    HEAT PUMP HEATING
    HEAT PUMP COOLING
    HUMIDIFIER
    VENTILATOR
       BACK               SELECT
    Fig. 25—SERVICE INFO MENUS
    A03205
    SERVICE INFO
    FURNACE STATUS
    HEAT PUMP STATUS
    LAST 10 SYSTEM FAULTS
    RUN/FAULT HISTORY
    TODAY’S DATE
    MODEL/SERIAL NUMBER
    SERVICE PHONE NUMBER
       BACK               SELECT
    10 
    						
    All Carrier manuals Comments (0)

    Related Manuals for Carrier Systxccuid01 B Manual