    Table5--40QNC,QNQFanCoilElectricalData 
    UNITSIZE V-PH-Hz VOLTAGERANGE* 
    MinMax FLA FAN 
    MotorPower 
    (Watts) MCA MINWIRE 
    SIZE  POWER 
    MOCP 
    15 
    15 
    15 
    15 
    15 
    15 
    15  40QNC01824208/230-1-601872530.38640.4814 
    40QNC030208/230-1-601872530.38740.4814 
    40QNC036208/230-1-601872530.44740.5514 
    40QNQ018208/230-1-601872530.38640.4814 
    40QNQ024208/230-1-601872530.38640.4814 
    40ONO030208/230-1-601872530.38740.4814 
    40QNQ036208/230-1-601872530.44740.5514 
    LEGEND 
    FLA--FullLoadAmps 
    MOA--MinimumCircuitAmpsperNECSection430-24 
    MOCP--MaximumOvercurrentProtection 
    NEC--NationalElectricalCode 
    RLA--RatedLoadAmps(Compressor) 
    *Permissiblelimitsofthevoltagerangeatwhichunitwilloperate 
    satisfactorily. NOTES: 
    1.IncompliancewithNECrequirementsformultimotorandcombi- 
    nationloadequipment(refertoNECArticles430and440),the 
    overcurrentprotectivedevicefortheunitshallbefuseor 
    equippedwithabreaker. 
    2.MotorRLAvaluesareestablishedinaccordancewithUL(Under- 
    writersLaboratories)Standard465. 
    START-UP 
    PreliminaryChecks 
    1.Checkthatallinternalwiringconnectionsaretightand 
    thatallban-iers,covers,andpanelsareinplace. 
    2.Fieldelectricalpowersourcemustameewithunitname- 
    platerating. 
    3.Allservicevanesmustbeopen. 
    4.Crankcaseheatermustbetightoncompressorcrmlkcase 
    (ifequipped). 
    LeakTest--Fieldpipingandtancoilmustbeleaktested 
    bypressuremetllod.UseR-410Aatapproxilnately25psig 
    backedupwithaninertgastoatotalpressurenottoexceed 
    245psig. 
    NOTE:LeakdetectorsshouldbedesiNledtodetectHFC 
    (hydrottuorocarbon)refrigerant. 
    EvacuateandDehydrate--Fieldpipingandfancoil 
    mustbeevacuatedanddehydratedt\_ltowinggoodretiigera- 
    tionpractices. 
    StartUnitwithOperatingTest--Turnpoweronto 
    theunit.Insertbatteriesinrelnotecontrol.PresstheAand 
    the_buttonsontherelnotecontroltbr5seconds.The 
    relnotecontrolwillbeclearedandthetimesemnentwiltdis- 
    playtheSrc1servicetestmode. 
    Pressthe=_buttontotranslnittheservicetestsiNmltothe 
    unit.Afterthetesthascompletedpressthe(!)buttontoleave 
    thetestmenu. 
    NOTE:When30secoMshaveelapsedandnobuttonshave 
    beenpressed,therelnotecontrolwillautomaticallyexitthetest 
    menuandresumeitsnorlnaloperation. ConfiguringTwoIndoorUnitRemoteCon- 
    trois--Ittwoindoorunitsarebeinginstalledinthesame 
    room,workingindependently,tworelnotecontrolsneedtobe 
    configuredforproperoperation. 
    UNITCONFIGURATION6Turntheunitoffbypressing 
    the_.PressandholdtheN_and_buttonsofthere- 
    motecontrolformorethan5seconds.Thedisplaywillbe 
    clearedandthetimesemnentswiltdisplaythefirstconfimlra- 
    tionitem(rAdrrelnoteaddress)andthetemperaturesemnents 
    willdisplaythedefaultvalueofthisconfigurationitem 
    (Abcontrolofbothindoorunits).Press_andVto 
    changethedefaultvaluetothenewvalueof(a)or(b).Pressthe 
    L_buttontotransmitthenewconfigurationtotheunit.Press 
    the(!)buttontoleavetheconfigurationmenu. 
    REMOTECONTROLCONFIGURATION6Turntheunit 
    offbypressingthe(1)button.PressaaldholdtheVand 
    _buttonsformorethan5seconds.Thedisplaywillbe 
    clearedandthetimesegnnentswilldisplaythefirstconfigura- 
    tionitem(CHrelnoteaddress)andthetemperaturesemnents 
    wiltdisplaythedefaultvalueofthisconfigurationitem 
    (Abcontrolofbothindoorunits).PressAandVto 
    &angethedefaultvaluetothenewvalueof(a)or(b).Pressthe 
    _buttontotransmitthenewconfi_rationtotheunit. 
    Pressthe0!)buttontoleavetheconfigurationmenu. 
    NOTE:When30secondshaveelapsedandnobuttonshave 
    beenpressed,theremotecontrolwillautomaticallyexitthe 
    configurationmenuandres_ulneitsnorlnaloperation. 
    13  
    						
    							  
    SERVICE 
    Betbrepertbnningrecomlnendedmaintenance,besure 
    unitmainpowerswitchisturnedoffFailuretodosomay 
    resultinelectricalshockorinjurytbnnrotatingfanblade. 
    PumpdownProcedure--Thesystemmaybepmnped 
    downinordertomakerepairsonthelowsidewithoutlosing 
    completeretiigerantcharge. 
    1.Attachpressuregagetosuctionservicevalvegageport. 
    2.Frontseatthemixedphaselinevalve. 
    Theunitcoilsholdonlythefactory-desiNlatedamountof 
    refrigerant.Additionalrefrigerantmaycauseunitsto 
    relievepressuretbaoughthecompressorinternalpressure 
    reliefvalve(indicatedbyasuddenriseofsuctionpressure) 
    beforesuctionpressurereaches20psig.Ifthisoccurs,shut 
    offunitimmediatelythenfiontseatthesuctionvalveand 
    removeandrecoverexcessretiigerantfotbwingaccepted 
    practices.Equipmentdamagemayresult. 
    3.Startunitandrununtilsuctionpressurereaches5psig. 
    4.Shutunitoffandfiontseatsuctionvalve. 
    5.Depressurizelowsideofunitandrecoverretiigerant 
    followingacceptedpractices. 
    FilterDrier--Wheneverthefilterdrierisexposedtotheat- 
    ruosphereitmustbereplaced.Onlyusefactoryspecifiedliquid- 
    linefilterdrierswithratedworkingpressureofatleast600psig 
    or1Ylore. NOTE:Donotinstallasuction-linefilterdrierinthemixed 
    phaseline. 
    RefrigerantCharging 
    Topreventpersonalinjury,wearsafetyglassesandgloves 
    whenhandlingreti-igerant.Donotoverchargesystemd 
    thiscancausecompressorflooding. 
    NOTE:Donotventordepressurizeunitretiigeranttoatmo- 
    sphere.Relnoveandrecoverrefiigerantfollowingaccepted 
    practices. 
    TROUBLESHOOTING 
    SeeTables6and7fortroubleshootingintbnnation. 
    FaultCode--Onceafailureoccurswiththeindoorunitin 
    operation,thegreenLEDontheindoorunitflashesatintervals 
    of0.5seconds.Thefauhcodeisdeducedfiolnthenumberof 
    timesthe_eenLEDflashes,blockingunitoperation.Between 
    oneflashcycleandthenextone,apauseof3secoMselapses. 
    Table6--GreenLED(IndoorUnitFault) 
    CODEDESCRIPTION 
    3RoomAirSensorFault 
    4IndoorUnitCoilSensorFault 
    14OutdoorUnitAirSensorFault 
    14  
    						
    							  
    Table7--Troubleshooting 
    PROBLEM 
    CompressorandFanoftheOutdoor 
    UnitWillNotStart 
    CompressorWillNotStart,But 
    OutdoorFanisOperating 
    CompressorStopsDueto 
    Overtemperature 
    CompressorRunsContinuously POSSIBLECAUSE 
    Unitnotenergized 
    MainswitchissettoOFF 
    Mainswitchfusesareblown 
    Compressorcyclingprotectionison 
    Mainpowervoltageistoolow 
    Electricalconnectionsaretoolooseorare 
    wrong 
    Electricalconnectionsofcompressorareloose 
    orwrong 
    Compressorburntout;seizedorprotection 
    deviceon 
    Wrongrefrigerantchargeinunit(excessiveor 
    low)orairorothernoncondensablegassesin 
    thecircuit 
    Mainvoltageistoohighortoolow 
    Condensercoilobstructed 
    Outdoorfanoff 
    Wrongindoorunitthermistors 
    Refrigerantcircuitclogged 
    Reversingvalvefaultyonheatpumpmodels 
    Expansiondevicecloggedorcoveredwithice 
    Unitselectedistoosmallforapplication 
    requirements 
    Indoortemperaturesettingtoolowortoohigh 
    Outdoorunitfanfaulty 
    Airorothernoncondensablegassesinthe 
    circuit 
    Obstructionsatairintakeordirtyindoorunit 
    filters 
    Outdoorfanisstopped SOLUTION 
    Checkthemainpowerconnection. 
    CheckandputittoONposition. 
    Replacefuses. 
    Waitfor3minutes. 
    Checkandsettothecorrectvoltage. 
    Checkandtightenorcorrectconnections. 
    Checkandtightenorrepaircompressor. 
    Checkforthecauseandreplacecompressorif 
    necessary. 
    Drainrefrigerant,evacuateandrecharge. 
    CAUTION:Donotventrefrigeranttotheatmosphere; 
    userefrigerantrecoveryequipment. 
    Checkvoltagesettingandadjustifnecessary. 
    Removeobstruction. 
    Checkcauseandresumeoperationorrepair. 
    Replacethermistors. 
    Checkandremoveobstructions. 
    Replacereversingvalve. 
    Drainrefrigerant,evacuateandrecharge. 
    CAUTION:Donotventrefrigeranttotheatmosphere; 
    userefrigerantrecoveryequipment. 
    Contactaqualifiedservicetechnicianforasystem 
    evaluation. 
    Checktemperaturesetting. 
    Replaceoutdoorfan. 
    Drainrefrigerant,evacuateandrecharge. 
    CAUTION:Donotventrefrigeranttotheatmosphere; 
    userefrigerantrecoveryequipment. 
    Removeobstructionand/orcleanfilter. 
    FrequentIce-Build-UponOutdoorCheckcauseandrepair. 
    Coil 
    DischargePressureTooHigh Outdoorcoildirtyorobstructed 
    Condenserfanfaulty 
    Indoortemperaturesettingtoolowortoohigh 
    Airorothernoncondensablegassesinthe 
    circuit 
    Indoortemperaturesettingtoohighortoolow 
    Outdoorcoildirtyorobstructed 
    Indoorunitairfilterdirty 
    Indoortemperaturesettingtoohighortoolow 
    Reversingvalvefaultyorinternalleak 
    Indoortemperaturesettingtoohighortoolow 
    Evaporatorcoilcoveredwithice 
    Expansiondeviceorsuctionlineclogged 
    Outdoorfandoesnotstopduringdefrost 
    _eriods 
    Electricalconnectionloose 
    Fanmotorburnout 
    Fanbearingseized 
    Expansiondevicecloggedorcoveredwithice  DischargePressureTooLow 
    SuctionPressureTooHigh 
    SuctionPressureTooLow 
    OutdoorFanCyclingDueto 
    Over-TemperatureProtection Cleanorremoveobstructions. 
    Replacecondenserfan. 
    Checktemperaturesetting. 
    Drainrefrigerant,evacuateandrecharge. 
    CAUTION:Donotventrefrigeranttotheatmosphere; 
    userefrigerantrecoveryequipment. 
    Checktemperaturesetting. 
    Cleanorremoveobstructions. 
    Cleanfilter. 
    Checktemperaturesetting. 
    Replacereversingvalve. 
    Checktemperaturesetting. 
    Aircirculationontheevaporatornotsufficient;check 
    andrepair. 
    Checkandrepair. 
    Checkelectricalparts. 
    Checkconnections. 
    Replace. 
    Checkandrepair. 
    Drainrefrigerant,evacuateandreplace. 
    CAUTION:Donotventrefrigeranttotheatmosphere; 
    userefrigerantrecoveryequipment. 
    ]5  
    						
    							  
    Copyright2006CarrierCorporation 
    Manufacturerreservestherighttodiscontinue,orchangeatanytime,specificationsordesignswithoutnoticeandwithoutincurringobligations. 
    CatalogNo.02-40QN0001-SIPrintedinU.S.A.Form40QN-8SIPg163-06Replaces:New  
    						