Table5--40QNC,QNQFanCoilElectricalData UNITSIZE V-PH-Hz VOLTAGERANGE* MinMax FLA FAN MotorPower (Watts) MCA MINWIRE SIZE POWER MOCP 15 15 15 15 15 15 15 40QNC01824208/230-1-601872530.38640.4814 40QNC030208/230-1-601872530.38740.4814 40QNC036208/230-1-601872530.44740.5514 40QNQ018208/230-1-601872530.38640.4814 40QNQ024208/230-1-601872530.38640.4814 40ONO030208/230-1-601872530.38740.4814 40QNQ036208/230-1-601872530.44740.5514 LEGEND FLA--FullLoadAmps MOA--MinimumCircuitAmpsperNECSection430-24 MOCP--MaximumOvercurrentProtection NEC--NationalElectricalCode RLA--RatedLoadAmps(Compressor) *Permissiblelimitsofthevoltagerangeatwhichunitwilloperate satisfactorily. NOTES: 1.IncompliancewithNECrequirementsformultimotorandcombi- nationloadequipment(refertoNECArticles430and440),the overcurrentprotectivedevicefortheunitshallbefuseor equippedwithabreaker. 2.MotorRLAvaluesareestablishedinaccordancewithUL(Under- writersLaboratories)Standard465. START-UP PreliminaryChecks 1.Checkthatallinternalwiringconnectionsaretightand thatallban-iers,covers,andpanelsareinplace. 2.Fieldelectricalpowersourcemustameewithunitname- platerating. 3.Allservicevanesmustbeopen. 4.Crankcaseheatermustbetightoncompressorcrmlkcase (ifequipped). LeakTest--Fieldpipingandtancoilmustbeleaktested bypressuremetllod.UseR-410Aatapproxilnately25psig backedupwithaninertgastoatotalpressurenottoexceed 245psig. NOTE:LeakdetectorsshouldbedesiNledtodetectHFC (hydrottuorocarbon)refrigerant. EvacuateandDehydrate--Fieldpipingandfancoil mustbeevacuatedanddehydratedt\_ltowinggoodretiigera- tionpractices. StartUnitwithOperatingTest--Turnpoweronto theunit.Insertbatteriesinrelnotecontrol.PresstheAand the_buttonsontherelnotecontroltbr5seconds.The relnotecontrolwillbeclearedandthetimesemnentwiltdis- playtheSrc1servicetestmode. Pressthe=_buttontotranslnittheservicetestsiNmltothe unit.Afterthetesthascompletedpressthe(!)buttontoleave thetestmenu. NOTE:When30secoMshaveelapsedandnobuttonshave beenpressed,therelnotecontrolwillautomaticallyexitthetest menuandresumeitsnorlnaloperation. ConfiguringTwoIndoorUnitRemoteCon- trois--Ittwoindoorunitsarebeinginstalledinthesame room,workingindependently,tworelnotecontrolsneedtobe configuredforproperoperation. UNITCONFIGURATION6Turntheunitoffbypressing the_.PressandholdtheN_and_buttonsofthere- motecontrolformorethan5seconds.Thedisplaywillbe clearedandthetimesemnentswiltdisplaythefirstconfimlra- tionitem(rAdrrelnoteaddress)andthetemperaturesemnents willdisplaythedefaultvalueofthisconfigurationitem (Abcontrolofbothindoorunits).Press_andVto changethedefaultvaluetothenewvalueof(a)or(b).Pressthe L_buttontotransmitthenewconfigurationtotheunit.Press the(!)buttontoleavetheconfigurationmenu. REMOTECONTROLCONFIGURATION6Turntheunit offbypressingthe(1)button.PressaaldholdtheVand _buttonsformorethan5seconds.Thedisplaywillbe clearedandthetimesegnnentswilldisplaythefirstconfigura- tionitem(CHrelnoteaddress)andthetemperaturesemnents wiltdisplaythedefaultvalueofthisconfigurationitem (Abcontrolofbothindoorunits).PressAandVto &angethedefaultvaluetothenewvalueof(a)or(b).Pressthe _buttontotransmitthenewconfi_rationtotheunit. Pressthe0!)buttontoleavetheconfigurationmenu. NOTE:When30secondshaveelapsedandnobuttonshave beenpressed,theremotecontrolwillautomaticallyexitthe configurationmenuandres_ulneitsnorlnaloperation. 13
SERVICE Betbrepertbnningrecomlnendedmaintenance,besure unitmainpowerswitchisturnedoffFailuretodosomay resultinelectricalshockorinjurytbnnrotatingfanblade. PumpdownProcedure--Thesystemmaybepmnped downinordertomakerepairsonthelowsidewithoutlosing completeretiigerantcharge. 1.Attachpressuregagetosuctionservicevalvegageport. 2.Frontseatthemixedphaselinevalve. Theunitcoilsholdonlythefactory-desiNlatedamountof refrigerant.Additionalrefrigerantmaycauseunitsto relievepressuretbaoughthecompressorinternalpressure reliefvalve(indicatedbyasuddenriseofsuctionpressure) beforesuctionpressurereaches20psig.Ifthisoccurs,shut offunitimmediatelythenfiontseatthesuctionvalveand removeandrecoverexcessretiigerantfotbwingaccepted practices.Equipmentdamagemayresult. 3.Startunitandrununtilsuctionpressurereaches5psig. 4.Shutunitoffandfiontseatsuctionvalve. 5.Depressurizelowsideofunitandrecoverretiigerant followingacceptedpractices. FilterDrier--Wheneverthefilterdrierisexposedtotheat- ruosphereitmustbereplaced.Onlyusefactoryspecifiedliquid- linefilterdrierswithratedworkingpressureofatleast600psig or1Ylore. NOTE:Donotinstallasuction-linefilterdrierinthemixed phaseline. RefrigerantCharging Topreventpersonalinjury,wearsafetyglassesandgloves whenhandlingreti-igerant.Donotoverchargesystemd thiscancausecompressorflooding. NOTE:Donotventordepressurizeunitretiigeranttoatmo- sphere.Relnoveandrecoverrefiigerantfollowingaccepted practices. TROUBLESHOOTING SeeTables6and7fortroubleshootingintbnnation. FaultCode--Onceafailureoccurswiththeindoorunitin operation,thegreenLEDontheindoorunitflashesatintervals of0.5seconds.Thefauhcodeisdeducedfiolnthenumberof timesthe_eenLEDflashes,blockingunitoperation.Between oneflashcycleandthenextone,apauseof3secoMselapses. Table6--GreenLED(IndoorUnitFault) CODEDESCRIPTION 3RoomAirSensorFault 4IndoorUnitCoilSensorFault 14OutdoorUnitAirSensorFault 14
Table7--Troubleshooting PROBLEM CompressorandFanoftheOutdoor UnitWillNotStart CompressorWillNotStart,But OutdoorFanisOperating CompressorStopsDueto Overtemperature CompressorRunsContinuously POSSIBLECAUSE Unitnotenergized MainswitchissettoOFF Mainswitchfusesareblown Compressorcyclingprotectionison Mainpowervoltageistoolow Electricalconnectionsaretoolooseorare wrong Electricalconnectionsofcompressorareloose orwrong Compressorburntout;seizedorprotection deviceon Wrongrefrigerantchargeinunit(excessiveor low)orairorothernoncondensablegassesin thecircuit Mainvoltageistoohighortoolow Condensercoilobstructed Outdoorfanoff Wrongindoorunitthermistors Refrigerantcircuitclogged Reversingvalvefaultyonheatpumpmodels Expansiondevicecloggedorcoveredwithice Unitselectedistoosmallforapplication requirements Indoortemperaturesettingtoolowortoohigh Outdoorunitfanfaulty Airorothernoncondensablegassesinthe circuit Obstructionsatairintakeordirtyindoorunit filters Outdoorfanisstopped SOLUTION Checkthemainpowerconnection. CheckandputittoONposition. Replacefuses. Waitfor3minutes. Checkandsettothecorrectvoltage. Checkandtightenorcorrectconnections. Checkandtightenorrepaircompressor. Checkforthecauseandreplacecompressorif necessary. Drainrefrigerant,evacuateandrecharge. CAUTION:Donotventrefrigeranttotheatmosphere; userefrigerantrecoveryequipment. Checkvoltagesettingandadjustifnecessary. Removeobstruction. Checkcauseandresumeoperationorrepair. Replacethermistors. Checkandremoveobstructions. Replacereversingvalve. Drainrefrigerant,evacuateandrecharge. CAUTION:Donotventrefrigeranttotheatmosphere; userefrigerantrecoveryequipment. Contactaqualifiedservicetechnicianforasystem evaluation. Checktemperaturesetting. Replaceoutdoorfan. Drainrefrigerant,evacuateandrecharge. CAUTION:Donotventrefrigeranttotheatmosphere; userefrigerantrecoveryequipment. Removeobstructionand/orcleanfilter. FrequentIce-Build-UponOutdoorCheckcauseandrepair. Coil DischargePressureTooHigh Outdoorcoildirtyorobstructed Condenserfanfaulty Indoortemperaturesettingtoolowortoohigh Airorothernoncondensablegassesinthe circuit Indoortemperaturesettingtoohighortoolow Outdoorcoildirtyorobstructed Indoorunitairfilterdirty Indoortemperaturesettingtoohighortoolow Reversingvalvefaultyorinternalleak Indoortemperaturesettingtoohighortoolow Evaporatorcoilcoveredwithice Expansiondeviceorsuctionlineclogged Outdoorfandoesnotstopduringdefrost _eriods Electricalconnectionloose Fanmotorburnout Fanbearingseized Expansiondevicecloggedorcoveredwithice DischargePressureTooLow SuctionPressureTooHigh SuctionPressureTooLow OutdoorFanCyclingDueto Over-TemperatureProtection Cleanorremoveobstructions. Replacecondenserfan. Checktemperaturesetting. Drainrefrigerant,evacuateandrecharge. CAUTION:Donotventrefrigeranttotheatmosphere; userefrigerantrecoveryequipment. Checktemperaturesetting. Cleanorremoveobstructions. Cleanfilter. Checktemperaturesetting. Replacereversingvalve. Checktemperaturesetting. Aircirculationontheevaporatornotsufficient;check andrepair. Checkandrepair. Checkelectricalparts. Checkconnections. Replace. Checkandrepair. Drainrefrigerant,evacuateandreplace. CAUTION:Donotventrefrigeranttotheatmosphere; userefrigerantrecoveryequipment. ]5
Copyright2006CarrierCorporation Manufacturerreservestherighttodiscontinue,orchangeatanytime,specificationsordesignswithoutnoticeandwithoutincurringobligations. CatalogNo.02-40QN0001-SIPrintedinU.S.A.Form40QN-8SIPg163-06Replaces:New