Page 91
POWER UNITS POWER UNITS 631DA1 Power Unit Provides +5 volt DC 60-amp power on the backplane on the control carrier and the port carriers. 631DB1 Power Unit Provides -48 volt DC 8-amp and -5 volt 6-amp power on the back- planes of the carriers. 644A1 Power Unit Provides +5 volt DC 60-amp power on the backplane on the control carrier and the port carriers of -48 volt DC powered cabinets. 645B1 Power Unit Provides -48 volt DC 8-amp and -5 volt DC 6-amp power on the backplanes of the carriers of -48 volt DC...
Page 92
POWER UNITS TN755B Power Unit Supports applications requiring neon message waiting lamps. 676B Power Unit Provides +5 volt DC power, -5 volt DC power, -48 volt DC power, +12 volt DC power, and ringing voltage for -48 volt DC powered single-carrier cabinets. 87
Page 93
DUPLICATION OPTION DUPLICATION OPTION G3iV2, the Duplication Option provides: lA duplicated control carrier (multicarrier cabinet) or a duplicated control cabinet (single-carrier cabinet) that houses a second Switch Processing Element (SPE). The SPE includes the following: — Processor Circuit Pack TN773 — Network Control Circuit Pack TN777B — Packet Control Circuit Pack TN778 (G3V2) — Memory Circuit Pack(s) TN770 Power source to the fans from both the control carrier and duplicated control carrier....
Page 94
DUPLICATION OPTION l lPort networks interconnected by single cables Duplicate switch node circuit packs in the switch node carrier In a fully-duplicated G3rV2 system, there is also, in addition to the items mentioned for the G3iV2 system, a CSS. 89
Page 95
ENVIRONMENTAL REQUIREMENTS ENVIRONMENTAL REQUIREMENTS (Multicarrier Cabinet) CABINET Fully Loaded 5-Carrier (PPN or EPN) HEAT DISSIPATION 8000 BTU/HR 5000 BTU/HR AC POWER REQUIREMENTS 120 volts 60Hz 208 volts (3-wire) 60Hz 208/240 volts (4-wire) 60Hz DC POWER REQUIREMENTS800 Lbs 70”x32”x28” Fully Loaded 5-Carrier Average 5-Carrier 50 Amps MCC 30 Amps MCC 25 Amps MCC -48 volts 75 Amps TEMPERATURE/ROOM HUMIDITY RANGE 40° To 120°F. 10% to 95% Relative Humidity at 84°F 10% to 45% Relative Humidity at 110°F...
Page 96
ENVIRONMENTAL REQUIREMENTS Each Port or Expansion125 Lbs19”x27”x22” HEAT DISSIPATION 6800 BTU/HRFully Loaded 4-Cabinet System (requirements are same for PPN and EPN) 1700 BTU/HRAverage for a Single Cabinet AC POWER REQUIREMENTS 120 volts 50-60Hz 15 Amps1-Cabinet System 120 volts 50-60Hz Two 15 Amps or 20 Amps 2-Cabinet System 120 volts 50-60Hz Three 15 Amps or 20 Amps 3-Cabinet System and 15 Amps 120 volts 50-60Hz Two 15 Amps and 20 Amps 4-Cabinet System or Two 20 Amps DC POWER REQUIREMENTS -48...
Page 97
MAXIMUM CABLING DISTANCES MAXIMUM CABLING DISTANCES Equipment24-Gauge Wire26-Gauge Wire (0.5106 mm) (0.4049 mm) FeetMetersFeetMeters Attendant console (301A) 2400732 1500457 Enhanced attendant console (302A) With selector console Phantom powered Locally powered Without selector console Phantom powered Locally powered800 5000 1400 5000244 1524 427 1524500 3400 900 3400 2200152 1037 274 1037 510D or 515 terminals 3000914 670 513, 610 BCT, or 615 MT, 4410 or 4425 terminals ( see also “data module” or “EIA...
Page 98
MAXIMUM CABLING DISTANCES Equipment EIA interface (data line circuit pack and ADU): 19.2 kbps 9.6 kbps 4.8 kbps 2.4 kbps 1.2 kbps 0.3 kbps Voice terminals: Analog 8-port circuit pack (TN742, TN769), on-premises or out-of-building — same premises (notes 1 and 2) 500- or 2500- type (note 3) 7100 series 16-port circuit pack (TN746), on-premises only — no out-of-building or bridging (note 1) AT&T 500 or 2500 type terminals without adjuncts 16-port circuit pack (TN746B), on-premises or out-of-building — same...
Page 99
MAXIMUM CABLING DISTANCES Equipment Meters ISDN (TN556) (note 5) 7500 series (point-to-point) Termination resistor (3 feet) Termination resistor (250 feet) 8503 Set MET sets (TN735)24-Gauge Wire (0.5106 mm) Feet 1900 1600 1600 1000579 488 487 30526-Gauge Wire (0.4049 mm) Feet 1600 1300 1330 650 Meters 488 396 405 198 Notes: 1. 2. 3. An out-of-building, same-premises, analog terminal instal- lation requires a carbon block, gas tube, or equivalent solid state device at each end of the interbuilding cable....
Page 100
MAXIMUM CABLING DISTANCES PPN CABINET TO EPN CABINET MAXIMUM CABLING DISTANCES The maximum length of the fiber-optic cable between the PPN cabinet and the EPN cabinet is approximately 7.6 km (25,000 feet) depending on installation requirements. The requirements that determine the maximum fiber link distance for an installation are: l l l l lThe mean loss and the length of the outside plant fiber cable The mean loss and the length of fiber cable shipped with the cabinet (including any fiber riser cable)...