    							FIGURE 1: DIMENSIONSDPD72PG1
    BILEVEL STEP MOTOR DRIVER PACK
    with RAMPING PULSE GENERATOR 
     Integrated 300 Watt Power Supply
     10 Amperes/phase Maximum Operating Current
     7 Amperes/phase Standstill motor current
     Adjustable Base and Max Speeds
     Linear Ramping Pulse Generator
     Half-step and Full-step Operation
     Bilevel Drive Operation 
     No RFI or EMI problems
     TTL/CMOS Compatible Inputs
     Motor Turn-off Input
    GENERAL DESCRIPTION
    The ANAHEIM AUTOMATION DPD72PG1 Step Motor Driver Pack is designed to operate 6-lead, 4-phase step motors rated at 1 - 7
    amps/phase.  This Driver Pack contains a BLD72 Step Motor Driver, an AA2876 Ramping Pulse Generator, a 300 Watt transformer,
    and a cooling fan.  Outstanding motor performance is provided by means of a Bilevel Drive technique.
    BILEVEL DRIVE
    The basic function of a step motor driver is to control the motor winding currents.  Motor performance is determined by how fast the
    driver can increase and decrease the winding currents. A rapid rise in winding current is achieved by applying a high voltage directly
    to a motor.  This rapid rise of current is also referred to as the kick or operating current.  When a desired current level is reached, a
    low voltage is applied to maintain a suitable holding current level.  When a motor winding is turned off, a rapid decrease in winding
    current is achieved by routing the energy in the collapsing field back to the power supply through a high voltage path.  The high voltage
    supply furnishes the energy necessary to maintain motor output torque at high step rates thus providing high mechanical power output.
    The low voltage supply provides much of the current needed at low step rates and all of the holding current.  
    Bilevel drivers do not use high frequency switching techniques as chopper drivers do.  Consequently, they do not create the EMI, RFI,
    and motor heating problems that are associated with chopper drivers.
    EXCITATION MODE SELECT 
    Users have a choice of dual-phase, full-step operation or half-step operation. Dual-phase, full-step operation occurs by energizing two
    phases at a time, rotating a typical motor 1.8 degrees per step.  Half-step operation occurs by alternately energizing one, and then two,
    phases at  a time, rotating the motor O.9 degrees per step.  Full-step operation is only suggested for applications that specifically require
    that mode, such as when retrofitting existing full-step systems.
    STEP AND  DIRECTION CONTROL
    The Clock output of the AA2876 Pulse Generator is internally wired to the Clock input of the Driver board.  Terminal 5 on the driver
    side is the Direction Input.  A  logic 1 on this input selects Clockwise motor direction.  A logic 0 on this input selects
    Counterclockwise direction.
    #L010026 
    						
    							1 2 3 4
    5 6 7
    +12V UNREG 0VDC +5VDC
    CLOCK OUT VCO IN STOP/RUN
    BASE/MAXPHASE 1
    PHASE 3
    1,3 COM
    RESET
    DIRECTION
    CLOCK IN
    0VDC
    HS/FS
    ON/OFF
    N/C INTERNALLY
    CONNECTED1
    2
    3
    4
    5
    6
    7
    8
    9
    10RED
    RED/WHT
    BLACK11
    12
    13GRN
    GRN/WHTWHITE
    ANAHEIM AUTOMATION
    6-LEAD STEP MOTOR 2,4 COM
    PHASE 2
    PHASE 41 AMPFIGURE 2:  TYPICAL HOOKUP DIAGRAM MOTOR ON/OFF INPUT
    The motor on/off input allows for de-energizing a motor without disturbing the positioning logic.  After re-energizing  the  motor,  a
    routine can continue. This reduces motor heating and conserves power, especially in applications where motors are stopped for long peri-
    ods and no holding torque is required.
    ADJUSTING KICK CURRENT
    By following the silkscreen markings on the cover, use a smallscrewdriver to adjust the potentiometer. Line up the arrow to the number
    corresponding to the motors rated current (amps/phase).  The kick current is preset for 40 percent over the motors rated amps/phase.
    MOTOR CONNECTIONS 
    Figure 2 is a hookup diagram for typical DPD72PG1 driver applications. Wiring connected to inputs must be separated from motor
    connections and all other possible sources of interference. 
    IMPORTANT NOTE: When the wiring from the driver to the step motor extends beyond 25 feet, consult the factory.
    TRANSIENT VOLTAGE SUPRESSION (TVS)
    The TVS diodes allow longer motor cables to be used.  Normally when using long motor cables, voltage transients and spikes are created.
    These transients often exceed the voltage ratings of the output phase transistors, resulting in blown transistors.  The addition of the TVS
    Diodes suppresses these transients and protects the transistors against damage.   
    						
    							1
    13
    WARNING:
    Set Kick Current 
    before operating motor!!!Terminal BlockKICK CURRENT ADJUSTJP21
    2
    3JP11 2 31
    2
    3JP3FAULT
    POWERFIGURE 1: JUMPER LOCATIONS.FUNCTIONJP1JP2JP3
    NEGATIVE GOING CLOCKS1-2XX
    POSITIVE GOING CLOCKS2-3XX
    TERMINAL 5 = CCWX1-2X
    TERMINAL 5 = DIRECTIONX2-3X
    GROUND FAULT DETECTION
    ENABLEDXX2-3
    GROUND FAULT DETECTION
    DISABLEDXX1-2
    TABLE 2: JUMPER SETTINGS  BILEVEL DRIVER
    The DPD72PG1 uses a BLD72 driver.  The BLD72 has two clock options:  Clock and Direction, or Dual Clock operation. Internal
    Terminal 5 on the BLD can be configured as the Direction Input or CCW Input by placing jumpers in the appropriate position.
    Pulses applied to the Clock input cause the motor to step in the clockwise direction if the Direction Input is a logic 1 or the
    counterclockwise direction if the Direction Input is a logic 0.  Pulses applied to the CCW Input cause the motor to step in
    the counterclockwise direction.  Either positive or negative going pulses may be used by setting jumpers in the appropriate
    position (SeeTable 1).
    PULSE GENERATOR
    The DPD72PG1 contains the AA2876 linear ramping pulse generator (PG).  The AA2876 PG has adjustable BASE and MAX speeds
    and independent adjustments for acceleration (ramping up) and deceleration (ramping down).  It also features a VCO Input where the
    clock frequency produced is proportional to the voltage fed into the VCO Input.  The clock pulse output of the AA2876 is an open
    collector type output.
    SPEED RANGES
    The AA2876 has an adjustable BASE speed (starting speed) and an adjustable MAX speed (running speed).  There are two speed ranges
    that are jumper selectable.  For the low speed range, the BASE speed can be adjusted from 50 pulses/sec to 500 pulses/sec and the MAX
    speed can be adjusted from 50 pulses/sec to 5,000 pulses/sec.  For the high speed range, the BASE speed can be adjusted from 200
    pulses/sec to 2,000 pulses/sec and the MAX speed can be adjusted from 200 pulses/sec to 20,000 pulses/sec.  Note: it is possible to have
    a MAX speed that is lower than the BASE speed.  The BASE speed potentiometer is on-board; the MAX speed  potentiometer is external
    (mounted on side of chassis).
    RAMPING
    There are separate adjustments for acceleration and deceleration.  The ramp times are adjustable from 50 milliseconds to 1.0 seconds.
    This is the time it takes to ramp from the lowest BASE speed to the highest MAX speed.  In terms of  acceleration units, the accel/decel
    rates are adjustable from 5,000 to 100,000 steps/s on the low speed range and 20,000 to 400,000 steps/s on the high speed range. 2           2
    INPUTS
    (See operating modes)
    STOP/RUN - When this input is open or logic 1, the PG is stopped and will not output any pulses.  When this input is pulled low to
    a logic 0, the PG will output pulses at the BASE speed rate if the BASE/MAX input is left open, or logic 1.  If both the STOP/RUN
    and the BASE/MAX inputs are at a logic 0, the PG will ramp up and output pulses at the MAX speed rate.  This input is only used
    in the Two-input operation. 
    						
    							BASE/MAX - This input has two functions.  In the Two-input operation, this input selects either BASE speed (logic 1) or MAX speed
    (logic 0).  When this input changes, the PG will ramp from one speed to the other.
    In the Single-input operation, this input is used to start and stop the PG (logic 1=stop, logic 0=run). Upon starting, the PG will start
    running at BASE speed but immediately ramp up to the MAX speed and keep running at the Max speed while this input is logic 0.
    When this input goes back to logic 1, the p.g. will either stop immediately, or it will ramp down and stop when it reaches BASE speed
    (depending on JP2 setting).  With Single-input operation, the PG only uses BASE speed as a starting speed;  it cannot run at BASE speed
    for a while.  The STOP/RUN input is NOT used with Single-input operation.
    VCO IN - A voltage (0 to 5Vdc) can be fed into this input instead of using the MAX speed remote POT.  The AA2876 will produce a
    frequency that is proportional to the voltage on this input.  To use this input, the BASE/MAX input must be pulled to a logic 0 and
    the MAX Speed POT disconnected.  Please note that the PG will start at BASE speed (set by the BASE speed POT) and ramp to the
    frequency determined by the voltage fed into the VCO Input.  In most cases, it is best to set the BASE speed POT to the lowest setting
    when using the VCO Input.  See Figure 5.
    LIMITING THE MAX SPEED
    In some applications, it may be necessary to limit the MAX speed so that the operator does not run the machine or system too fast.
    The 
    MAX Speed Limit potentiometer can be adjusted to limit the top speed.  Please note that this only affects the MAX speed; the BASE
    speed is unaffected.
    +5V POWER SUPPLY
    This power supply is capable of supplying up to 1.0A to other devices or circuitry.  The +12V unregulated voltage may also be used for
    supplying current to external loads up to 1.5A.  These outputs can only source a combined total of 1.5 Amps max. 
    						
    							ABCD
    EFBASE SP.MAX SPEED
    RAMPING UPRAMPING DOWNABCBASE SP.MAX SPEED
    RAMPING UPABCBASE SP.MAX SPEED
    RAMPING UP
    RAMPINGDOWN
    D1 2 31 2 3
    FUNCTIONJP1JP2Low Speed Range1-2-----
    High Speed Range2-3-----
    Ramp Up Only-----2-3
    Ramp Up and Down-----1-2 TABLE 1:  Speed and Ramp Options for
    AA2876 Pulse Generator
    FIGURE 3:  JUMPER LOCATIONS FOR AA2876 OPERATING MODES
    1.  TWO INPUT OPERATION - see Ramp Profile 1.
    A.STOP/RUN is pulled low; Start at BASE speed and run for a while 
    at BASE speed
    B.BASE/MAX is pulled low; Ramp up to MAX speed
    C.Both inputs are still low; MAX speed is reached (keep running at MAX
    speed)
    D.BASE/MAX input is let go, or pulled high and STOP/RUN is still low;
    Ramp down to BASE speed
    E. STOP/RUN is still low; BASE speed is reached
    F. STOP/RUN input is let go, or pulled high; STOP
    2.  SINGLE INPUT OPERATION W/ NO RAMPING DOWN* 
    see Ramp Profile 2.
    A.BASE/MAX input is pulled low; Start at BASE speed and immediately
    ramp up to MAX speed
    B.  BASE/MAX input is still low; MAX speed is reached 
    C.BASE/MAX input is let go, or pulled high; STOP immediately 
    Note: In this mode, the PG still ramps down internally even though pulses
    stop; so, before starting again, the operator must allow sufficient time for the
    PG to ramp back down to BASE speed.  Also, the decel adjustment should be
    set for the fastest ramp down.
    3.  SINGLE INPUT OPERATION W/ RAMPING DOWN* 
     see Ramp Profile 3.
    A.BASE/MAX input is pulled low; Start at BASE speed and immediately
    ramp up to MAX speed 
    B. MAX speed is reached
    C. BASE/MAX input is let go or pulled high; Ramp down
    D. Automatically stop when BASE speed is reached.
    * NOTE:  With single input operation, jumper JP2 is used to select RAMPING
    DOWN, or NO RAMPING DOWN. 
    						
    							115 VAC HOOKUP
    100 VAC HOOKUP130 VAC HOOKUP
    245 VAC HOOKUP 230 VAC HOOKUP 215 VAC HOOKUP 110 VAC MAX
    100 VAC NOM
    90 VAC MIN125 VAC MAX
    115 VAC NOM
    105 VAC MIN140 VAC MAX
    130 VAC NOM
    120 VAC MIN235 VAC MAX
    215 VAC NOM
    195 VAC MIN250 VAC MAX
    230 VAC NOM
    210 VAC MIN265 VAC MAX
    245 VAC NOM
    225 VAC MINFIGURE 4:  Hookup diagram for various power inputs. X250A VERSIONS
    The DPD72PG1 Driver Pack is available in an X250 version to accomodate power inputs other than the standard 115VAC.  The
    X250 version can be configured to accept nominal power inputs of 100VAC, 115VAC, 130VAC, 215VAC, 230VAC, and 245VAC. 
    Figure 4 below  shows connections to the power terminals for each configuration. 
    						
    							DRIVER SPECIFICATIONS
    Control Inputs (All) : (Terminals 5, 6, 8, 9)
    TTL/CMOS-compatible 
    Logic O - O  to  O.8 V
    Logic 1 - 3.5 to 5.O V  
    Clock Inputs :  (Terminals 5 & 6)
    15 microseconds minimum pulse width required.  The Clock input is internally pulled up to +5Vdc through a 1OKÙ resistor.  
    Direction Control: (Terminal 5)
    pulled up to +5Vdc through 10k ohm resistor
    Logic 1 (open) - CW motor direction
    Logic O - CCW motor direction
    Excitation Mode Select: (Terminal 8)
    pulled up to +5Vdc through 10k ohm resistor
    Logic 1 - Half-step
    Logic O -Full-step
    Motor On/Off: (Terminal 9)
    pulled up to +5Vdc through 10k ohm resistor
    Logic 1 (open) - motor current on
    Logic 0 - motor current off
    Output Current Rating:
    (Terminals 1, 2, 3, 11, 12, & 13)
    10 Amps per phase maximum operating or running current, and 7 Amps per phase maximum standstill current.  Motor phase 
    ratings of 1.0 Amp minimum are required to meet the minimum kick level.
    Power Requirement :  Standard 115VAC version can accept power inputs ranging from 105VAC to 125VAC, 50-60Hz.  See figure 4
    for power requirements for the X250 versions.
    Operating Temperature : 0 to 60 degrees C
    The DPD Driver Packs contains an internal fan to create airflow through the unit.  Heating considerations should include where the
    unit is mounted, the duty cycle of operation, ambient temperature, etc.  Care should be taken so that no point on the chassis exceeds
    60 degrees Celsius.
    Fuse Rating: 
    5 Amp Fast Blow, 5x20mm
    5Amp Fast Blow, 3AG for X250 Versions. 
    						
    							TERMINALFUNCTION1AC INPUT
    2AC INPUT TABLE 2: TB1 Terminals
    TERMINALFUNCTION1+12V UNREG INPUT
    20VDC
    3+5VDC
    4CLOCK OUT
    5VCO INPUT
    6STOP/RUN
    7BASE/MAX TABLE 3: TB2 Terminals
    FIGURE 5:  VCO IN vs. FREQUENCY OUT PULSE GENERATOR SPECIFICATIONS
    BASE/MAX Input: pin 7, TB2
    (10k ohm pullup)
    Base speed - Logic 1 or open
    Max speed (single input running) - Logic 0
    STOP/RUN Input: pin 6, TB2
    (10k ohm pullup)
    Stop - Logic 1 or open
    Run - Logic 0
    VCO Input: pin 5, TB2
    0 to 5Vdc
    Input Impedance: 1Meg Ohm
    PULSE OUTPUT: pin 4, TB2
    Open collector, sink 100 mA
    SPEED RANGES, approximate:
    Low:BASE SPEED 50 - 500 pulses/sec
    MAX SPEED  50 - 5,000 pulses/sec
    High:  BASE SPEED 200 - 2,000 pulses/sec
    MAX SPEED  200 - 20,000 pulses/sec
    RAMP TIMES: time to ramp from lowest BASE to highest MAX
    50 milliseconds to 1.0 seconds
    ACCELERATION/DECELERATION RATES:
    5,000 - 100,000 pulses/s for the Low speed range 2 
    20,000 - 400,000 pulses/s for the High speed range 2 
    POWER SUPPLY OUTPUTS
    +5VDC output:  1.0 Amps absolute maximum *
    (see paragraph on +5VDC OUTPUT)
    +12VDC unregulated output: 1.5 Amps maximum *
    * No more than 1.5A total can be drawn from both of these 
       outputs simultaneously. 
    						
    							TORQUE/SPEED CURVES 
    						