Home
>
American Water Heater
>
Gas Heater
>
American Water Heater Polaris High Efficiency Commercial Gas Water Heater PCG3 User Manual
American Water Heater Polaris High Efficiency Commercial Gas Water Heater PCG3 User Manual
Have a look at the manual American Water Heater Polaris High Efficiency Commercial Gas Water Heater PCG3 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
11 INLET/OUTLET VENT TERMINATIONS Standard Horizontal Termination When 3 inch pipe is used between the water heater and the outside wall, reduce it to 2 inch pipe before penetrating the wall. A maximum of 18 inches (45.7 cm) of 2 inch pipe may be used between the 3 inch transition and the inside of the wall (see figure 7). The standard horizontal air inlet termination is a 2 inch pipe which terminates at the exterior wall and utilizes a coupling to prevent the pipe from being pushed back into the structure. The standard horizontal exhaust outlet termination is a 2 inch pipe which terminates 12 inches (30.5 cm) from the outside wall. The air inlet must be located with respect to the exhaust outlet as shown in figure 7 (bottom). Install a drain tee assembly and trap in the inlet vent as close to the water heater as possible. This is to drain any water that may be in the combustion air pipe and prevent it from entering the blower. Connect the trap drain line to a suitable drain or downstream of the condensate trap of the water heater. Note: See “Venting Additional Polaris ® Units” on Page 12 for correct terminations if installing more than one Polaris® gas water heater. Alternative Horizontal Termination The combustion air and exhaust terminations may be raised up to 24 inches (61 cm) above the wall penetrations if required for anticipated snow levels (see figure 8). The two elbows shown in figure 8 are considered part of the termination and should not be included when determining the maximum allowable vent pipe length. Note: See “Venting Additional Polaris ® Units” on Page 12 for correct terminations if installing more than one Polaris® gas water heater. (30.5 cm) 24” (61 cm) Max. (76.2 cm) Figure 7: Standard Horizontal Termination 3” (7.6cm) Max. 4” (10 cm) Max. 4” (10 cm) Max.12” (30.5 cm) 2” Coupling 12” (30.5cm) Min. Above Grade or Anticipated Snow Level. See Note 4. Notes: 1. Support Horizontal Pipe Every Four Feet (1.2 m). Support Vertical Pipe Every Six Feet (1.8 m). 2. When Using 3 Inch Pipe, Reduce To 2 Inches Before Penetrating The Outside Wall. 3. 18 Inch (45.7 cm) Maximum When Using 3 Inch Pipe. 4. Increase The 12 Inch (30.5 cm) Minimum Above Grade To Keep Terminal Openings Above Anticipated Snow Levels. 5. Slope All Piping Down Toward the Water Heater as Follows:
12 VERTICAL TERMINATIONS When 3 inch pipe is used between the water heater and the roof, reduce it to 2 inch pipe before penetrating the roof. A maximum of 18 inches (45.7 cm) of 2 inch pipe may be used between the 3 inch transition and the inside of the roof. The vertical inlet air termination requires a return bend or two short or long sweep radius 90 elbows to keep the inlet downward and prevent entry of rain. These elbows are considered part of the termination and should not be included when calculating the maximum allowable vent pipe length. Refer to figure 9 for the proper location of the air inlet with respect to the exhaust outlet termination. The vertical exhaust outlet termination is a 2 inch (30.5 cm) pipe which terminates at least 12 inches (30.5 cm) above the inlet air termination. The air inlet and exhaust outlet terminations must be at least 12 inches (30.5 cm) above the roof line or anticipated snow levels. See figure 9 below. Note: See “Venting Additional Polaris ® Units” below if installing more than one Polaris® gas water heater. Venting Additional Polaris® Units When using two (2) Polaris® units, install vent terminations using either Method A or Method B below:When using three or more Polaris ® units, install vent terminations per Method C or Method D: Figure 9: Vertical Termination Notes: 1. Support Horizontal Pipe Every Four Feet (1.2 m). Support Vertical Pipe Every Six Feet (1.8 m). 2. When Using 3 Inch Pipe, Reduce To 2 Inches Before Penetrating The Roof. 3. 18 Inch (45.7 cm) Maximum When Using 2 Inch Pipe. 4. Increase The 12 Inch (30.5 cm) Minimum Above Grade To Keep Terminal Openings Above Anticipated Snow Levels.4” (10 cm) Max. 12” (30.5cm) Min. Above Roof or Anticipated Snow Level. See Note 4.12” (30.5 cm) Min. 12” (30.5 cm) Min. 4” (10 cm) Max. 12” (30.5 cm) Min. * * 3” (7.6cm) Max. 4” (10cm) Max. 3” (7.6 cm) Max. 4” (10cm) Max.36” (91.4 cm) Minimum3” (7.6 cm) Max. 4” (10cm) Max. 3” (7.6 cm) Max. 4” (10cm) Max. 4” (10cm) Max.36” (91.4 cm) Minimum 4” (10cm) Max.4” (10cm) Max.4” (10cm) Max. 36” (91.4 cm) Minimum36” (91.4 cm) Minimum Figure 9A, 9BFigure 9C, 9D
13 CONCENTRIC VENT TERMINATIONS For new installations, install 2” Concentric vent kit model KGAVT0501CVT, part number 6910542. See Manufacturer’s instructions for complete installation or call customer service at 1-800-456-9805 for assistance or go to www.americanwaterheater.com. For planning purposes, see figures 10-13 below for vent terminal specifications. Note: For replacement installations, previously installed American Water Heater Company supplied concentric vent kits are acceptable for use on 100,000-130,000 BTU/Hr models only. Make sure that the existing vent complies with current codes. (14.6cm) (15.7cm) (8.9cm Dia.) (42.2cm) (84.77cm)(4.8cm)(3.8cm) Figure 10: 2 Inch Concentric Vent (2.54cm) Figure 11: Through the Wall Termination 12” (30.5cm) Minimum clearance above anticipated snow level. 24” (61cm) Max. Figure 12: Through the Roof Termination Notes: 1. Support Horizontal Pipe Every Four Feet (1.2 m). Support Vertical Pipe Every Six ft. (1.8 m). 4. Increase The 12 Inch (30.5 cm) Minimum Above Grade To Keep Inlet Opening Above Anticipated Snow Levels. 5. Slope All Piping Down Toward the Water Heater as follows:
14 Figure 14: Input GraphGas Input Rate The gas input rate of this water heater is affected by several environmental factors such as: • The heating value of the gas • The air and gas densities (which vary widely due to baro- metric pressure and temperature changes) • Venting installations (pipe diameter, length and fittings) • Altitude When measuring the input rate these factors should be incorporated into the calculations. Also measure the gas consumption over a sufficiently long time to obtain an accurate gas consumption rate (e.g. 3-5 minutes, not one revolution of the meter needle). Long vents and each additional elbow, inherently reduce the gas input rate due to increased resistance to moving combustion air and flue gases. The approximate maximum/ minimum input for the 100k, 130k, and 150k models is shown in figure 15. WATER PIPING SYSTEM Piping Installation Piping, fittings, and valves should be installed according to the installation drawing (figure 15). If the indoor installation area is subject to freezing temperatures, the water piping must be protected by insulation. The water supply pressure should not exceed 80 psi (551.5 kPa). If this occurs, a pressure reducing valve with a bypass should be installed in the cold water inlet line. This should be placed on the supply to the entire house in order to maintain equal hot and cold water pressures. Important: Heat cannot be applied to the water fittings on the heater as they may contain nonmetallic parts. If solder connections are used, solder the pipe to the adapter before attaching the adapter to the hot and cold water fittings. Important: Do not install this water heater with iron or galvanized piping. Use brass caps on all unused inlet/ outlet connections. 1. Install the water piping and fittings as shown in figure 15. Note: If state or local codes require, install a vacu- um relief valve per the manufactures instructions in the cold water supply line. Connect the cold water supply (use 1” NPT) to the fitting marked “COLD INLET”. Do not turn the cold water nipple. The mark should remain along the top side of the nipple. Connect the hot water supply (use 1” NPT) to the fitting marked “HOT OUTLET”. 2. Always use a suitable grade of joint compound and be certain that all fittings are tightened properly. 3. The installation of unions in both the hot and cold water supply lines is recommended for ease of removing the water heater for service or replacement. 4. If installing the water heater in a closed water system, install an expansion tank in the cold water line as speci- fied under “Closed System/Thermal Expansion” (Page 15). 5. Install a shut-off valve in the cold water inlet line. It should be located close to the water heater and be easily accessible. Know the location of this valve and how to shut off the water to the heater.6. The Polaris ® gas water heater is shipped with a factory- installed Temperature and Pressure Relief Valve. Install a discharge line in the opening in the T & P valve (see instructions on Page 17). 7. After piping has been properly connected to the water heater, remove the aerator at the nearest hot water faucet. Open the hot water faucet and allow the tank to completely fill with water. (To prevent damage to the unit, DO NOT connect power until the tank is COMPLETELY FILLED). To purge the lines of any excess air, keep the hot water faucet open for 3 min- utes after a constant flow of water is obtained. Close the faucet and check all connections for leaks. Corrosion and Water Quality Water quality will vary from location to location and may contain contaminates that may reduce the life or perfor- mance of the water heater. To test for contaminates a water quality test kit is available, reference part number 6903791. Contaminates which can reduce the life or performance of the water heater if present in high quantities include those which contribute to hardness (dissolved minerals such as sodium, calcium and magnesium); plus chlorides and sulfates. Additionally, water that is too acidic or basic (measured as pH) can reduce the life of the water heater. Water treatment systems (such as water softeners for hardness) should be used and maintained properly if the contaminate levels exceed the following: Warranty is void in applications which exceed the water quality requirements listed below. Table 2: Total Hardness:12 grains per gal. (205 mg/liter) max. Chloride: 200 mg/liter max. pH: 6.5-8.0 Alkalinity: 200 mg/liter max.
15 Figure 15: Typical One-Temperature System Piping Installation Mixing Valve Installation A mixing valve has been provided for use with the Polaris® Gas water heater and must be installed, per the manufacturer’s instructions, in the domestic hot water line. See Figure 16 for a sample tempering valve installation. General Information Water piping, fittings, and valves must be properly installed for the correct and safe operation of this water heater. Please note the following: • The system should be installed only with piping that is suitable for potable (drinking) water such as copper, CPVC, PEX or polybutylene. PVC water piping may be used on the cold water inlet supply but not within 18 inches (45.7 cm) of the cold water connection on the water heater. • Do not use PVC piping on the hot water outlet, space heating supply, or space heating return. • Do not use any pumps, valves, or fittings that are not compatible with potable water. • Do not use valves that may cause excessive restriction to water flow. Use full flow ball or gate valves only. • Do not use 50/50 tin-lead solder (or any lead based solder) in potable water lines. Use 95/5 solder or other equivalent material. • Do not tamper with the thermostat, gas valve, blower, electrical components, or temperature and pressure relief valve. Tampering with any of the components is dangerous and can result in death, severe injury, or property damage. Tampering voids all warranties. Only qualified technicians should service these components. • Do not use this water heater as a replacement for an existing boiler installation. • Do not use with piping that has been treated with chromates, boiler seal, or other chemicals. • Do not add any chemicals to the system piping which will contaminate the potable water supply. Closed System/Thermal Expansion As water is heated, it expands (thermal expansion). In a closed system, the volume of water will increase. As the volume of water increases, there will be a correspond- ing increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leak- age). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent temperature-pressure relief valve operation; water dis- charged from the valve due to excessive pressure build up. The temperature-pressure relief valve is not intended for the constant relief of thermal expansion. This condition is not covered under the limited warranty. A properly-sized thermal expansion tank should be installed on all closed systems to control the harmful effects of thermal expansion. Contact a plumbing service agency or your retail supplier regarding the installation of a thermal expansion tank. The manufacturer of this water heater will void the warranty if there is a failure to install a properly sized expansion tank. Combination Space Heating/Potable Water System Some water heater models are equipped with inlet/ outlet connections for use in space heating applications. Note: this water heater, “Suitable for combination water (potable) heating and space heating and not suitable for space heating applications only.” If this water heater is to be used to supply both space heating and potable (drinking) water, the instructions listed below must be followed (see figure 17). • Be sure to follow the manual(s) shipped with the air handler or other type heating system. • This water heater is not to be used as a replacement for an existing boiler installation. Check local codes. (set to 120° F [48.8° C] or lower) Figure 16: Sample Mixing Valve Installation Mixing Valve Mixing Valve Metal Drain Pan6” (15.2cm) Air Gap Max. Adequate Drain
16 • Do not use with piping that has been treated with chromates, boiler seal or other chemicals and do not add any chemicals to the water heater piping. • If the space heating system requires water temperatures in excess of 120°F (48.9°C), a mixing valve (provided) must be installed per the manufacturer’s instructions in the potable hot water supply to limit the risk of scald injury. • Pumps, valves, piping and fittings must be compatible with potable water. • A properly installed flow control valve is required to pre- vent thermosiphoning. Thermosiphoning is the result of a continuous flow of water through the air handler circuit during the off cycle. Weeping (blow off) of the temperature and pressure relief valve (T & P) or higher than normal water temperatures are the first signs of thermosiphoning. • The hot water line from the water heater should be ver- tical past any mixing valve or supply line to the heating system to remove air bubbles from the system. • Do not connect the water heater to any system or components previously used with non-potable water heating appliances when used to supply potable water. Storage Tank Installation When installing the Polaris® with a storage tank, see figure 18 for piping suggestions. Solar Installation If this water heater is used as a solar storage heater or as a backup for the solar system, the water supply tempera- tures to the water heater tank may be in excess of 120°F (48.9°C). A mixing valve must be installed in the water sup- ply line to limit the supply temperature to 120°F (48.9°C). Note: Solar water heating systems can often supply water with temperatures exceeding 180°F (82.2°C) and may result in water heater malfunction. Figure 17: Air Handler Piping Installation Mixing Valve Metal Drain Pan 6” (15.2cm) Air Gap Max. Adequate Drain Massachusetts code does not allow this type of installation.
17 Temperature and Pressure Relief Valve For protection against excessive pressures and tempera- tures, a temperature and pressure relief valve must be installed in the opening marked “T & P RELIEF VALVE”. This valve must be design certified by a nationally recog- nized testing laboratory that maintains periodic inspection of the production of listed equipment or materials as meet- ing the requirements for Relief Valves and Automatic Shut-off Devices for Hot Water Supply Systems, ANSI Z21.22. The function of the temperature and pressure relief valve is to discharge water in large quantities in the event of exces- sive temperature or pressure developing in the water heat- er. The valve’s relief pressure must not exceed the working pressure of the water heater as stated on the data plate. Important: Only a new temperature and pressure relief valve should be used with this water heater. Do not use an old or existing valve as it may be damaged or not ade- quate for the working pressure of the new water heater. Do not place any valve or piping between the relief valve and the tank. The Temperature & Pressure Relief Valve: • Must not be in contact with any electrical part. • Must be connected to an adequate discharge line. • Must not be rated higher than the working pressure shown on the data plate of the water heater. • The BTUH rating of the T & P valve must be greater than, or equal to, the input rating of the water heater The Discharge Line: • Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line. • Must not be capped, blocked, plugged or contain any valve between the relief valve and the end of the dis- charge line. • Must terminate a maximum of 6 inches (15.2 cm) above a floor drain or external to the building. • Must be capable of withstanding 250°F (121°C) without distortion. • Must be installed to allow complete drainage of both the valve and discharge line. Mixing ValveTank Temperature Control (170°F [76.6°C] Max.) (If Used) Figure 18: Polaris® with Auxillary Storage Tank - One or Two Temperature System (With or Without Building Recirculation)Notes on Figure 18: If tank temperature is set above 120°F (48.9°C) and water is sup- plied for domestic use (hand wash- ing, showering, etc.) a mixing valve must be installed in the hot water line to domestic fixtures. Installation must conform to local code requirements. If a check valve is installed in the cold water sup- ply line, an expansion tank must be installed between the check valve and the water heater’s cold water inlet. Set storage tank temperature five degrees lower than the water heater’s temperature setting. Using the plug valve in the recirculating line, adjust the flow in the recirculat- ing line to five gallons per minute. Explosion Hazard • Temperature-pressure relief valve must comply with ANSI Z21.22-CSA 4.4 and ASME code. • A properly-sized temperature-pressure relief valve must be installed in the opening provided. • Do not plug, block, or cap the discharge line. • Failure to follow this warning can result in excessive tank pressure, serious injury or death.
18 GAS SUPPLY AND PIPING Gas Requirements Read the data plate to be sure the water heater is made for the type of gas being used. This information will be found on the data plate located on the front of the water heater. If the information does not agree with the type of gas available, do not install or operate the water heater. Call your dealer. Note: An odorant may be added by the gas supplier to the gas used by this water heater. This odorant may fade over an extended period of time. Do not depend upon this odorant as an indication of leaking gas. Gas Piping The gas piping must be installed according to all local and state codes or in absence of local and state codes with the “National Fuel Gas Code”, ANSI Z223.1 (NFPA 54)-current edition. Canadian installations must be performed in accordance with CAN/CSA-B149.1-current edition. Note: If using a flexible gas connector, make sure its rating tag matches or exceeds the input of the water heater. Follow the instructions below and reference figure 19 for gas piping installation. 1. Install a readily accessible manual shut-off valve in the gas supply line as recommended by the local utility. Know the location of this valve and how to turn off the gas to this unit. 2. Install a drip leg as shown. The drip leg must be no less than 3 inches (7.62 cm) long for the accumulation of dirt, foreign material and water droplets. 3. Install a ground joint union between the water heater and the manual shut-off valve. This is to allow easy servicing. 4. Turn the gas supply on and check for leaks. Use a chloride-free soap and water solution (bubbles forming indicate a leak) or other approved method. 3” (7.62 cm) Minimum Figure 19: Gas Piping Installation Gas Pressure Important: The gas supply pressure must not exceed the maximum supply pressure as stated on the water heater’s data plate. Minimum supply pressure should also be maintained per the data plate. Explosion Hazard Use a new AGA or CSA approved gas supply line. Install a shut-off valve. Do not connect a natural gas water heater to a L.P. Gas Supply. Do not connect an L.P. gas water heater to a Natural Gas Supply. Failure to follow these instructions can result in death, explosion, or carbon monoxide poisoning.
19 Gas Pressure Testing Important: This water heater and its gas connection must be leak tested before placing the appliance in operation. • If the code requires the gas lines to be tested at a pressure of 14” W.C. (3.486 kPa) or greater, the water heater and its manual shut-off valve must be discon- nected from the gas supply piping system and the line capped. • If the gas lines are to be tested at a pressure less than 14” W.C. (3.486 kPa), the water heater must be isolated from the gas supply piping system by closing its manual shut-off valve. Nationally listed/recognized fuel gas and carbon monoxide(CO) detectors are recommended in all applications and should be installed using the manufacturer’s instructions and local codes, rules, or regulations. Note: Air may be present in the gas lines and could prevent the burner from lighting on initial start-up. The gas lines should be purged of air by a qualified service technician after installation of the gas piping system. Explosion Hazard Have a qualified person make sure that the L.P. gas operating pressure does not exceed 13” water column (3.237 kPa). Examples of a qualified person include licensed heating personnel, authorized gas company personnel, and authorized service personnel. Failure to do so can result in death, explosion, or fire.
20 Electrical Shock Hazard Disconnect power before servicing. Replace all parts and panels before operating. Failure to do so can result in death or electrical shock. ELECTRICAL CONNECTIONS Figure 20: Electrical Connections If you lack the necessary skills required to properly install the electrical wiring to this water heater, do not proceed but have a qualified electrician perform the installation. When making the electrical connections, always make sure: • The voltage and frequency correspond to that specified on the water heater data plate on the front of the water heater. • The electrical supply has the proper overload fuse or breaker protection. The heater draws less than 7 amps. • Wire sizes and connections comply with all applicable codes. • Wiring enclosed in approved conduit (if required by lo- cal codes). • The water heater and electrical supply are properly grounded. • This water heater must be “hard-wired” - do not use an extension cord to supply electrical power to this water heater. Note: The wiring diagram can be found on Page 21. Always reference the wiring diagram(s) for the correct electrical connections. When installing the electrical wiring to the water heater: 1. Shut off the power at the electrical service box. 2. Loosen the screws securing the access panel to the electrical compartment. (The electrical wiring diagram. models can be found on the inside of the access panel at the base of the water heater.) Set the access panel aside. 3. Connect the electrical supply to the water heater in accordance with local utility requirements and codes. Use only a dedicated electrical circuit containing a properly sized fuse or circuit breaker. Maximum over- load protection should not exceed 15 amperes. 4. Connect this circuit (directly from the electrical service box) to an electrical disconnect switch. 5. Ground the water heater by connecting the electrical service ground wire to the green ground wire (provided). Note: The power supply to this water heater must be properly polarized, [120 volts from the hot lead (black) to ground and 0 volts from the neutral lead (white) to ground] otherwise, the unit will not operate. 6. After making all electrical connections, completely fill the tank with water and check all connections for leaks. Open the nearest hot water faucet and let it run for 3 minutes to purge the water lines of air and sediment and to ensure complete filling of the tank. The electri- cal power may then be turned on. See figure 20 for completed installation.