Home > American Water Heater > Gas Heater > American Water Heater Polaris High Efficiency Commercial Gas Water Heater PCG3 User Manual

American Water Heater Polaris High Efficiency Commercial Gas Water Heater PCG3 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Water Heater Polaris High Efficiency Commercial Gas Water Heater PCG3 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							11
    INLET/OUTLET VENT TERMINATIONS
    Standard Horizontal Termination
    When 3 inch pipe is used between the water heater and the 
    outside wall, reduce it to 2 inch pipe before penetrating the 
    wall. A maximum of 18 inches (45.7 cm) of 2 inch pipe may 
    be used between the 3 inch transition and the inside of the 
    wall (see figure 7).
    The standard horizontal air inlet termination is a 2 inch 
    pipe which terminates at the exterior wall and utilizes a 
    coupling to prevent the pipe from being pushed back into the 
    structure. The standard horizontal exhaust outlet termination 
    is a 2 inch pipe which terminates 12 inches (30.5 cm) from 
    the outside wall. The air inlet must be located with respect to 
    the exhaust outlet as shown in figure 7 (bottom).
    Install a drain tee assembly and trap in the inlet vent as close 
    to the water heater as possible. This is to drain any water 
    that may be in the combustion air pipe and prevent it from 
    entering the blower.  Connect the trap drain line to a suitable 
    drain or downstream of the condensate trap of the water 
    heater.
    Note: See “Venting Additional Polaris
    ® Units” on Page 12 
    for correct terminations if installing more than one Polaris® 
    gas water heater.  
    Alternative Horizontal Termination
    The combustion air and exhaust terminations may be 
    raised up to 24 inches (61 cm) above the wall penetrations 
    if required for anticipated snow levels (see figure 8).  The 
    two elbows shown in figure 8 are considered part of the 
    termination and should not be included when determining 
    the maximum allowable vent pipe length.
    Note: See “Venting Additional Polaris
    ® Units” on Page 12 
    for correct terminations if installing more than one Polaris® 
    gas water heater.  
    (30.5 cm)
    24”
    (61 cm)
    Max.
    (76.2 cm)
    Figure 7: Standard Horizontal Termination
    3” (7.6cm) Max.
    4” (10 cm) 
    Max.
    4” (10 cm) 
    Max.12” (30.5 cm) 
    2” 
    Coupling  
    12” (30.5cm) Min. Above
    Grade or Anticipated
    Snow Level.  See
    Note 4.
    Notes:
    1.  Support Horizontal Pipe Every 
    Four Feet (1.2 m).  Support Vertical 
    Pipe Every Six Feet (1.8 m).
    2.  When Using 3 Inch Pipe,  Reduce To 2 Inches Before 
    Penetrating The Outside Wall.
    3.  18 Inch (45.7 cm) Maximum When Using 3 Inch Pipe.
    4.  Increase The 12 Inch (30.5 cm) Minimum Above 
    Grade To Keep Terminal Openings Above Anticipated 
    Snow Levels.
    5.   Slope All Piping Down Toward the Water Heater as 
    Follows: 
     
    						
    							12
    VERTICAL TERMINATIONS
    When 3 inch pipe is used between the water heater and the 
    roof, reduce it to 2 inch pipe before penetrating the roof. 
    A maximum of 18 inches (45.7 cm) of 2 inch pipe may be 
    used between the 3 inch transition and the inside of the 
    roof.
    The vertical inlet air termination requires a return bend 
    or two short or long sweep radius 90 elbows to keep the 
    inlet downward and prevent entry of rain. These elbows 
    are considered part of the termination and should not be 
    included when calculating the maximum allowable vent 
    pipe length. Refer to figure 9 for the proper location of the 
    air inlet with respect to the exhaust outlet termination. The 
    vertical exhaust outlet termination is a 2 inch (30.5 cm) pipe which terminates at least 12 inches (30.5 cm) above the 
    inlet air termination.
    The air inlet and exhaust outlet terminations must be at 
    least 12 inches (30.5 cm) above the roof line or anticipated 
    snow levels.  See figure 9 below.
    Note: See “Venting Additional Polaris
    ® Units” below if 
    installing more than one Polaris® gas water heater.  
     
    Venting Additional Polaris® Units
    When using two (2) Polaris® units, install vent terminations 
    using either Method A or Method B below:When using three or more Polaris
    ® units, install vent 
    terminations per Method C or Method D:
    Figure 9: Vertical Termination
    Notes:
    1.  Support Horizontal Pipe Every 
    Four Feet (1.2 m).  Support Vertical 
    Pipe Every Six Feet (1.8 m).
    2.  When Using 3 Inch Pipe,  Reduce To 
    2 Inches Before Penetrating The 
    Roof.
    3.  18 Inch (45.7 cm) Maximum When 
    Using 2 Inch Pipe.
    4.  Increase The 12 Inch (30.5 cm) 
    Minimum Above Grade To Keep 
    Terminal  Openings Above Anticipated 
    Snow Levels.4” (10 cm)  Max.
    12” (30.5cm) Min. 
    Above Roof or 
    Anticipated Snow 
    Level.  See Note 4.12” (30.5 cm) Min. 
    12” (30.5 cm) 
    Min. 
    4” (10 cm)  
    Max.
    12” 
    (30.5 cm) 
    Min. 
    *
    *
    3” (7.6cm) Max.
    4” (10cm) 
    Max.
    3” 
    (7.6 cm) 
    Max.
    4” 
    (10cm) 
    Max.36” (91.4 cm) 
    Minimum3” (7.6 cm) Max.
    4” 
    (10cm) 
    Max.
    3” 
    (7.6 cm) 
    Max.
    4” 
    (10cm) 
    Max. 4” 
    (10cm) 
    Max.36” (91.4 cm) 
    Minimum
    4” 
    (10cm) 
    Max.4” 
    (10cm) 
    Max.4” 
    (10cm) 
    Max.
    36” (91.4 cm) 
    Minimum36” (91.4 cm) 
    Minimum
    Figure 9A, 9BFigure 9C, 9D 
    						
    							13
    CONCENTRIC VENT TERMINATIONS
    For new installations, install 2” Concentric vent kit model 
    KGAVT0501CVT, part number 6910542.  See Manufacturer’s 
    instructions for complete installation or call customer service at 
    1-800-456-9805 for assistance or go to www.americanwaterheater.com.   
    For planning purposes, see figures 10-13 below for vent terminal 
    specifications.
    Note:  For replacement installations, previously installed 
    American Water Heater Company supplied concentric vent kits 
    are acceptable for use on 100,000-130,000 BTU/Hr models only. 
    Make sure that the existing vent complies with current codes.
    (14.6cm)
    (15.7cm)
    (8.9cm Dia.)
    (42.2cm)
    (84.77cm)(4.8cm)(3.8cm)
    Figure 10: 2 Inch Concentric Vent
    (2.54cm)
    Figure 11: Through the Wall Termination
    12” (30.5cm) Minimum 
    clearance above 
    anticipated snow level.  
    24” (61cm) Max.
    Figure 12: Through the Roof Termination
    Notes:
    1.  Support Horizontal Pipe Every 
    Four Feet (1.2 m).  Support 
    Vertical Pipe Every Six ft. (1.8 m).
    4.  Increase The 12 Inch (30.5 cm) 
    Minimum Above Grade To Keep 
    Inlet Opening Above Anticipated 
    Snow Levels.
    5.   Slope All Piping Down Toward 
    the Water Heater as follows: 
     
    						
    							14
    Figure 14: Input GraphGas Input Rate
    The gas input rate of this water heater is affected by 
    several environmental factors such as:
    • The heating value of the gas
    • The air and gas densities (which vary widely due to baro-
    metric pressure and temperature changes)
    • Venting installations (pipe diameter, length and fittings)
    • Altitude
    When measuring the input rate these factors should be 
    incorporated into the calculations. Also measure the gas 
    consumption over a sufficiently long time to obtain an 
    accurate gas consumption rate (e.g. 3-5 minutes, not one 
    revolution of the meter needle).
    Long vents and each additional elbow, inherently reduce 
    the gas input rate due to increased resistance to moving 
    combustion air and flue gases. The approximate maximum/
    minimum input for the 100k, 130k, and 150k models is 
    shown in figure 15.
    WATER PIPING SYSTEM
    Piping Installation
    Piping, fittings, and valves should be installed according to 
    the installation drawing (figure 15). If the indoor installation 
    area is subject to freezing temperatures, the water piping 
    must be protected by insulation. 
    The water supply pressure should not exceed 80 psi 
    (551.5 kPa). If this occurs, a pressure reducing valve with a 
    bypass should be installed in the cold water inlet line. This 
    should be placed on the supply to the entire house in order 
    to maintain equal hot and cold water pressures.
    Important: Heat cannot be applied to the water fittings 
    on the heater as they may contain nonmetallic parts. 
    If solder connections are used, solder the pipe to the 
    adapter before attaching the adapter to the hot and 
    cold water fittings. 
    Important:  Do not install this water heater with iron or 
    galvanized piping.  Use brass caps on all unused inlet/
    outlet connections. 
    1.  Install the water piping and fittings as shown in figure 
    15. Note: If state or local codes require, install a vacu-
    um relief valve per the manufactures instructions in the 
    cold water supply line. Connect the cold water supply 
    (use 1” NPT) to the fitting marked “COLD INLET”.  
    Do not turn the cold water nipple. The mark should         
    remain along the top side of the nipple. Connect the 
    hot water supply (use 1” NPT) to the fitting marked 
    “HOT OUTLET”. 
    2.  Always use a suitable grade of joint compound and be 
    certain that all fittings are tightened properly.
    3.  The installation of unions in both the hot and cold water 
    supply lines is recommended for ease of removing the 
    water heater for service or replacement.
    4.  If installing the water heater in a closed water system, 
    install an expansion tank in the cold water line as speci-
    fied under “Closed System/Thermal Expansion” (Page 
    15).
    5.  Install a shut-off valve in the cold water inlet line.  It 
    should be located close to the water heater and be 
    easily accessible. Know the location of this valve and 
    how to shut off the water to the heater.6. The Polaris
    ® gas water heater is shipped with a factory-
    installed Temperature and Pressure Relief Valve.  
    Install a discharge line in the opening in the T & P valve 
    (see instructions on Page 17).
    7.  After piping has been properly connected to the water  
    heater, remove the aerator at the nearest hot water    
    faucet.  Open the hot water faucet and allow the tank  
    to completely fill with water. (To prevent damage to 
    the unit, DO NOT connect power until the tank is 
    COMPLETELY FILLED). To purge the lines of any  
    excess air, keep the hot water faucet open for 3 min-
    utes after a constant flow of water is obtained. Close 
    the  faucet and check all connections for leaks.
    Corrosion and Water Quality
    Water quality will vary from location to location and may 
    contain contaminates that may reduce the life or perfor-
    mance of the water heater. To test for contaminates a 
    water quality test kit is available, reference part number 
    6903791.
    Contaminates which can reduce the life or performance 
    of the water heater if present in high quantities include 
    those which contribute to hardness (dissolved minerals 
    such as sodium, calcium and magnesium); plus chlorides 
    and sulfates. Additionally, water that is too acidic or basic 
    (measured as pH) can reduce the life of the water heater. 
    Water treatment systems (such as water softeners for 
    hardness) should be used and maintained properly if the 
    contaminate levels exceed the following:
    Warranty is void in applications which exceed the 
    water quality requirements listed below.
    Table 2:
    Total Hardness:12 grains per gal. (205 mg/liter) max.
    Chloride: 200 mg/liter max.
    pH: 6.5-8.0
    Alkalinity: 200 mg/liter max. 
    						
    							15
    Figure 15: Typical One-Temperature System Piping Installation
    Mixing Valve Installation
    A mixing valve has been provided for use with the 
    Polaris®  Gas water heater and must be installed, per the 
    manufacturer’s instructions, in the domestic hot water line.  
    See Figure 16 for a sample tempering valve installation.
    General Information
    Water piping, fittings, and valves must be properly installed 
    for the correct and safe operation of this water heater. 
    Please note the following:
    •  The system should be installed only with piping that is 
    suitable for potable (drinking) water such as copper, 
    CPVC, PEX or polybutylene. PVC water piping may be 
    used on the cold water   inlet supply but not within 18 
    inches (45.7 cm) of the cold water connection on the 
    water heater.  
    •  Do not use PVC piping on the hot water outlet,      
    space heating supply, or space heating return.
    •  Do not use any pumps, valves, or fittings that are      
    not compatible with potable water.
    •  Do not use valves that may cause excessive      
    restriction to water flow. Use full flow ball or gate      
    valves only.
    •  Do not use 50/50 tin-lead solder (or any lead based    
    solder) in potable water lines. Use 95/5 solder or      
    other equivalent material.
    •  Do not tamper with the thermostat, gas valve,     
    blower, electrical components, or temperature and   
    pressure relief valve. Tampering with any of the      
    components is dangerous and can result in death,   
    severe injury, or property damage. Tampering voids  
    all warranties. Only qualified technicians should     
    service these components.
    •  Do not use this water heater as a replacement for an 
    existing boiler installation.
    •  Do not use with piping that has been treated with      
    chromates, boiler seal, or other chemicals.
    •  Do not add any chemicals to the system piping      
    which will contaminate the potable water supply.
    Closed System/Thermal Expansion
    As water is heated, it expands (thermal expansion). In a 
    closed system, the volume of water will increase. As the 
    volume of water increases, there will be a correspond-
    ing increase in water pressure due to thermal expansion.  
    Thermal expansion can cause premature tank failure (leak-
    age). This type of failure is not covered under the limited 
    warranty. Thermal expansion can also cause intermittent 
    temperature-pressure relief valve operation; water dis-
    charged from the valve due to excessive pressure build up. 
    The temperature-pressure relief valve is not intended for 
    the constant relief of thermal expansion. This condition is 
    not covered under the limited warranty.  
    A properly-sized thermal expansion tank should be 
    installed on all closed systems to control the harmful 
    effects of thermal expansion. Contact a plumbing service 
    agency or your retail supplier regarding the installation of a 
    thermal expansion tank.  The manufacturer of this water 
    heater will void the warranty if there is a failure to 
    install a properly sized expansion tank. 
    Combination Space Heating/Potable 
    Water System 
    Some water heater models are equipped with inlet/
    outlet connections for use in space heating applications.       
    Note: this water heater, “Suitable for combination water 
    (potable) heating and space heating and not suitable for 
    space heating applications only.” If this water heater is to be 
    used to supply both space heating and potable (drinking) 
    water, the instructions listed below must be followed (see 
    figure 17).
    •  Be sure to follow the manual(s) shipped with the  air 
    handler or other type heating system.
    •  This water heater is not to be used as a replacement  
    for an existing boiler installation.
    Check local codes.
    (set to 120° F 
    [48.8° C] or lower)
    Figure 16: Sample Mixing
    Valve Installation
    Mixing Valve
    Mixing Valve
    Metal Drain Pan6” (15.2cm) 
    Air Gap Max.
    Adequate Drain 
    						
    							16 •  Do not use with piping that has been treated with 
    chromates, boiler seal or other chemicals and do not 
    add any chemicals to the water heater piping.
    •  If the space heating system requires water temperatures 
    in excess of 120°F (48.9°C), a mixing valve (provided) 
    must be installed per the manufacturer’s instructions 
    in the potable hot water supply to limit the risk of scald 
    injury.
    •  Pumps, valves, piping and fittings must be compatible  
    with potable water.
    •  A properly installed flow control valve is required to pre-
    vent thermosiphoning. Thermosiphoning is the result 
    of a continuous flow of water through the air handler  
    circuit during the off cycle. Weeping (blow off) of the  
    temperature and pressure relief valve (T & P) or higher  
    than normal water temperatures are the first signs of    
    thermosiphoning.
    •  The hot water line from the water heater should be ver-
    tical past any mixing valve or supply line to the heating 
    system to remove air bubbles from the system.
    • Do not connect the water heater to any system or 
    components previously used with non-potable water   
    heating appliances when used to supply potable water.
    Storage Tank Installation 
    When installing the Polaris® with a storage tank, see figure 
    18 for piping suggestions.
    Solar Installation
    If this water heater is used as a solar storage heater or as 
    a backup for the solar system, the water supply tempera-
    tures to the water heater tank may be in excess of 120°F 
    (48.9°C). A mixing valve must be installed in the water sup-
    ply line to limit the supply temperature to 120°F (48.9°C).
    Note:  Solar water heating systems can often supply water 
    with temperatures exceeding 180°F (82.2°C) and may 
    result in water heater malfunction.
    Figure 17: Air Handler Piping Installation
    Mixing Valve
    Metal Drain Pan
    6” (15.2cm) 
    Air Gap Max.
    Adequate Drain
    Massachusetts code does not allow this type of installation. 
    						
    							17
    Temperature and Pressure 
    Relief Valve
    For protection against excessive pressures and tempera-
    tures, a temperature and pressure relief valve must be 
    installed in the opening marked “T & P RELIEF VALVE”.  
    This valve must be design certified by a nationally recog-
    nized testing laboratory that maintains periodic inspection 
    of the production of listed equipment or materials as meet-
    ing the requirements for Relief Valves and Automatic Shut-off Devices for Hot Water Supply Systems, ANSI Z21.22. 
    The function of the temperature and pressure relief valve is 
    to discharge water in large quantities in the event of exces-
    sive temperature or pressure developing in the water heat-
    er. The valve’s relief pressure must not exceed the working 
    pressure of the water heater as stated on the data plate.
    Important:  Only a new temperature and pressure relief 
    valve should be used with this water heater. Do not use 
    an old or existing valve as it may be damaged or not ade-
    quate for the working pressure of the new water heater. Do 
    not place any valve or piping between the relief valve and 
    the tank.
    The Temperature & Pressure Relief Valve:   
    •  Must not be in contact with any electrical part.
    •  Must be connected to an adequate discharge line.
    •  Must not be rated higher than  the working pressure  
    shown on the data plate of the water heater.
    •  The BTUH rating of the T & P valve must be  greater 
    than, or equal to, the input rating of the water heater
    The Discharge Line:
    •  Must not be smaller than the pipe size of the relief 
    valve or have any reducing coupling installed in the 
    discharge line.
    •  Must not be capped, blocked, plugged or contain any 
    valve between the relief valve and the end of the dis-
    charge line.
    •  Must terminate a maximum of 6 inches (15.2 cm) 
    above a floor drain or external to the building.
    •  Must be capable of withstanding 250°F (121°C) without 
    distortion.
    •  Must be installed to allow complete drainage of both 
    the valve and discharge line.
    Mixing
    ValveTank 
    Temperature
    Control
    (170°F [76.6°C] Max.)
    (If Used)
    Figure 18: Polaris® with Auxillary Storage Tank - One or Two 
    Temperature System (With or Without Building Recirculation)Notes on Figure 18:
    If tank temperature is set above 
    120°F (48.9°C) and water is sup-
    plied for domestic use (hand wash-
    ing, showering, etc.) a mixing valve 
    must be installed in the hot water 
    line to domestic fixtures.
    Installation must conform to local 
    code requirements. If a check valve 
    is installed in the cold water sup-
    ply line, an expansion tank must be 
    installed between the check valve 
    and the water heater’s cold water 
    inlet.  Set storage tank temperature 
    five degrees lower than the water 
    heater’s temperature setting.  Using 
    the plug valve in the recirculating 
    line, adjust the flow in the recirculat-
    ing line to five gallons per minute.
    Explosion Hazard
    • Temperature-pressure relief valve must 
    comply with ANSI Z21.22-CSA 4.4 and 
    ASME code.
    • A properly-sized temperature-pressure 
    relief valve must be installed in the 
    opening provided.
    • Do not plug, block, or cap the discharge 
    line.
    • Failure to follow this warning can result in 
    excessive tank pressure, serious injury 
    or death. 
    						
    							18
    GAS SUPPLY AND PIPING
    Gas Requirements
    Read the data plate to be sure the water heater is made 
    for the type of gas being used.  This information will be 
    found on the data plate located on the front of the water 
    heater. If the information does not agree with the type of 
    gas available, do not install or operate the water heater. 
    Call your dealer.
    Note:  An odorant may be added by the gas supplier to 
    the gas used by this water heater. This odorant may fade 
    over an extended period of time. Do not depend upon this 
    odorant as an indication of leaking gas.
    Gas Piping
    The gas piping must be installed according to all local and 
    state codes or in absence of local and state codes with the 
    “National Fuel Gas Code”, ANSI Z223.1 (NFPA 54)-current 
    edition. Canadian installations must be performed in 
    accordance with CAN/CSA-B149.1-current edition.      
    Note:  If using a flexible gas connector, make sure its rating 
    tag matches or exceeds the input of the water heater.
    Follow the instructions below and reference figure 19 for 
    gas piping installation.
    1.  Install a readily accessible manual shut-off valve in the 
    gas supply line as recommended by the  local utility. 
    Know the location of this valve and how to turn off the 
    gas to this unit.
    2.  Install a drip leg as shown. The drip leg must be no  
    less than 3 inches (7.62 cm) long for the accumulation 
    of dirt,   foreign material and water droplets.
    3.  Install a ground joint union between the water heater  
    and the manual shut-off valve.  This is to allow easy  
    servicing.
    4.  Turn the gas supply on and check for leaks. Use a 
    chloride-free soap and water solution (bubbles forming 
    indicate a leak) or other approved method.
    3” (7.62 cm)
    Minimum 
    Figure 19: Gas Piping Installation
    Gas Pressure
    Important: The gas supply pressure must not exceed the 
    maximum supply pressure as stated on the water heater’s 
    data plate.  Minimum supply pressure should also be 
    maintained per the data plate. 
    Explosion Hazard
    Use a new AGA or CSA approved gas 
    supply line.
    Install a shut-off valve.
    Do not connect a natural gas water 
    heater to a L.P. Gas Supply.
    Do not connect an L.P. gas water heater 
    to a Natural Gas Supply.
    Failure to follow these instructions can 
    result in death, explosion, or carbon 
    monoxide poisoning. 
    						
    							19
    Gas Pressure Testing
    Important: This water heater and its gas connection must 
    be leak tested before placing the appliance in operation.  
    • If the code requires the gas lines to be tested at  a 
    pressure of 14” W.C. (3.486 kPa) or greater, the water 
    heater and its manual shut-off valve must be discon-
    nected  from the gas supply piping system and the line  
    capped.
    • If the gas lines are to be tested at a pressure less   
    than 14” W.C. (3.486 kPa), the water heater must be 
    isolated from the gas supply piping system by closing 
    its manual shut-off valve.
    Nationally listed/recognized fuel gas and carbon 
    monoxide(CO) detectors are recommended in 
    all applications and should be installed using the 
    manufacturer’s instructions and local codes, rules, or 
    regulations.
    Note: Air may be present in the gas lines and could prevent 
    the burner from lighting on initial start-up. The gas lines 
    should be purged of air by a qualified service technician 
    after installation of the gas piping system.   
    Explosion Hazard
    Have a qualified person make sure that 
    the L.P. gas operating pressure does not 
    exceed 13” water column (3.237 kPa).
    Examples of a qualified person include 
    licensed heating personnel, authorized 
    gas company personnel, and authorized 
    service personnel.
    Failure to do so can result in death, 
    explosion, or fire. 
    						
    							20
    Electrical Shock Hazard
    Disconnect power before
    servicing.
    Replace all parts and panels
    before operating.
    Failure to do so can result in 
    death or electrical shock.
    ELECTRICAL CONNECTIONS
    Figure 20: Electrical Connections
    If you lack the necessary skills required to properly install 
    the electrical wiring to this water heater, do not proceed but 
    have a qualified electrician perform the installation.
    When making the electrical connections, always make 
    sure:
    • The voltage and frequency correspond to that specified 
    on the water heater data plate on the front of the water 
    heater.
    • The electrical supply has the proper overload fuse  
    or breaker protection.  The heater draws less than 7 
    amps.
    • Wire sizes and connections comply with all applicable 
    codes.
    • Wiring enclosed in approved conduit (if required by lo-
    cal codes).
    •  The water heater and electrical supply are properly    
    grounded.
    •  This water heater must be “hard-wired” - do not use an 
    extension cord to supply electrical power to this water 
    heater.
    Note:
    The wiring diagram can be found on Page 21.  Always 
    reference the wiring diagram(s) for the correct electrical 
    connections. 
    When installing the electrical wiring to the water heater:
    1.  Shut off the power at the electrical service box.
    2.  Loosen the screws securing the access panel to  the 
    electrical compartment. (The electrical wiring diagram. 
    models can be found on the inside of the access panel 
    at the base of the water heater.) Set the access panel 
    aside. 
    3.  Connect the electrical supply to the water heater in 
    accordance with local utility requirements and codes.  
    Use only a dedicated electrical circuit containing a 
    properly sized fuse or circuit breaker. Maximum over-
    load protection should not exceed 15 amperes. 4.  Connect this circuit (directly from the electrical  service 
    box) to an electrical disconnect switch. 
    5.  Ground the water heater by connecting the electrical  
    service ground wire to the green ground wire (provided).
    Note:  The power supply to this water heater must be 
    properly polarized, [120 volts from the hot lead (black) to 
    ground and 0 volts from the neutral lead (white) to ground] 
    otherwise, the unit will not operate.
    6.  After making all electrical connections, completely fill    
    the tank with water and check all connections for leaks.  
    Open the nearest hot water faucet and let it run for 3    
    minutes to purge the water lines of air and sediment     
    and to ensure complete filling of the tank.  The electri-
    cal power may then be turned on.  See figure 20 for 
    completed installation.  
    						
    All American Water Heater manuals Comments (6)

    Related Manuals for American Water Heater Polaris High Efficiency Commercial Gas Water Heater PCG3 User Manual