Home > American Water Heater > Gas Heater > American Water Heater Polaris High Efficiency Commercial Gas Water Heater PCG3 User Manual

American Water Heater Polaris High Efficiency Commercial Gas Water Heater PCG3 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Water Heater Polaris High Efficiency Commercial Gas Water Heater PCG3 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							1
    Polaris® 
    Commercial Gas 
    Water Heater
    Installation 
    Instructions and 
    Use & Care Guide
    To obtain technical, warranty or service assistance during or 
    after the installation of this water heater, visit our website at:
    http://www.americanwaterheater.com
    or call toll free: 
    1-800-456-9805
    When calling for assistance, please have the following 
    information ready:
    1. Model number
    2.  7 Digit product number
    3. Serial number
    4.  Date of installation
    5.   Place of Purchase
    Table of Contents...........................................................  2
    Do not store or use gasoline or other 
    flammable vapors and liquids in the 
    vicinity of this or any other appliance.
    WHAT TO DO IF YOU SMELL GAS
      •  Do not try to light any appliance.
      •  Do not touch any electrical switch;  
        do not use any telephone in your  
      building.
      •  Immediately call your gas supplier  
        from a neighbor’s telephone. Follow  
        the gas supplier’s instructions.
      •  If you cannot reach your gas 
        supplier, call the fire department.
    Installation and service must be performed 
    by a qualified installer, service agency or 
    the gas supplier.
    WARNING:  If the information in these
    instructions is not followed exactly, a fire 
    or explosion may result causing property 
    damage, personal injury or death.
    322762-001
    INSTALLER:
    •  Affix these instructions to or adjacent to the water 
    heater.
    OWNER:
    •  Retain these instructions and warranty for future 
    reference. Retain the original receipt as proof of 
    purchase.
    PRINTED IN U.S.A.  0514
    LOW LEAD
    CONTENT
    This manual covers model numbers:
       United States
       PGC* 34-100-2NV or 2PV
       PGC* 34-130-2NV or 2PV
       PGC* 34-150-2NV or 2PV
       PGC* 50-130-2NV or 2PV
       PGC* 50-150-2NV or 2PV
       PGC* 50-175-3NV or 3PV
       PGC* 50-199-3NV or 3PV
      * Indicates warranty period
     Note:
     The manufacturer of this water heater recommends that it     
     be professionally installed by trained and qualified service  
     professionals. 
    						
    							2
    Your safety and the safety of others are very important.
    We have provided many important safety messages in this manual and on your appliance. Always read and obey all 
    safety messages.
    This is the safety alert symbol.
    This symbol alerts you to potential hazards that can kill or hurt you and others.
    All safety messages will follow the safety alert symbol and either the word “DANGER” or
    “WARNING.” These words mean:
    Indicates an imminently hazardous situation which, if not 
    avoided, will result in death or injury.
    Indicates a hazardous situation which, if not avoided, 
    could result in death or serious injury.
    All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you 
    what can happen if the instructions are not followed.
    Important Instructions
    •  Do not use this water heater if any part has been under water. Immediately call a qualified service technician.   
      Water heaters subjected to flood conditions or anytime the gas controls, main burner or ignition control have been  
      submerged in water require replacement of the entire water heater.
    •  Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally  
      two weeks or more). Hydrogen gas is extremely flammable and can ignite when exposed to a spark or flame. To  
      prevent the possibility of injury under these conditions, we recommend the hot water faucet be opened for several  
      minutes at the kitchen sink before using any electrical appliance which is connected to the hot water system. If  
      hydrogen is present, there will probably be an unusual sound such as air escaping through the faucet as water  
      begins to flow. Do not smoke or have any open flame near the faucet at the time it is open.
    The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of 
    substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires 
    businesses to warn of potential exposure to such substances.
    Warning:  This product contains a chemical known to the State of California to cause cancer, birth defects, or other 
    reproductive harm. 
    This appliance can cause low-level exposure to some of the substances listed in the act.
    Water Heater Safety  ............................................................................ 1-2
    Installation Instructions  ...................................................................... 3-22
       Unpacking the Water Heater  ............................................................ 3
      State of Massachusetts Installation Requirements  ........................... 4
      Location Requirements  ..................................................................... 5
       Condensate Line   ........................................................................... 6-7
       Intergrated Filter Installation   ............................................................ 8
      Vent Pipe System  ........................................................................ 9-12
     Vent Terminations  ...................................................................... 10-13
      Gas Input Rate  ................................................................................ 14
      Water System Piping  ................................................................. 14-17
      Gas Supply and Piping   ............................................................. 18-19
      Electrical Connections/Wiring Diagram  ..................................... 20-21
      Installation Checklist  ....................................................................... 22
    Operating Your Water Heater  .......................................................... 23-25
    Polaris® Operating Instructions   ........................................................... 24
    Maintenance of Your Water Heater  ................................................. 25-26
    Troubleshooting  .................................................................................... 27
    Software Operation Sequence  ............................................................. 28
    Parts List and Diagram  ......................................................................... 29
    Polaris
    ® Models and Dimensions .......................................................... 30
    Table of Contents          Page 
    						
    							3
    INSTALLATION INSTRUCTIONS
    Consumer Information
    OBSERVE ALL GOVERNING CODES AND ORDINANCES.
    This water heater is design-certified by CSA International 
    as a Category IV, direct vented water heater which takes 
    its combustion air from the outside of the structure and 
    exhausts all products of combustion to the outside of the 
    structure.
    This water heater must be installed according to all local 
    and state codes or in the absence of local and state codes 
    with the “National Fuel Gas Code”, ANSI Z223.1(NFPA 
    54)- current edition. Canadian installations must be per-
    formed in accordance with CAN/CSA-B149.1 -current edi-
    tion. This is available from the following:
    CSA America,  Inc.
    8501 East Pleasant Valley Road
    Cleveland, OH 44131
    National Fire Protection Agency
    1 Batterymarch Park
    Quincy, MA 02169-7471
    Canadian Standards Association
    178 Rexdale Boulevard
    Toronto, ON M9W 1R3
    Check the phone listings for the local authorities having 
    jurisdiction over this installation.
    Installer and Owner Responsibilities
    This manual has been prepared to acquaint you with the 
    installation, operation, and maintenance of your gas water 
    heater and provide important safety information in these 
    areas. 
    Read all of the instructions thoroughly before attempting 
    the installation or operation of this water heater. 
    Do not discard this manual. You or future users of this 
    water heater will need it for future reference.
    Service to the water heater should only be performed 
    by a qualified service technician.
    Examples of qualified service technicians include: 
    those trained in the plumbing and heating industry, 
    local gas utility personnel, or an authorized service 
    person.
    The manufacturer and seller of this water heater will 
    not be liable for any damages, injuries, or deaths 
    caused by failure to comply with the installation and 
    operating instructions outlined in this manual. 
    If you lack the necessary skills required to properly install 
    this water heater, or you have difficulty following the 
    instructions, you should not proceed but have a qualified 
    service technician perform the installation of this water 
    heater.
    Unpacking the Water Heater
    Removing Packaging Materials
    Important: Do not remove any permanent instructions, 
    labels, or the data plate from outside of the water heater or 
    on the inside of panels.
    •  Remove exterior packaging and place installation  
    components aside.
    •  Inspect all parts for damage prior to installation and 
    start-up.
    •  Completely read all instructions before attempting to 
    assemble and install this product.
    •  After installation, dispose of packaging material in the 
    proper manner.
    Excessive Weight Hazard
    Use two or more people to move and 
    install water heater unless proper 
    handling equipment is utilized.
    Failure to do so can result in back or 
    other injury.
    A data plate identifying your water heater can be found on 
    the front of the heater. When referring to your water heater, 
    always have the information listed on the data plate readily 
    available.
    Massachusetts code requires this water heater to be 
    installed in accordance with Massachusetts Plumbing and 
    Fuel Gas Code 248 CMR section 2.00 and 5.00. See page 
    4 in this manual for the Commonwealth of Massachusetts 
    installation requirements.
    This product is certifield to comply with a maximum weight-
    ed average of 0.25% lead content as required in some 
    areas.
    Keep combustibles such as boxes, magazines, clothes, 
    etc., away from water heater area.
    Retain your original receipt as proof of purchase. 
    						
    							4
    For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters 
    installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or 
    operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished 
    grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 
    INSTALLATION OF CARBON MONOXIDE DETECTORS  At the time of installation of the side wall horizontal vented gas 
    fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm 
    and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber 
    or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each 
    additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It shall 
    be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard 
    wired carbon monoxide detectors.
    In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired 
    carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
    In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall 
    have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a 
    battery operated carbon monoxide detector with an alarm shall be installed.
    APPROVED CARBON MONOXIDE DETECTORS  Each carbon monoxide detector as required in accordance with the above 
    provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certified. 
    SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum 
    height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heat-
    ing appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY 
    BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
    INSPECTION  The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the 
    installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance 
    with the provisions of 248 CMR 5.08(2)(a) 1 through 4. 
    EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 
    1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 
    54 as adopted by the Board; and 
    2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the 
    dwelling, building, or structure used in whole or in part for residential purposes. 
    MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED When the manufacturer of Product 
     Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with 
    the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall 
    include:
    1. Detailed instructions for the installation of the venting system design or the venting system components; and
    2. A complete parts list for the venting system design or venting system. 
    MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED  When the manufacturer of 
    a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, 
    but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:
    1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation
     instructions; and 
    2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a 
    parts list and detailed installation instructions. 
    A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting 
    instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or 
    equipment at the completion of the installation. 
    INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS 
    						
    							5
    Location Requirements
    The water heater design has been tested by CSA 
    International and complies with ANSI Z21.10.1, Section 
    2.35 Flammable Vapors Resistance.  In garage installation 
    avoid damage to your water heater by installing a vehicle 
    stop as shown in figure below.  Check state and local 
    codes for requirements prior to installation.Important:  The water heater should be located in 
    an area where leakage of the tank or connections will 
    not result in damage to the area adjacent to the water 
    heater or to lower floors of the structure. Due to the 
    normal corrosive action of the water, the tank will 
    eventually leak after an extended period of time. 
    Also any external plumbing leak, including those 
    from improper installation, may cause early failure 
    of the water tank due to corrosion if not repaired. 
    A qualified service technician should be contacted 
    for repairs.  A suitable metal drain pan should be 
    installed under the water heater as shown below, to 
    help protect the property from damage which may 
    occur from condensate formation or leaks in the piping 
    connections or tank. The pan must limit the water level 
    to a maximum depth of 1-3/4” (4.45 cm) and be at least 
    two inches (5 cm) wider than the heater and piped to an 
    adequate drain. Locate the water heater near a suitable 
    indoor drain. Outside drains are subject to freezing 
    temperatures which can obstruct the drain line. The 
    piping should be at least 3/4” (1.91 cm) ID and pitched 
    for proper drainage. Under no circumstances will the 
    manufacturer or seller of this water heater be held liable 
    for any water damage which is caused by your failure to 
    follow these instructions.
    •  The water heater should be located in an area not sub-
    ject to freezing temperatures. Water heaters  located in 
    unconditioned spaces (i.e., attics,  basements, etc) may 
    require insulation of the  water piping and drain piping 
    to protect against freezing. The drain and controls must 
    be easily accessible for operation and service. Maintain 
    proper clearances as specified on the data plate. 
    Figure 1: Garage Installation 
    Do not store or use gasoline or other 
    flammable vapors and liquids in the vicinity 
    of this or any other appliance. Storage of or 
    use of gasoline or other flammable vapors 
    or liquids in the vicinity of this or any other 
    appliance can result in serious injury or death
    FIRE AND EXPLOSION HAZARD
    Can result in serious injury or death
    This water heater is not certified for installation in mobile 
    homes.
    Note: In the State of California, the water heater must be 
    braced, anchored, or strapped to avoid moving during an 
    earthquake. Contact local utilities for code requirements in 
    your area or call 1-800-456-9805 and request instructions.
    Site Location
    •  Select a location near the center of the water piping 
    system. The water heater must be installed   indoors 
    and in a vertical position on a level surface. DO NOT 
    install in bathrooms, bedrooms, or any occupied room 
    normally kept closed. Note: The water heater may be 
    installed in a closet with a door off a bedroom or bath-
    room providing the units are installed and vented per 
    the manufacturer’s instructions.•  Consider the inlet and exhaust vent system piping  
    when selecting the water heater location.  The venting 
    system must be able to run from the water heater to 
    the termination with a minimal length and number of 
    elbows.  Input rates are reduced as vent system length 
    increases.  The venting system must comply with the 
    requirements  set forth in the venting section of this 
    manual.
    •  Locate the water heater near the existing gas piping. 
    If installing a new gas line, locate the water heater to 
    minimize the pipe length and elbows.
    Important:  Air for combustion and ventilation must not 
    come from a corrosive atmosphere.  Any failure due to cor-
    rosive elements in the atmosphere is excluded from war-
    ranty coverage.
    Note:  The water heater must be installed according to all 
    local and state codes or in absence of the local and state 
    codes with the “National Fuel Gas Code”, ANSI Z223.1 
    (NFPA 54)-current edition.  Canadian installations must be 
    performed in accordance with CAN/CSA-B149.1-current 
    edition. 
    1-3/4” (4.45 cm) Max.
    (5 cm)
    Figure 1A 
    						
    							6
    CONDENSATE LINE
    Important:  Do not run the condensate drain in areas 
    that are likely to freeze. Frozen condensate will block the 
    drain line and result in property damage or water heater 
    malfunction.
    Condensate Trap Assembly
    A condensate trap/drain stem assembly has been supplied 
    with the water heater and is located behind the access door 
    inside the base of the water heater.  This assembly must be 
    installed between the water heater and the exhaust outlet 
    piping to ensure proper operation of the water heater. To 
    install, remove the slip-joint nut, stainless steel washer, and 
    O-ring from the trap assembly.  Slip the nut, washer and 
    O-ring (in that order) over the stainless exhaust tubing and 
    slide them back near the base of the heater.  Insert the trap 
    assembly over the tubing (see figure 3A accordingly) and 
    firmly hand-tighten (using a wrench will cause the O-ring to 
    seal improperly) the nut to form a water-tight seal between 
    the O-ring and the stainless exhaust tubing.  When 
    tightened, the nut to heater base clearance should be 3/4” 
    (+/- 1/8”) tolerance (1.9 cm +/- 0.31 cm tolerance).
    Note:  The trap should be aligned so that the exhaust pipe 
    is in a vertical position close to the surface of the water 
    heater.
    Figure 2: Minimum Clearance Locations 
    Back 0” (0 cm)
    Sides: 4” (10.2 cm) 
    Min. for service
    Front: 24”  
    (61 cm ) 
    Min. for serviceTop: 0” (0 cm)
    Vent: 0” 
    (0 cm)
    Sides: 4” (10.2 cm) 
    Min. for service
    Clearances and Accessibility
    Notice:  Minimum clearances from combustible materi-
    als are stated on the data plate located on the front of the 
    water heater.
    •  The water heater is certified for installation on a
     combustible floor. 
    Important: If installing over carpeting, the carpeting must 
    be protected by a metal or wood panel beneath the water 
    heater. The protective panel must extend beyond the full 
    width and depth of the water heater by at least 3 inches 
    (7.62 cm) in any direction or if in a alcove or closet instal-
    lation, the entire floor must be covered by the panel. The 
    panel must be strong enough to carry the weight of the 
    heater when full of water.
    Figure 2 may be used as a reference guide to locate the 
    specific clearance locations. A minimum of 24 inches     
    (61 cm) of front clearance and 4 inches (10.2 cm) on each 
    side should be provided for inspection and service. 
    Figure 3A: 2” Condensation Trap Installation  
    						
    							7
    Condensate Drain Line
    All parts of the condensate trap are glued except for the 
    1/2” CPVC drain stem joint at the elbow (see figure 3A).  
    This assembly can be turned with the outlet of the tee 
    oriented as needed.
    Once orientation direction is decided, remove the unglued 
    joint from the elbow at the bottom and apply a suitable 
    cement to joint. Re-insert the joint fully and quickly into 
    the elbow making sure to orient it before the cement sets.  
    Connect the remaining piping and run the condensate drain 
    line to a suitable drain.
    Important:  Be sure the drain stem joint is inserted against 
    the stop in the elbow.  Failure to do so may result in 
    improper water heater operation.
    If required by local codes, install a condensate neutralizer 
    cartridge on the drain line (see figure 3B).
    The condensate drain line must be routed to a suitable  
    drain.  If no floor drain is available or the drain  is above 
    the level of the condensate line, install a condensate pump 
    that is resistant to the acidic condensate.  These pumps are 
    available from local distributors.  If the pump is not resistant 
    to acidic water, a condensate neutralizer must be used 
    ahead of the pump.
    When installing the drain line, note the following:
    •  Plastic pipe or tubing must be used to connect the 
    condensate drain to a suitable drain or condensate      
    pump. Do not use copper tubing, iron, or steel pipe for 
    the condensate drain line.
    • Condensate drain lines should be installed in condi-
    tioned areas only.  Drain lines installed in areas that are 
    subject to freezing temperatures should be wrapped 
    with a nationally recognized/listed heat tape and/or 
    approved insulation for freeze protection. Install per 
    manufacturer’s instructions.
    • Do not common drain with the temperature and pres-
    sure relief valve or the condensate line from  an air 
    conditioner evaporator coil.
    • Slope the condensate drain toward the inside floor 
    drain or condensate pump.
    • The condensate drain line and connection to the drain 
    piping must comply with all local codes.
    • Do not run the condensate line into the metal drain 
    pan. 
    VENT PIPE SYSTEM
    Carbon Monoxide Hazard
    Follow all instructions to locate and install 
    the vent pipe system.
    Instructions can be found in this manual, in 
    state or local codes (or the authority having 
    jurisdiction), or in the absence of such, the 
    National Fuel Gas Code, ANSI Z223.1, NFPA 
    54, Current Edition.  Canadian installations 
    must be performed in accordance with 
    CAN/CSA-B149.1, Current Edition.
    Failure to properly locate and install the 
    vent pipe system can result in death or 
    carbon monoxide poisoning.
    Venting
    This water heater has a direct vent system in which all air 
    for combustion is taken from the outside atmosphere and 
    all combustion products are discharged to the outdoors.  
    This water heater must be properly vented for removal 
    of exhaust gases to the outside atmosphere.  Correct 
    installation of the vent pipe system is mandatory for the 
    safe and efficient operation of this water heater and is an 
    important factor in the life of the unit.
    Vent pipe installation must be performed in accordance 
    with state and local codes, or in the absence of such, the 
    National Fuel Gas Code, NFPA 54, ANSI Z223.1-current 
    edition.  Canadian installations must be performed in 
    accordance with CAN/CSA-B149.1-current edition.  
    When replacing an existing Polaris
    ® unit, it is recommended 
    that the venting system be reviewed for compliance with 
    the requirements contained in this installation manual. If the  
    venting is not in compliance, it is recommended that the 
    appropriate changes be made to bring it into compliance. 
    Note: It is important that the factory-installed air inlet filter 
    be inspected periodically and cleaned if necessary. See 
    “Integrated Filter Installation, Preventive Maintenance”. 
    Note: if the vent system is not in compliance with the 
    current installation manual, the manufacturer reserves 
    the right to evaluate the installation prior to granting any 
    warranty on service claims.
    Important: Check to make sure the vent pipe is not 
    blocked in any way. 
    Note:  Do not common vent this water heater with any 
    other appliance.  Do not install in the same chase or 
    chimney with a metal or high-temperature plastic from 
    another gas or fuel burning appliance.
    Figure 3B: Condensate Drain 
    						
    							8
    Integrated Filter Installation
    When installing the adaptor rubber boot, note the following:
    •  Remove and discard the plastic cap from the outer 
    clamshell housing (see figure 4A).
    • To connect the heater to the air inlet, use the vent 
    adaptor rubber boot provided in the base skirt. The 
    adaptor rubber boot is designed for 3” venting (see 
    figure 4B). Note: If there is a need for 2” venting, then 
    use plastic pipe and fittings to transition down.
    • Loosen the hose clamp at the adaptor rubber boot and 
    slide the plastic piping into the adaptor rubber boot. 
    With piping in place, tighten the hose clamp. Install  
    a 3” x 3” x 2” drain/waste/vent fitting to trap airborne 
    particulates (see figure 4C). Note: If piping has been 
    previously cut with a saw, be sure to remove all burrs 
    and plastic shavings from the piping before installing.
    Preventive Maintenance
    The heater is designed to shut down if the pressure 
    switch senses that the air inlet vent or the exhaust vent 
    is restricted. In this case, the pressure switch will open 
    and the heater will generate a 2-flash code (see the 
    troubleshooting section). If troubleshooting section of 
    this manual indicates that there is a blockage, note the 
    following:
    •  Turn off the gas supply to the water heater at the 
    manual gas shut-off valve, and disconnect power to the 
    water heater.
    • To inspect the filter, loosen the hose clamp at the adap-
    tor rubber boot and slide the plastic pipe out and away 
    from the adaptor rubber boot (see figure 4C).
    • Remove the adaptor rubber boot containing the outer 
    clamshell housing by turning clockwise approximately 
    1/2” (30.5 cm) and pulling off of the internal clamshell 
    housing (see figure 4C).
    • Using your fingers or a small flat blade screwdriver,   
    remove the filter media from the outer clamshell hous-
    ing, handle carefully (see figure 4D).
    • To clean filter, lightly tap the back of the filter support 
    to dislodge any large debris. Smaller debris may be re-
    moved by using a vacuum cleaner. the filter media may 
    be cleaned by dipping the filter media into a solution of 
    warm soapy water and rinsing in clean water. Do not 
    scrub, allow to air dry before reinstalling. Filter media 
    may be cleaned on an average 2 to 3 times before 
    replacing with a new filter media is required.
    • Reinstall the filter media by doing the above steps in 
    reverse order.
    • Turn on the gas supply and reconnect power, refer to 
    the operating instructions on front of the water heater. 
    Verify proper operation of the water heater before   
    leaving.
    Note: The heater must never be operated without the 
    filter media installed.
    Figure 4B: Adaptor Rubber Boot
    Push On &
    Tighten Clamp
    Adaptor Rubber
    Boot
    Outer Clamshell
    Housing
    Figure 4C: Air Inlet Piping
    Hose Clamp
    3” Plastic Pipe
    Adaptor Rubber Boot
    Outer Clamshell Housing
    3” x 3” x 2” DWV Fitting
    Piped To
    External Air
    Supply
    Figure 4D: Filter Media
    Adaptor
    Rubber Boot
    Remove
    Filter Media Filter Media shown inside
    the Outer Clamshell Housing
    Outer Clamshell
    HousingNOTE: if found difficult to
    reattach the outer clamshell
    housing to the internal clamshell
    housing - apply a thin layer of silicone
    grease to the surface of the black rubber
    support of the Filter Media.
                             
    Figure 4A: Remove Plastic Cap
    Outer Clamshell
    Housing With Filter
    Base Skirt Gas Piping
    Remove
    Plastic Cap 
    						
    							9
    Vent Pipe Material
    The following plastic materials may be used for both the 
    combustion air inlet and exhaust outlet piping subject to 
    state and local codes:  
      •  Schedule 40 PVC
      •  Schedule 40 or 80 CPVC
      •  DWV Pipe is acceptable
    Note: Use only solid (not foam core) piping.
    Plastic pipe and fittings are available through most 
    plumbing suppliers. Always check the marking on the pipe 
    to make sure you are using the correct material.
    Important: Do not use vent elbows in this vent pipe instal-
    lation (see figure 5 below).
    Vent Pipe Installation
    The following guidelines should be followed when installing 
    the air inlet and exhaust outlet piping:
    •  Venting should be as direct as possible with a minimum 
    number of pipe fittings.
    •  Vent diameter must not be reduced unless specifically   
    noted in the installation instructions.
    •  All 2” horizontal vent piping must be sloped upward  
    1/4 inch per foot (21 mm per meter); (3” Piping must 
    slope upward at 1/8” per  foot) (10.5 mm per meter). 
    This will allow condensate to run back to the heater  
    and exit through the condensate trap.
    •  Support all horizontal pipe runs every four feet (1.2 m) 
    and all vertical pipe runs every six feet (1.8 m) or       
    according to local codes. 
    •  Vents run through unconditioned spaces where below  
    freezing temperatures are expected should be  properly 
    insulated to prevent freezing. Wrap the vent pipe with 
    approved insulation for freeze protection. Install per the 
    manufacturer’s instructions.
    •  An air intake filter is included with the unit and must be  
      installed according to the installation instructions 
      supplied with the filter.
    The combustion air inlet and exhaust outlet piping and 
    termination may be installed in one of the following type 
    terminations:
      1.   Standard Horizontal (2 Pipe) 
      2.   Alternate Horizontal (2 Pipe)
      3.   Vertical (2 Pipe) 
      4.    Concentric Vent - Through the Wall
      5.    Concentric Vent - Through the Roof
    All pipe, fittings, pipe cement, primers and procedures 
    must conform to American National Standard Institute and 
    American Society for Testing and Materials (ANSI/ASTM) 
    standards in the United States. This water heater has been 
    design certified by the Canadian Standards Association for 
    use with the specified (CSA) listed plastic vent pipe. All joints in the inlet and outlet piping must be properly 
    cemented. Size and cut all piping before cementing.
    1.   Cut the pipe end square and remove all ragged edges 
    and burrs.  Make sure the inside of the pipe is clean 
    and free of cuttings and loose dirt.  Chamfer the end 
    and apply primer to the fitting and pipe.  
    2.    Using a suitable grade of pipe cement, apply a moder-
    ate, even coat inside the fitting.  Apply a liberal amount 
    of cement to the outside of the pipe to socket depth. 
    Note: It is important to select the proper pipe cement for 
    the type of plastic pipe being used.
    3.   Assemble the parts quickly while the cement is             
    still  wet. Twist  the  pipe  1/4  turn  during  insertion                   
    and hold for 30 seconds.
    Vent Pipe Length
    Size the exhaust outlet and combustion air inlet pipes as 
    specified in Table 1. This table lists the maximum allow-
    able length in feet of the exhaust outlet and combustion air 
    inlet pipes as related to the number of required elbows and 
    the termination. The specified maximum lengths are for 
    the separate inlet and exhaust pipe systems and not the 
    combined length of both systems. Minimum pipe length is 
    6 feet (1.8 m) with one elbow per side.
    1.   Determine termination type and pipe size.
    2.   Determine number of elbows in exhaust pipe. Do not 
    include the elbows in the termination or the condensate 
    trap.  Corresponding number Indicates the maximum 
    length of exhaust pipe.
    3.   Determine number of elbows in inlet pipe.  Do not  
    include the elbows in the termination.  The correspond-
    ing number indicates the maximum length of inlet pipe.
    Pipe 
    Size in 
    Inches
    *2
    *2 *2 *2
    3
    3 3 352 
    (15.8)48 
    (14.6)40
    (12.2) 44
    (13.4)32
    (9.7)
    100
    (30.5) 125
    (38.1)36
    (11)
    44
    (13.4)40
    (12.2)36
    (11)32
    (9.7)28
    (8.5)24
    (7.3)
    48 
    (14.6) 52 
    (15.8)44
    (13.4)40
    (12.2)36
    (11)32
    (9.7)28
    (8.5)
    52 
    (15.8)48 
    (14.6)44
    (13.4)40
    (12.2)36
    (11)32
    (9.7)
    130
    (39.6)120
    (36.6)11 5
    (35)11 0
    (33.5)105
    (32)
    11 5
    (35)11 0
    (33.5)105
    (32)100
    (30.5)90
    (27.4) 95
    (28.9)
    120
    (36.6)11 5
    (35)11 0
    (33.5)105
    (32)100
    (30.5)95
    (28.9)
    125
    (38.1)120
    (36.6)11 5
    (35)11 0
    (33.5)105
    (32)100
    (30.5) Maximim allowable Length in Feet (Meters) of Exhaust and Air Inlet Pipe
    For Schedule 40 CPVC, OR PVC Pipe and Fittings
    Minimum length is 6 feet (1.8 m) per pipe with 1 elbow per side.
    *  3” pipe must be used for 175,000 BTU/Hr (51.29 kW) input and above.
    2 Inch pipe may be used with 100,000, 130,000 & 150,000 
    BTU/HR (29.3, 38, & 43.9 kW) input models only.
    Figure 5: Correct and Incorrect Pipe Fittings 
    						
    							10
    Vent Termination Locations
    The air inlet and exhaust outlet must be installed with the 
    following minimum clearances (see figure 6):
    •  Twelve inches (30 cm) above grade or maximum antici-
    pated snow level.
    •  Twelve inches (30 cm) from any opening through which 
    flue gases could enter the structure.
    •  Four feet (122 cm) horizontally and vertically from gas 
    or electric meters, gas regulators, dryer vents, vent 
    hoods, bathroom fan exhaust, attic fans and turbines.
    •  Two feet (61 cm) from an inside corner formed by two 
    exterior walls. 
    •  Two feet from porches, decks, overhangs and  other 
    obstructions.
    In addition to maintaining the minimum clearances , the 
    vent should terminate according to the following guidelines:1.    Use only 2 inch pipe or a 2 inch concentric vent 
    on the vent termination for 100,000 - 150,000 BTU/
    Hr models. Do not expose any 3” X 2” reducers or 
    bushings to outdoor ambient temperatures. 
    2.    The air inlet and exhaust outlet must not terminate 
    under a patio, deck or any covered area.
    3.   Do not terminate the vent near walkways or into alleys 
    or other publicly accessible areas.
    4.    Combustion air inlet termination and exhaust air termi-
    nation must be located in the same pressure zone.
    Figure 6: Minimum Clearances for Inlet/Outlet and Concentric Vent
    A.  12 in (30 cm) min. clearance above grade, 
    veranda, porch, deck, balcony, or maximum 
    anticipated snow level.
    B.  12 in (30 cm) min. clearance on top and side of 
    window or door that may be opened. Maintain a 
    36 in (91 cm) minimum clearance below a window 
    or door that may be opened.
    C.  Clearance to permanently closed window.**
    D.  12 in (30 cm) min vertical clearance to ventilated 
    soffit located above the terminal within a horizontal  
    distance of 2 ft (61 cm) from the center line of the  
    terminal.
    E.  12 in (30 cm) min. clearance to unventilated soffit.
    F.  Clearance to outside corner **
    G.  2 ft (61 cm) clearance to inside corner formed by 
    two exterior walls.
    H.  4 ft (122 cm) clearance to each side of center line 
    extending above meter/regulator assembly.
    I.  4 ft (122 cm) clearance to service regulator vent 
    outlet.
    J.  12 in (30 cm) clearance to nonmechanical air 
    supply inlet to building or the combustion air inlet 
    to any other appliance.
    K.  3 ft (91 cm) above if within 10 ft (3 m) horizontally of 
    mechanical air supply inlet.
    **Clearance in accordance with local installation codes and the requirements of the gas supplier. 
    A.  12 in (30 cm) min. clearance above grade,    
      veranda, porch, deck, balcony, or maximum    
      anticipated snow level.
    B.  12 in (30 cm) min. clearance on top and side of  
      window or door that may be opened. Maintain         
      a 36 in (91 cm) minimum clearance below a    
      window or door that may be opened.
    C.  Clearance to permanently closed window.**
    D.  12 in (30 cm) min vertical clearance to ventilated  
      soffit located above the terminal within a horizontal  
      distance of 2 ft (61 cm) from the center line of the  
     terminal.
    E.  12 in (30 cm) min. clearance to unventilated soffit.
    F.  Clearance to outside corner. **
    G.  2 ft (61 cm) clearance to inside corner formed by  
      two exterior walls.
    H.  3 ft (91 cm) within a height 15 ft (4.57 m) above the  
     meter/regulator assembly.
    I.  4 ft (122 cm) clearance to service regulator vent outlet.
    J.  12 in (30 cm) clearance to nonmechanical air  
      supply inlet to building or the combustion air inlet to  
      any other appliance.
    K.  6 ft (1.83 m) clearance to mechanical air supply inlet. US Installations Canadian Installations 
    						
    All American Water Heater manuals Comments (6)

    Related Manuals for American Water Heater Polaris High Efficiency Commercial Gas Water Heater PCG3 User Manual