Page 11
11 Page 2. Direct-vent conversion kit: 9007667005 (TK-TV10) This kit can be used to convert the water heater from a single vent system to a direct- vent (double vent) (or sealed combustion) system with a 3 in. (76 mm) intake. Install this conversion kit in accordance with the installation instructions and any applicable codes. The pipe cover protects the plumbing pipes to the water heater from unexpected adjustments. This pipe cover is fixed to the bottom of the water heater, which hides...
Page 12
12 Page WARNING DO NOT adjust any DIPswitches on the upper bank for the 510 (T-D2) model. NOTE: The dark squares indicate the direction the DIPswitches should be set to. Installation Installation Manual 110 (T-KJr2) and 310 (T-K4) models Altitude0 to 2,000 ft. (DEFAULT)2,000 to 4,000 ft.4,000 to 6,000 ft. Switch No. 3OFFONOFF Switch No. 4OFFOFFON ON8 7 6 5 4 3 2 1ON 8 7 6 5 4 3 2 1ON 8 7 6 5 4 3 2 1 510 (T-D2) model (Left bank of dipswitches) Altitude0 to 2,000 ft. (DEFAULT)2,000 to 4,000 ft.4,000 to...
Page 13
13 Page VENTING INSTRUCTIONS -General- The water heater must be vented in accordance with the section “Venting of Equipment" of the current edition of the National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the United States and/or Section 8 of the B149.1 Natural Gas and Propane Installation Code in Canada, as well as applicable local building codes. The manufacturer recommends the NovaVent line. However, the following are also UL listed manufacturers: ProTech Systems Inc. (FasNSeal),...
Page 14
14 Page -Exhaust venting- For the 110 Indoor (T-KJr2-IN), 310 Indoor (T-K4-IN), and 510 Indoor (T-D2-IN) models This is a Category III appliance and must be vented accordingly. The vent system must be sealed airtight. All seams and joints without gaskets must be sealed with high heat resistant silicone sealant or UL listed aluminum adhesive tape having a minimum temperature rating of 350 °F (177 °C). For best results, a vent system should be as short and straight as possible. • This water heater...
Page 15
15 Page Venting Illustrations- For the 110 Indoor (T-KJr2-IN), 310 Indoor (T-K4-IN), and 510 Indoor (T-D2-IN) models For details of the optional items, refer to the Installation manual for each Optional item. Horizontal Installation with Direct-vent concentric termination Wall Direct-vent concentric termination Installation of Direct-vent conversion kit (TK-TV10) with a water heater Installation Installation Manual *Backflow preventer (Recommended for freezing weather conditions: 36 °F (2 °C) and...
Page 16
16 Page -Vent termination clearances- CanadaU.S.A Direct-vent and other than Direct-vent Direct- vent Other than Direct-vent AClearance above grade, veranda, porch, deck, or balcony1 foot1 foot1 foot B Clearance to window or door that may be opened3 feet1 foot 4 feet from below or side opening. 1 foot from above opening. CClearance to permanently closed window*** D Vertical clearance to ventilated soffit located above the vent terminator within a horizontal distance of 2 feet (61cm) from the...
Page 17
17 Page -For sidewall terminations- -For rooftop terminations- For multiple sidewall exhaust terminations (e.g. multi- unit systems), an exhaust termination must be at least 1 ft. (305mm) away from another exhaust termination. An exhaust termination must also be at least 2 ft. (610 mm) away from an inside corner. (If the adjacent wall is less than 2 ft. (610 mm) of length, the minimum required distance away from the inside corner will be equal to the length of that adjacent wall.) For...
Page 18
18 Page GAS SUPPLY AND GAS PIPE SIZING -General- • The minimum and maximum inlet gas pressures are: • Inlet gas pressures that fall outside the range of values listed above may adversely affect the performance of the water heater. These pressures are measured when the water heater is in full operation. • Inlet gas pressure must not exceed the above maximum values; gas pressure above the specified range will cause dangerous operating conditions and damage to the unit. • Until testing of the main gas...
Page 19
19 Page -Natural Gas Supply Piping- Maximum delivery capacity of cubic feet of gas per hour of IPS pipe carrying Natural Gas with 0.60 specific gravity Based on pressure drop of 0.5" W.C. Based on energy content of 1,000 BTU/Cubic ft.: The water heater requires 140 Cubic ft./hr for the 110 (T-KJr2) model, 190 Cubic ft./hr for the 310 (T-K4) model, and 199 Cubic ft./hr for the 510 (T-D2) model. -Propane (LP) Supply Piping- Maximum Capacity of Propane (LP) Based on 11” W.C. supply pressure at a...
Page 20
20 Page -Measuring inlet gas pressure- The water heater cannot perform properly without sufficient inlet gas pressure. Below are instructions on how to check the inlet gas pressure. THIS IS ONLY TO BE DONE BY A LICENSED PROFESSIONAL. WATER CONNECTIONS All pipes, pipe fittings, valves and other components, including soldering materials, must be suitable for potable water systems. 1. A manual shutoff valve must be installed on the cold water inlet to the water heater between the main water supply...