American Water Heater HeavyDuty Surface Thermostat Commercial Electric STCE3150 80 119 User Manual
American Water Heater HeavyDuty Surface Thermostat Commercial Electric STCE3150 80 119 User Manual
Here you can view all the pages of manual American Water Heater HeavyDuty Surface Thermostat Commercial Electric STCE3150 80 119 User Manual. The American Water Heater manuals for Electric Heater are available online for free. You can easily download all the documents as PDF.
Page 21
21 THERMOSTAT SETTINGS - ELECTRONIC CONTROLS These models are equipped with an electronic control system. The control system senses temperature from a factory installed Immersion Temperature Probe (see Figure 2). The “Operating Set Point” is adjusted to control water temperature. This is an adjustable user setting in the control system’s “Temperatures Menu.” This and all control system menus are accessed through the UIM (User Interface Module - see Figure 8)...
Page 22
22 Menu: The left Operational Button is pressed to enter the Main Menu where all control system menus are accessed. See Table 9. for a list of control system menus. Help: The right Operational Button is pressed to access instructions and explanations for user settings, Operating States, Status Icons, manufacturer’s web address, technical support phone number and service agent contact information. Day/Time/Operating Mode: The current time and day are also displayed on the Desktop Screen....
Page 23
23 TEMPERATURES MENU Operating Set Point User adjustable setting 90°F to 190°F range; factory default is 120°F. When the water temperature sensed by the control system from the immersion Temperature Probe reaches the Operating Set Point the control system will end the heating cycle. A call for heat will be activated again when the water temperature drops below the Operating Set Point minus the 1st Differential Setting. Example: Operating Set Point is 120°F, the 1st Differential...
Page 24
24 Differential Settings Adjustable user setting(s) 1°F to 20° range; factory default is 2°F. The water heaters covered in this Instruction Manual will have 3, 6 or 9 heating elements. Each group of 3 heating elements is one “Bank” of heating elements. Heating elements are energized in Banks of 3. Each Bank of heating elements will have a Differential Setting associated with it. Differential Settings are located in the Temperatures Menu. There is a 1st Differential Setting on all...
Page 25
25 HEATER STATUS MENU This menu displays non adjustable operational information. This menu contains more information that can be displayed on one screen of the LCD display. Use the Up & Down Buttons to navigate to the bottom of this menu. Top of Menu Bottom of Menu Status Displays the current Operating State of the control system. IE: Heating, Standby, Fault see Table 8. Element Banks On Displays the current number of heating element Banks the control system has energized. Each Bank...
Page 26
26 “Normal Operation All Day” - “Economy Mode All Day” and “Normal Operation Between.” Only one Operating Mode can be active, the factory default is Normal Operation All Day. Normal Operation All Day: When this operating mode is active the normal Operating Set Point is used for the entire day. Economy Mode All Day: When this operating mode is active the Economy Set Point is used for the entire day.Normal Operation Between: When this operating mode is active there will also be start and...
Page 27
27 ECONOMY MODE SETTINGS Time Clock Settings ACTIONDISPLAY From the Desktop Screen navigate to the Economy Mode Setup menu. Use the Up/Down buttons to select (highlight in black) Current Time sub menu. Press the Operational Button underneath “CHANGE” to enter the Current Time sub menu. Use the Up/Down buttons to select the “Weekday” setting. Press the Operational Button underneath “CHANGE” to activate the adjustment mode for this setting. Press the Up and Down...
Page 28
28 ECONOMY MODE SETTINGS Daily Operating Mode Settings ACTIONDISPLAY Economy Mode All Day: From the Economy Mode Setup menu use the Up/Down buttons to select (highlight in black) the Daily sub menu for “Sun.” Press the Operational Button underneath “CHANGE” to enter this menu. Use the Up/Down buttons to select (highlight in black) the “Economy Mode All Day” setting. Press the Operational Button underneath “SELECT” to change from the factory default Normal Operation All Day...
Page 29
29 ALARM OUTPUT SETUP MENU Permits user to set the condition (from a list of options) for when the CCB’s integral alarm output relay will be energized. Alarm relay connections (common, normally open, normally closed) are located on the J3 terminal strip on the CCB. Alarm output relay contacts are capable of switching 1 amp maximum at 120 VAC. The alarm relay operates in the background according to the settings in this menu and is not capable of disabling water...
Page 30
30 Elapsed Time Total accumulated time the control system (water heater) has been energized. Total Heating Time Total accumulated time the control system has been in the heating mode. IE: any heating elements have been energized. Bank # Cycles Total accumulated count of heating cycles for each Bank of heating elements. Bank # On Time Total accumulated heating on time for each Bank of heating elements. CCB Version Software version for Central Control Board. UIM Version Software version for...