Home
>
American Water Heater
>
Gas Heater
>
American Water Heater Heavy Duty Commercial Gas BCG3 User Manual
American Water Heater Heavy Duty Commercial Gas BCG3 User Manual
Here you can view all the pages of manual American Water Heater Heavy Duty Commercial Gas BCG3 User Manual. The American Water Heater manuals for Gas Heater are available online for free. You can easily download all the documents as PDF.
Page 11
11 INSULATION BLANKET Do not obstruct water heater air intake with insulating blanket. Gas and carbon monoxide detectors are available. Install water heater in accordance with the instruction manual. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Breathing Hazard - Carbon Monoxide Ga s Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose...
Page 12
12 Breathing Hazard - Carbon Monoxide Gas Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Under no circumstances should the input exceed the rate shown on the water heater ’s rating label. Overfiring could result in damage to the water heater and sooting. Gas and carbon monoxide detectors are available. Installations above 2000 feet (610 meters) require replacement of burner orifices in accordance with current edition of...
Page 13
13 4. When installing multiple water heaters in the same gas supply system it is recommended that individual positive lock-up gas pressure regulators be installed at each unit. POWER SUPPLY The water heaters covered in this manual require a 120 VAC, 1Ø (single phase), 60Hz, 15 amp power supply and must also be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/...
Page 14
14 HOT WATER OUTLET TO TA NK INLET CHECK VA LVE MIXING VA LVE COLD WA TER INLET TEMPERED WA TER OUTLET 12” TO 15” (30-38 cm) CHECK VA LVE FIGURE 10. DISHWASHING MACHINES All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch (103 kPa and 173 kPa). Flow pressures above 25 pounds per square inch (173 kPa), or below 15 pounds per square inch (103 kPa),...
Page 15
15 No valve or other obstruction is to be placed between the Temperature-Pressure Relief Valve and the tank. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable...
Page 16
16 DIRECT VENT APPLIANCES Appliances installed in a Direct Vent configuration that derive all air for combustion from the outdoor atmosphere through sealed intake air piping are not factored in the total appliance input Btu/ hr calculations used to determine the size of openings providing fresh air into confined spaces. EXHAUST FANS Where exhaust fans are installed, additional air shall be provided to replace the exhausted air. When an exhaust fan is installed in the same space with a...
Page 17
17 MULTIPLE HEATER MANIFOLD Figure 13 and tables on pages 19 and 20 should be used for horizontally manifolding two or more heaters. FIGURE 13. FRESH AIR OPENINGS FOR CONFINED SPACES The following instructions shall be used to calculate the size, number and placement of openings providing fresh air for combustion, ventilation and dilution in confined spaces. The illustrations shown in this section of the manual are a reference for the openings that provide...
Page 18
18 When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches. AIR FROM OTHER INDOOR SPACES FIGURE 18. The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 18. Each opening shall...
Page 19
19 TYPE B GAS VENT Multiple Gas Fired Tank-Type Heaters When venting multiple tank type heaters using Type B vent pipe, follow the installation diagram (Figure 13) and tables below which give sizing and data based upon NFPA 54/ANSI Z223. TABLE 6. TECHNICAL DATA VENTING MODEL (A)BCG370T120 Input: 120,000 Btuh \ Total Vent Height (Feet)Draft Hood: 5” 6810 15203050100 Input Btuh Rise Vent Connector...