American Water Heater Condensing UltraLow NOx Indoor 120000 BTU Liquid Propane GT140PIH User Manual
American Water Heater Condensing UltraLow NOx Indoor 120000 BTU Liquid Propane GT140PIH User Manual
Here you can view all the pages of manual American Water Heater Condensing UltraLow NOx Indoor 120000 BTU Liquid Propane GT140PIH User Manual. The American Water Heater manuals for Water Heater are available online for free. You can easily download all the documents as PDF.
Page 11
11 Page Installation Installation Manual -Exhaust vent (ABS, PVC, CPVC, or polypropylene vent)- The Indoor model can be vented with ABS, PVC, CPVC, or polypropylene (temperature rated up to at least 149 °F) Vent material certified to ULC S636 standards is recommended in the USA In Canada, plastic venting must be certified to ULC S636 standards ItemMaterialUnited States Canada Exhaust pipe and Fittings Schedule 40 PVC ANSI/ASTM D1785 ULC S636 Certified Materials Only PVC-DWV...
Page 12
12 Page Installation Installation Manual -DIPswitch settings for Vent length- Vent lengthTwo-pipe and Single pipe 5 to 50 ft. (DEFAULT)No 6 : ON No 7 : OFF 51 to 100 ft.No 6 : OFF No 7 : OFF OFF ON12 34 56 78910 OFF ON1 2 34 56 78910 Vent lengthTwo-pipe 5 to 20 ft. (DEFAULT)No 6 : ON No 7 : OFF 21 to 40 ft.No 6 : OFF No 7 : OFF 41 to 70 ft.No 6 : ON No 7 : ON OFF ON1 2 34 56 78910 OFF ON1 2 34 56 78910 OFF ON1 2 34 56 78910 Set DIPswitches shown in the tables...
Page 13
13 Page Installation Installation Manual -Intake and Exhaust Venting Illustrations- Typical installations using ABS, PVC, CPVC, or polypropylene vent 2 inch vent installation For details of the optional items, refer to the Installation manual for each optional item Single pipe with room-air intake Termination Hanger 1. Connect a 3" elbow directly on the intake vent collar of the water heater 2. Connect a 3" x 2" reducer directly on the exhaust vent collar of the...
Page 14
14 Page Installation Installation Manual 3 inch vent installation 1. Connect a 3" elbow directly on the intake vent collar of the water heater 2. Connect a 3" coupling directly on the exhaust vent collar of the water heater Make sure the couplings engage the o-rings installed in the intake and exhaust vent collars 3. Connect a 3" straight pipe to the coupling Exhaust vent collar (Female) 3" straight pipe 3" coupling(included) Intake vent...
Page 15
15 Page Installation Installation Manual Two-pipe, direct-ventSingle pipe with room-air intake Terminations WallHanger Hanger Roof Roof flashing Fire stop Termination WallHanger Roof flashing Fire stop Roof Refer to pages 17 and 19 for clearance information Examples of installation of 3 inch & 4 inch vent
Page 16
16 Page Installation Installation Manual Vent connections for two-pipe 4" stainless steel vent straight pipe Exhaust vent collar (Female)Intake vent collar(Female) 4" stainless steel vent straight pipe Exhaust vent collar (Female) 4" stainless steel vent straight pipe Intake vent collar(Female) 4" elbow with bird screen 1. Connect a 4" stainless steel vent straight pipes directly on the exhaust vent collar of the water heater 2. Connect a 4" elbow...
Page 17
17 Page Installation Installation Manual -Vent termination clearances- CanadaUS A Direct-vent and other than Direct-vent Direct- vent Other than Direct-vent AClearance above grade, veranda, porch, deck, or balcony1 foot1 foot1 foot B Clearance to window or door that may be opened3 feet1 foot 4 feet from below or side opening 1 foot from above opening CClearance to permanently closed window*** D Vertical clearance to ventilated soffit located above the vent terminator within a...
Page 18
18 Page Installation Installation Manual For multiple sidewall exhaust terminations, an exhaust termination must be at least 1 ft (305mm) away from another exhaust termination An exhaust termination must also be at least 2 ft (610 mm) away from an inside corner (If the adjacent wall is less than 2 ft (610 mm) of length, the minimum required distance away from the inside corner will be equal to the length of that adjacent wall)Exhaust terminationInsidecorner 1 ft(305...
Page 19
19 Page Installation Installation Manual Exhaust and/or direct-vent sidewall terminations should be at least 2 ft (610 mm) away from an opposite surface/ wall Do not place the termination directly in front of an opening into a building Intake airExhaust gas 3 ft (914 mm) min. BA 2 ft (610 mm) min. Intake air BB A Exhaust Gas A:Exhaust terminations must be at least 1 ft (305 mm) away from any obstructions B:Intake terminations must be at least 1 ft (305 mm) away from any...
Page 20
20 Page Installation Installation Manual GAS SUPPLY AND GAS PIPE SIZING -General- • The minimum and maximum inlet gas pressures are: • Inlet gas pressures that fall outside the range of values listed above may adversely affect the performance of the water heater These pressures are measured when the water heater is in full operation • Inlet gas pressure must not exceed the above maximum values; gas pressure above the specified range will cause dangerous operating conditions and damage to the...